Operating Instructions
Vector Control
du/dt-Filter
dv/dt filter
Änderungen von Funktionen, technischen Daten, Normen, Zeichnungen und Parametern vorbehalten.
We reserve the right to make changes to functions, technical data, standards, drawings and parameters.
Inhaltsverzeichnis / Contents
2 BESCHREIBUNG ................................................................................................ 6
3 MONTAGE / ANSCHLUß.................................................................................... 8
4 INBETRIEBSETZEN ......................................................................................... 18
2 DESCRIPTION .................................................................................................. 23
4 START-UP ......................................................................................................... 35
SIEMENS AG 6SE7087-6CX87-1FD0
SIMOVERT MASTERDRIVES Betriebsanleitung / Operating Instructions 3
Definitionen und Warnungen
GEFAHR im Sinne der Dokumentation bzw. der Warnhinweise auf dem Produkt
selbst bedeutet, daß Tod, schwere Körperverletzung oder erheblicher
Sachschaden eintreten werden, wenn die entsprechenden
Vorsichtsmaßnahmen nicht getroffen werden.
WARNUNG im Sinne der Dokumentation bzw. der Warnhinweise auf dem Produkt
selbst bedeutet, daß Tod, schwere Körperverletzung oder erheblicher
Sachschaden eintreten können, wenn die entsprechenden
Vorsichtsmaßnahmen nicht getroffen werden.
VORSICHT im Sinne der Dokumentation bzw. der Warnhinweise auf dem Produkt
selbst bedeutet, daß leichte Körperverletzung oder Sachschaden
eintreten können, wenn die entsprechenden Vorsichtsmaßnahmen
nicht getroffen werden.
HINWEIS im Sinne der Dokumentation ist eine wichtige Information über das
Produkt oder den jeweiligen Teil der Dokumentation, auf die besonders
aufmerksam gemacht werden soll.
6SE7087-6CX87-1FD0 Siemens AG
4 Betriebsanleitung / Operating Instructions SIMOVERT MASTERDRIVES
Definitionen und Warnungen
SIEMENS AG 6SE7087-6CX87-1FD0
SIMOVERT MASTERDRIVES Betriebsanleitung / Operating Instructions 5
Beschreibung
2 Beschreibung
Beim Betrieb an Frequenzumrichtern wird die Wicklungsisolation von
Motoren einer höheren Spannungsbelastung ausgesetzt als beim
Betrieb am sinusförmigen Netz. Ursache sind die periodischen
Schaltvorgänge im Umrichter, die zu hohen Spannungssteilheiten und
hohen transienten Spannungsspitzen an der Motorwicklung führen.
Diese erhöhte Spannungsbelastung der Motorwicklung kann abhängig
von der Betriebsspannung und vom Motortyp die Lebensdauer der
Motorwicklung erheblich verkürzen.
Das du/dt-Filter der Frequenzumrichterreihe SIMOVERT
MASTERDRIVES schützt die Motorisolation durch Begrenzung der
Spannungssteilheiten und der transienten Spannungsspitzen an der
Motorwicklung auf unkritische Werte:
♦ Spannungssteilheit du/dt ≤ 500 V / µs
♦ transiente Spannungsspitzen
Ûtypisch ≤ 1000 V für 500 V ≤ UN (3AC) ≤ 575 V
675 V ≤ UN (DC) ≤ 780 V
Ûtypisch ≤ 1250 V für 660 V ≤ UN (3AC) ≤ 690 V
890 V ≤ UN (DC) ≤ 930 V
Gleichzeitig reduziert das du/dt-Filter bei langen Motorleitungen die
Ladestromspitzen, die den Umrichter durch das periodische Umladen
der Kabelkapazitäten zusätzlich belasten.
Das du/dt-Filter ist einsetzbar mit der regelungstechnischen
Ausprägung
♦ VC (Vector Control)
der Frequenzumrichterreihe SIMOVERT MASTERDRIVES.
Der Einsatz des du/dt-Filters bringt keine Einschränkungen mit sich im
Hinblick auf:
♦ maximalen Umrichterausgangsstrom
♦ maximale Umrichterausgangsspannung und
♦ regelungstechnische Eigenschaften des Umrichters.
Beschränkungen existieren nur in folgenden Punkten:
♦ Die zulässige Pulsfrequenz ist begrenzt auf Werte ≤ 3 kHz (siehe
Kapitel "Inbetriebsetzen")
♦ Die zulässige Motorleitungslänge ist begrenzt (siehe Abschnitt
"Zulässige Motorleitungslängen")
♦ Der Umrichter mit du/dt-Filter ist nur bedingt leerlauffest (siehe
Kapitel "Inbetriebsetzen")
Das du/dt-Filter ist geeignet für den Einsatz in
♦ geerdeten Netzen (TN- und TT-Netze)
♦ ungeerdeten Netzen (IT-Netze)
(Ausnahmen: 6SE70 _ _ - _ _ B _ _ -1FD0 und
6SE70 _ _ - _ _ C _ _ -1FD0 mit Erzeugnisstand A gemäß Abschnitt
„Bauformen B und C“)
6SE7087-6CX87-1FD0 Siemens AG
6 Betriebsanleitung / Operating Instructions SIMOVERT MASTERDRIVES
Beschreibung
SIEMENS AG 6SE7087-6CX87-1FD0
SIMOVERT MASTERDRIVES Betriebsanleitung / Operating Instructions 7
Montage / Anschluß
3 Montage / Anschluß
Bei der Montage ist generell zu beachten:
♦ Das du/dt-Filter ist in unmittelbarer Nähe des Umrichters zu
plazieren.
♦ Die Verbindungsleitungen zum Zwischenkreis des Umrichters
(Verbindung zwischen den C/D-Anschlüssen von Filter und
Umrichter) sind so kurz wie möglich zu halten (max. Leitungslänge
siehe Tabelle 3-1).
♦ Eine ausreichende Entwärmung des du/dt-Filters ist
sicherzustellen (max. Verlustleistung siehe Tabelle 5-1). Die
Verlustleistung wird durch freie Konvektion abgeführt.
Die mechanische Ausführung des du/dt-Filters, die Art der Befestigung
sowie die maximale Leitungslänge zwischen C/D-Anschlüssen von
Umrichter und du/dt-Filter sind in Tabelle 3-1 angegeben.
6SE7087-6CX87-1FD0 Siemens AG
8 Betriebsanleitung / Operating Instructions SIMOVERT MASTERDRIVES
Montage / Anschluß
3.1 Maßbilder
Abmessungen A B C D E F
du/dt-Filter [mm]
min. 100 mm
max 150
für Schraube M6
F Luftaustritt
SIEMENS
45
58
E
B
C
D
U1/L1 V1/L2 W1/L3
Leistungsanschlüsse
IN
Bolzen G
65
Leistungs-
schild
Warnschild
100 mm
A Lufteintritt
max 150
min.
für Schraube M6
SIEMENS AG 6SE7087-6CX87-1FD0
SIMOVERT MASTERDRIVES Betriebsanleitung / Operating Instructions 9
Montage / Anschluß
Abmessungen A B C D E F G
du/dt-Filter [mm]
6SE70 _ _ - _ _ E _ _ - 1FD0 53 153 970 1035 1050 1025 310
6SE70 _ 1 - _ _ S _ _ - 1FD0
bis 68 188 1350 1435 1450 1425 410
6SE70 _ 2 - _ _ S _ _ - 1FD0
E
SIEMENS
D
C/L+ D/L-
Abdeckung
Begrenzungsnetzwerk
Abdeckung
F
Drossel
Abdeckung
Erdungs-
bolzen
B Erdungs-
bolzen
0
10 180 50
270 97
für Schrauben M8
6SE7087-6CX87-1FD0 Siemens AG
10 Betriebsanleitung / Operating Instructions SIMOVERT MASTERDRIVES
Montage / Anschluß
Abmessungen A B C D E
Begrenzungsnetzwerk
für du/dt-Filter [mm]
360 E
270 130
für Schrauben M8
15
CB
C/L+ D/L- U2 V2 W2
10
Erdungsbolzen
Zwischenkreis für Schrauben M8
SIEMENS AG 6SE7087-6CX87-1FD0
SIMOVERT MASTERDRIVES Betriebsanleitung / Operating Instructions 11
Montage / Anschluß
Abmessungen Drossel A B C D E F G H J
für du/dt-Filter [mm]
6SE70_3- _ _ S _ _ -1FD0 458 356 416 133 435 155 194 M12 11
6SE70_4- _ _ S _ _ -1FD0 458 356 416 159 435 212 251 M12 11
6SE70_5- _ _ S _ _ -1FD0 533 410 470 186 565 170 207 M10 11
6SE70_6- _ _ S _ _ -1FD0 533 410 470 212 565 198 235 M10 14
6SE70_8- _ _ S _ _ -1FD0 608 470 540 217 650 198 245 M12 14
U1 V1 W1
A
Z
E
U2 V2 W2
Erdungs-
schraube
B F
C G
Durchgangsloch
für Schraube oder
Ansicht Z bis Wicklung
Gewinde
F
Bohrbild
H
6SE7087-6CX87-1FD0 Siemens AG
12 Betriebsanleitung / Operating Instructions SIMOVERT MASTERDRIVES
Montage / Anschluß
3.2 Anschluß
3.2.1 Bauformen B und C
WARNUNG Vertauschen der C/L+ -und D/L− -Anschlüsse führt zur Zerstörung von
Umrichter und du/dt-Filter.
Anschluß C/L+ des du/dt-Filters mit Anschluß C/L+ des Umrichters und
Anschluß D/L− des du/dt-Filters mit Anschluß D/L- des Umrichters
verbinden.
♦ Leitungslängen: so kurz wie möglich, maximal 3 m
♦ Leitung so legen, daß kein Kurz- oder Erdschluß durch
Isolationsversagen auftreten kann (Kurz- und Erdschlußsichere
Verlegung).
♦ Leitungsquerschnitte:
Bauform Querschnitte
AWG mm2
min. max. min. max.
B 14 10 1,5 4,0
C 10 10 4,0 4,0
AWG: Amerikanisches Drahtmaß
+
−
3M
SIEMENS AG 6SE7087-6CX87-1FD0
SIMOVERT MASTERDRIVES Betriebsanleitung / Operating Instructions 13
Montage / Anschluß
Anschluß C/L+ des du/dt-Filters mit Anschluß C/L+ des Umrichters und
Anschluß D/L− des du/dt-Filters mit Anschluß D/L- des Umrichters
verbinden.
♦ Leitungslängen: so kurz wie möglich, maximal 5 m
♦ Leitung so legen, daß kein Kurz- oder Erdschluß durch
Isolationsversagen auftreten kann (Kurz- und Erdschlußsichere
Verlegung).
♦ Leitungsquerschnitte:
Bauform Querschnitte Bohrung
AWG / MCM mm2 für
min. max. min. max. Schraube
E 4 1/0 16 50 M8
1- _ _ S 2 250 35 120 M10
2- _ _ S 1/0 250 50 120 M10
AWG: Amerikanisches Drahtmaß für Querschnitte < 120 mm2
MCM: Amerikanisches Drahtmaß für Querschnitte ≥ 120 mm2
3M
6SE7087-6CX87-1FD0 Siemens AG
14 Betriebsanleitung / Operating Instructions SIMOVERT MASTERDRIVES
Montage / Anschluß
WARNUNG Vertauschen der C/L+ -und D/L− -Anschlüsse führt zur Zerstörung von
Umrichter und du/dt-Filter.
Anschluß C/L+ des du/dt-Filters mit Anschluß C/L+ des Umrichters und
Anschluß D/L− des du/dt-Filters mit Anschluß D/L- des Umrichters
verbinden.
♦ Leitungslängen: so kurz wie möglich, maximal 8 m
♦ Leitung so legen, daß kein Kurz- oder Erdschluß durch
Isolationsversagen auftreten kann (Kurz- und Erdschlußsichere
Verlegung).
♦ Leitungsquerschnitte:
SIEMENS AG 6SE7087-6CX87-1FD0
SIMOVERT MASTERDRIVES Betriebsanleitung / Operating Instructions 15
Montage / Anschluß
+
−
3M
Umrichter Begrenzungsnetz-
werk
C/L+ U2/T1
D/L− V2/T2
W2/T3
C/L+ D/L−
du/dt-Filter
U2/ V2/ W2/
T1 T2 T3 Drossel
U1 U2 M
V1 V2 3AC
W1 W2
♦ Leitungsquerschnitte:
6SE7087-6CX87-1FD0 Siemens AG
16 Betriebsanleitung / Operating Instructions SIMOVERT MASTERDRIVES
Montage / Anschluß
U1 V1 W1
6SE7031-2HS87-1FD0 6SE7031-2HS87-1FE0
6SE7031-7HS87-1FD0 6SE7031-7HS87-1FE0
6SE7032-3HS87-1FD0 6SE7032-3HS87-1FE0
U2 V2 W2
6SE7033-0HS87-1FD0 6SE7033-0GS87-1FE0
6SE7033-5HS87-1FD0 6SE7033-5GS87-1FE0
6SE7034-5HS87-1FD0 6SE7034-5GS87-1FE0
U1 V1 W1 6SE7035-7HS87-1FD0 6SE7035-7GS87-1FE0
L1 L2 L3
C/L+ 6SE7036-5HS87-1FD0 6SE7036-5GS87-1FE0
du/dt-Filter 6SE7038-6HS87-1FD0 6SE7038-6GS87-1FE0
D/L−
U2 V2 W2
T1 T2 T3 Tabelle 3-7 Zuordnung Zusatzdrossel und du/dt-Filter
M
3AC
SIEMENS AG 6SE7087-6CX87-1FD0
SIMOVERT MASTERDRIVES Betriebsanleitung / Operating Instructions 17
Inbetriebsetzen
4 Inbetriebsetzen
Das du/dt-Filter ist für den Betrieb mit einer Pulsfrequenz fp = 3 kHz
ausgelegt und kann mit Pulsfrequenzen fp ≤ 3 kHz betrieben werden.
Hierzu ist im Rahmen der Antriebseinstellung des Umrichters
(P060 = 5) der Parameter P068 = 2 zu setzen. Damit wird der
Parameter P340 (Pulsfrequenz) automatisch auf Werte ≤ 3 kHz
begrenzt.
Die Antriebseinstellung muß anschließend mit P115 = 1, 2 oder 3
beendet werden, damit die Einstellungen wirksam werden.
WARNUNG Der Betrieb mit einer höheren Pulsfrequenz als 3 kHz ist nicht zulässig
und führt zur Zerstörung des du/dt-Filters.
Wechselrichter mit du/dt-Filter sind grundsätzlich nur mit
angeschlossenem Motor zu betreiben!
Sollte es zu Inbetriebsetzungszwecken unvermeidbar sein, den
Wechselrichter mit du/dt-Filter und Motorleitung, jedoch ohne Motor zu
betreiben, so ist unbedingt zu beachten:
♦ Der Wechselrichter muß mit U/f-Steuerung betrieben werden
(P100 = 1); die Vektorregelungsarten (P100 = 3, 4, 5) dürfen auf
keinen Fall angewählt werden.
♦ Die Motornennfrequenz (P107) muß auf > 30 Hz eingestellt werden.
♦ Die Spannungsanhebung (P325) muß auf < 5 % eingestellt werden.
Bei Nichtbeachtung können die Begrenzungsnetzwerke der du/dt-Filter
zerstört werden!
6SE7087-6CX87-1FD0 Siemens AG
18 Betriebsanleitung / Operating Instructions SIMOVERT MASTERDRIVES
Technische Daten
5 Technische Daten
Betriebstemperatur 0 °C bis + 40 °C
Lagerungstemperatur − 25 °C bis + 70 °C
Transporttemperatur − 25 °C bis + 70 °C
Umweltklasse nach DIN IEC 721 Teil 3-3/04.90
♦ Feuchte 3K3
♦ Schadstoffbeanspruchung 3C2
Schutzklasse I nach DIN VDE 0160 Teil 1/05.82
IEC 536/1976
Mechanische Festigkeit nach DIN IEC 68-2-67/06.90
♦ im Betrieb Schärfegrad 12
♦ bei Transport Schärfegrad 22
Brennbarkeit FV1 nach DIN VDE 0304 Teil 3 / 09.85
V1 UL94
Tabelle 5-2
SIEMENS AG 6SE7087-6CX87-1FD0
SIMOVERT MASTERDRIVES Betriebsanleitung / Operating Instructions 19
Technische Daten
6SE7087-6CX87-1FD0 Siemens AG
20 Betriebsanleitung / Operating Instructions SIMOVERT MASTERDRIVES
Definitions and Warnings
DANGER For the purpose of this documentation and the product warning labels,
"Danger" indicates death, severe personal injury or substantial property
damage will result if proper precautions are not taken.
WARNING For the purpose of this documentation and the product warning labels,
"Warning" indicates death, severe personal injury or property damage
can result if proper precautions are not taken.
CAUTION For the purpose of this documentation and the product warning labels,
"Caution" indicates that minor personal injury or material damage can
result if proper precautions are not taken.
SIEMENS AG 6SE7087-6CX87-1FD0
SIMOVERT MASTERDRIVES Betriebsanleitung / Operating Instructions 21
Definitions and Warnings
NOTE This documentation does not purport to cover all details on all types of
the product, nor to provide for every possible contingency to be met in
connection with installation, operation or maintenance.
Should further information be desired or should particular problems
arise which are not covered sufficiently for the purchaser’s purposes,
the matter should be referred to the local Siemens sales office.
The contents of this documentation shall not become part of or modify
any prior or existing agreement, commitment or relationship. The sales
contract contains the entire obligation of Siemens AG. The warranty
contained in the contract between the parties is the sole warranty of
Siemens. Any statements contained herein do not create new
warranties or modify the existing warranty.
6SE7087-6CX87-1FD0 Siemens AG
22 Betriebsanleitung / Operating Instructions SIMOVERT MASTERDRIVES
Description
2 Description
When motors are fed from frequency converters, their winding
insulation is subject to higher voltage stressing than when fed directly
online from a sinusoidal source. The reason for this are the periodic
switching operations in the drive converter, which result in high voltage
gradients (voltage rate of rise) and high transient voltage spikes at the
motor winding. This increased voltage stressing of the motor winding
can significantly reduce the motor winding lifetime, depending on the
actual operating voltage and the motor type.
The dv/dt filter of the SIMOVERT MASTERDRIVES drive converters
protects the motor insulation by limiting the voltage gradients (voltage
rate of rise) and the transient voltage spikes at the motor winding to
uncritical values:
♦ Voltage gradient dv/dt ≤ 500 V / µs
♦ Transient voltage spikes
Vtypical ≤ 1000 V for 500 V ≤ VN (3-ph. AC) ≤ 575 V
675 V ≤ VN (DC) ≤ 780 V
Vtypical ≤ 1250 V for 660 V ≤ VN (3-ph. AC) ≤ 690 V
890 V ≤ VN (DC) ≤ 930 V
Further, the dv/dt filter reduces, for long motor cables, the charging
current spikes, which additionally stress the drive converter due to the
periodic re-charging of the cable capacitances.
The dv/dt filter can be used with the following control versions
♦ VC (Vector Control)
of the SIMOVERT MASTERDRIVES frequency drive converter series.
When a dv/dt filter is used, it does not place any restrictions regarding:
♦ maximum drive converter output current
♦ maximum drive converter output voltage, and
♦ the control characteristics of the drive converter.
Restrictions only occur as far as the following are concerned:
♦ The permissible pulse frequency is limited to ≤ 3 kHz (refer to
Section “Start-up”)
♦ The permissible motor cable length is limited (refer to Section
“Permissible motor cable lengths”)
♦ The drive converter with dv/dt filter is only conditionally no-load
proof (refer to Chapter “Start-up”)
The dv/dt filter is suitable for use with
♦ grounded supply networks (TN- and TT line networks)
♦ ungroudned line networks (IT line networks)
(Exceptions: 6SE70 _ _ - _ _ B _ _ -1FD0 and
6SE70 _ _ - _ _ C _ _ -1FD0, Prod. State A according to Section
“Size B and C”).
SIEMENS AG 6SE7087-6CX87-1FD0
SIMOVERT MASTERDRIVES Betriebsanleitung / Operating Instructions 23
Description
6SE7087-6CX87-1FD0 Siemens AG
24 Betriebsanleitung / Operating Instructions SIMOVERT MASTERDRIVES
Installation and Connection
SIEMENS AG 6SE7087-6CX87-1FD0
SIMOVERT MASTERDRIVES Betriebsanleitung / Operating Instructions 25
Installation and Connection
min. 100 mm
max 150
for M6 bolt
F Air discharge
SIEMENS
45
58
E
B
C
D
U1/L1 V1/L2 W1/L3
Power connections
IN
Studs G
Rating
65
plate
Warning
label
100 mm
A Air entry
max 150
min.
for M6 bolt
6SE7087-6CX87-1FD0 Siemens AG
26 Betriebsanleitung / Operating Instructions SIMOVERT MASTERDRIVES
Installation and Connection
Dimensions A B C D E F G
dv/dt filters [mm]
6SE70 _ _ - _ _ E _ _ - 1FD0 53 153 970 1035 1050 1025 310
6SE70 _ 1 - _ _ S _ _ - 1FD0
to 68 188 1350 1435 1450 1425 410
6SE70 _ 2 - _ _ S _ _ - 1FD0
Table 3-3 Dimensions for size E and 1- _ _ S to 2- _ _ S
for M8 screws
1/2 x G Open space
180 for cooling
G
E
SIEMENS
D
C/L+ D/L-
Covering
Limiting network
Covering
F
Reactor
Covering
Grounding
bolt
B Grounding
bolt
0
10 180 50
270 97
for M8 screws
SIEMENS AG 6SE7087-6CX87-1FD0
SIMOVERT MASTERDRIVES Betriebsanleitung / Operating Instructions 27
Installation and Connection
Dimensions, voltage A B C D E
limiting network
for dv/dt filter [mm]
360 E
270 130
for M8 screws
15
C
B
C/L+ D/L- U2 V2 W2
10
Grounding bolt
DC link for M8 screws
Fig. 3-3 Dimension drawing, voltage limiting network for dv/dt filters,
size 3- _ _ S to 8- _ _ S
6SE7087-6CX87-1FD0 Siemens AG
28 Betriebsanleitung / Operating Instructions SIMOVERT MASTERDRIVES
Installation and Connection
Dimensions, reactor A B C D E F G H J
for dv/dt filter [mm]
6SE70_3- _ _ S _ _ -1FD0 458 356 416 133 435 155 194 M12 11
6SE70_4- _ _ S _ _ -1FD0 458 356 416 159 435 212 251 M12 11
6SE70_5- _ _ S _ _ -1FD0 533 410 470 186 565 170 207 M10 11
6SE70_6- _ _ S _ _ -1FD0 533 410 470 212 565 198 235 M10 14
6SE70_8- _ _ S _ _ -1FD0 608 470 540 217 650 198 245 M12 14
U1 V1 W1
A
Z
E
U2 V2 W2
Grounding
stud
B F
C G
Template
H
SIEMENS AG 6SE7087-6CX87-1FD0
SIMOVERT MASTERDRIVES Betriebsanleitung / Operating Instructions 29
Installation and Connection
3.2 Connection
3.2.1 Size B and C
NOTE dv/dt filters, Prod. State A are not suitable for operation from
ungrounded line supplies.
DC link connection
WARNING The drive converter and dv/dt filter will be destroyed if the C/L+ and
D/L- connections are interchanged.
Connect C/L+ of the dv/dt filter with C/L+ of the drive converter and
D/L- of the dv/dt filter with D/L- of the drive converter.
♦ Cable lengths: as short as possible, max. 3 m
♦ Route the cable so that no short-circuit or ground fault can occur
due to insulation damage (short-circuit-proof).
♦ Cable cross-sections:
Type of Cross-sections
2
constr. AWG mm
min. max. min. max.
B 14 10 1.5 4.0
C 10 10 4.0 4.0
AWG: American Wire Gauge
NOTE When fed from a DC bus, the inverter and associated dv/dt filter must
be commonly fused (Fig. 3-5).
+
−
3M
6SE7087-6CX87-1FD0 Siemens AG
30 Betriebsanleitung / Operating Instructions SIMOVERT MASTERDRIVES
Installation and Connection
Power connections ♦ Connect the filter inputs U1/L1, V1/L2, W1/L3 with the drive
converter outputs U2/T1, V2/T2, W2/T3.
♦ Connect filter outputs U2/T1, V2/T2, W2/T3 with the motor.
♦ Cable cross-sections, refer to the drive converter Instruction Manual.
♦ Permissible motor cable lengths, refer to Section “Permissible motor
cable lengths”.
Protective ♦ The protective conductor connection must be dimensioned
conductor according to the power connections and must be connected to
connection grounding studs; minimum cross-section 10 mm2.
WARNING The drive converter and dv/dt filter will be destroyed if the C/L+ and
D/L- connections are interchanged.
Connect C/L+ of the dv/dt filter with C/L+ of the drive converter and
D/L- of the dv/dt filter with D/L- of the drive converter.
♦ Cable lengths: as short as possible, max. 5 m
♦ Route the cable so that no short-circuit or ground fault can occur
due to insulation damage (short-circuit-proof).
♦ Cable cross-sections:
Type of Cross-sections Hole
constr. AWG / MCM mm2 for
min. max. min. max. bolt
E 4 1/0 16 50 M8
1- _ _ S 2 250 35 120 M10
2- _ _ S 1/0 250 50 120 M10
AWG: American Wire Gauge for cross-sections < 120 mm2
MCM: American Wire Gauge for cross-sections ≥ 120 mm2
NOTE When fed from a DC bus, the inverter and associated dv/dt filter must
be commonly fused (Fig. 3-6).
+
−
3M
SIEMENS AG 6SE7087-6CX87-1FD0
SIMOVERT MASTERDRIVES Betriebsanleitung / Operating Instructions 31
Installation and Connection
Power connections ♦ Connect the filter inputs U1/L1, V1/L2, W1/L3 with the drive
converter outputs U2/T1, V2/T2, W2/T3.
♦ Connect filter outputs U2/T1, V2/T2, W2/T3 with the motor.
♦ Cable cross-sections, refer to the drive converter Instruction Manual.
♦ Permissible motor cable lengths, refer to Section “Permissible motor
cable lengths”.
Protective ♦ The protective conductor connection must be dimensioned
conductor according to the power connections and must be connected to
connection grounding studs; minimum cross-section 10 mm2.
3.2.3 Size 3- _ _ S to 8- _ _ S
DC link connection
WARNING The drive converter and dv/dt filter will be destroyed if the C/L+ and
D/L- connections are interchanged.
Connect C/L+ of the dv/dt filter with C/L+ of the drive converter and
D/L- of the dv/dt filter with D/L- of the drive converter.
♦ Cable lengths: as short as possible, max. 8 m
♦ Route the cable so that no short-circuit or ground fault can occur
due to insulation damage (short-circuit-proof).
♦ Cable cross-sections:
Type of constr. Cross-sections Hole
AWG / MCM mm2 for
min. max. min. max. bolt
3- _ _ S 4/0 400 95 185 M12
4- _ _ S / 5- _ _ S 250 350 120 185 M12
6- _ _ S / 8- _ _ S 350 350 185 185 M12
AWG: American Wire Gauge for cross-sections < 120 mm2
MCM: American Wire Gauge for cross-sections ≥ 120 mm2
NOTE When fed from a DC bus, the inverter and associated dv/dt filter must
be commonly fused (Fig. 3-7).
6SE7087-6CX87-1FD0 Siemens AG
32 Betriebsanleitung / Operating Instructions SIMOVERT MASTERDRIVES
Installation and Connection
+
−
3M
C/L+ U2/T1
D/L− V2/T2
W2/T3
C/L+ D/L−
dv/dt filter
U2/ V2/ W2/
T1 T2 T3 Reactor
U1 U2 M
V1 V2 3AC
W1 W2
♦ Cable cross-sections:
Type of constr. Cross-sections Hole
AWG / MCM mm2 for
min. max. min. max. bolt
3- _ _ S 1/0 250 50 120 M10
4- _ _ S / 5- _ _ S 2/0 250 70 120 M10
6- _ _ S / 8- _ _ S 4/0 250 95 120 M10
AWG: American Wire Gauge for cross-sections < 120 mm2
MCM: American Wire Gauge for cross-sections ≥ 120 mm2
SIEMENS AG 6SE7087-6CX87-1FD0
SIMOVERT MASTERDRIVES Betriebsanleitung / Operating Instructions 33
Installation and Connection
Drive converter
dv/dt filters Supplementary reactor
6SE7016-2FB87-1FD0 not permissible
6SE7021-5FB87-1FD0 6SE7021-5FS87-1FE0
D/L−
6SE7022-2FC87-1FD0 6SE7022-2FS87-1FE0
C/L+
6SE7023-4FC87-1FD0 6SE7023-4FS87-1FE0
6SE7024-7FC87-1FD0 6SE7024-7FS87-1FE0
U2/ V2/ W2/
T1 T2 T3 6SE7026-0HE87-1FD0 6SE7026-0HS87-1FE0
6SE7028-2HE87-1FD0 6SE7028-2HS87-1FE0
Supplementary reactor
6SE7031-2HS87-1FD0 6SE7031-2HS87-1FE0
U1 V1 W1 6SE7031-7HS87-1FD0 6SE7031-7HS87-1FE0
6SE7032-3HS87-1FD0 6SE7032-3HS87-1FE0
6SE7033-0HS87-1FD0 6SE7033-0GS87-1FE0
U2 V2 W2 6SE7033-5HS87-1FD0 6SE7033-5GS87-1FE0
6SE7034-5HS87-1FD0 6SE7034-5GS87-1FE0
U1 V1 W1 6SE7035-7HS87-1FD0 6SE7035-7GS87-1FE0
L1 L2 L3 6SE7036-5HS87-1FD0 6SE7036-5GS87-1FE0
C/L+
dv/dt filter 6SE7038-6HS87-1FD0 6SE7038-6GS87-1FE0
D/L−
U2 V2 W2
T1 T2 T3 Table 3-7 Assignment, supplementary reactor and dv/dt
filters
M
3AC
6SE7087-6CX87-1FD0 Siemens AG
34 Betriebsanleitung / Operating Instructions SIMOVERT MASTERDRIVES
Start-up
4 Start-up
The dv/dt filter is designed for operation with a pulse frequency
fp = 3 kHz and can be operated with pulse frequencies fp ≤ 3 kHz.
In this case, when setting the drive converter (P060 = 5) parameter
P068 = 2 must be set to 2. In this case, parameter P340 (pulse
frequency) is automatically limited to values ≤ 3 kHz.
The drive setting must then be ended with P115 = 1, 2 or 3 so that the
settings become effective.
WARNING Pulse frequencies exceeding 3 kHz are not permissible and will destroy
the dv/dt filter.
Inverters with dv/dt filter must always be operated with a motor
connected!
When commissioning, if an inverter has a dv/dt filter and motor cable,
but a motor cannot be connected, then the following must be observed:
♦ The inverter must be operated with V/Hz control (P100 = 1);
It is not permissible to select the vector control types
(P100 = 3, 4, 5).
♦ The rated motor frequency (P107) must be set to > 30 Hz.
♦ The voltage boost (P325) must be set to < 5 %.
If this is not observed, the limiting networks of the dv/dt filter could be
destroyed!
SIEMENS AG 6SE7087-6CX87-1FD0
SIMOVERT MASTERDRIVES Betriebsanleitung / Operating Instructions 35
Technical Data
5 Technical Data
Table 5-1
Operating temperature 0 °C to + 40 °C
Storage temperature − 25 °C to + 70 °C
Transport temperature − 25 °C to + 70 °C
Environmental class acc. to DIN IEC 721 part 3-3/04.90
♦ climatic 3K3
♦ pollutant exposure 3C2
Protection class I acc. to DIN VDE 0160 part 1/05.82
IEC 536/1976
Mechanical ruggedness acc. to DIN IEC 68-2-67/06.90
♦ during operation Vibration severity 12
♦ during transport Vibration severity 22
Flammability FV1 acc. to DIN VDE 0304 part 3 / 09.85
V1 UL94
Table 5-2
6SE7087-6CX87-1FD0 Siemens AG
36 Betriebsanleitung / Operating Instructions SIMOVERT MASTERDRIVES
Bisher sind folgende Ausgaben erschienen: Ausgabe Interne Sachnummer
01.95 477 453.4000.76 J
05.95 477 453.4000.76 Ja
AB 477 453.4000.76 J AB-74
AC 477 453.4000.76 J AC-74
AD 477 453.4000.76 J AD-74
The following editions have been published so far: Edition Internal Item Number
01.95 477 453.4000.76 J
05.95 477 453.4000.76 Ja
AB 477 453.4000.76 J AB-74
AC 477 453.4000.76 J AC-74
AD 477 453.4000.76 J AD-74