Sie sind auf Seite 1von 6

HH-Sicherungseinstze

H.V.-Fuse links

E-

HH-Sicherungseinstze nach franz. Standard HV- fuse links in accordence to french standard

HH1-58

HH-Sicherungseinstze
H.V.-Fuse links

HH-Sicherungseinstze nach franz. Standard HV- fuse links in accordence to french standard
Einfhrung Bei den nachfolgenden Hochspannungssicherungen handelt es sich um Innenraum- bzw. Freiluftsicherungen zum Schutz von Energieverteilungstransformatoren. Introduction The high voltage fuses described here after are suitable for protection of power transformers used in energy distribution. They are designed for indoor and outdoor use.

Standard Die Sicherungen entsprechen folgendem Standard: - IEC 60282-1 - MFC 64210 Konstruktion Die Sicherungen haben ein hochwertiges Keramikrohr, das innen und auen braun glasiert ist. Die Kontaktkappen bestehen aus versilbertem Elektrolytkupfer. Die reinsilber Schmelzleiter sind auf einem sternfrmigen keramischen Trger gewickelt. Zur Lichtbogenlschung sind die Sicherungen mit Quarzsand bestimmer Korngre und Feuchte gefllt. Die Sicherungen sind mit oder ohne Auslser / Anzeigestift verfgbar. Umgebungstemperatur Bei Umgebungstemperaturen ber 40C mssen Reduzierfaktoren fr den Belastungsstrom beachtet werden. Dokumentation auf Anfrage erhltlich. Auswahl der Sicherungen Es handelt sich um Teilbereichsicherungen. Werte wie Nennstrom / kleinster Ausschaltstrom sowie grter Kurzschlustrom werden auf Seite 60 gezeigt. Bei Teilbereichsicherungen mu der kleinste Ausschaltstrom bercksichtigt werden, der gleichzeitig auch der kleinste Strom ist, den die Sicherung unterbrechen kann. Schutz von Transformatoren Bei der Auswahl von Sicherungen fr den Schutz von Transformatoren mu folgendes beachtet werden: - Einschaltstromste, die beim Einschalten des Transformators entstehen - berlaststrme Zur Auswahl des richtigen Nennstromes der Sicherung fr eine bestimmte Transformatorgre siehe Tabelle Seite 60. Beim Auswechseln von Sicherungen ist zu beachten, da in 3-phasigen Systemen grundstzlich alle 3 Sicherungen gewechselt werden sollten, wenn eine Sicherung anspricht.

Standards The fuses of in this leaflet comply with the following standards: - IEC 60 282-1 - NFC 64 210 Design and construction All fuses are made of high grade ceramic which is brown glazed inside and outside. The contact caps are made of electrolytic copper and are silver plated. The pure silver fuse elements and are wound on a star shaped ceramic support. For arc quenching the fuses are filled with quartz sand of certain grain size and humidity.

The fuses are available with or without striker/indicator pin.

Ambient temperature For temperatures above 40C, derating of the actual load current has to be observed. For this purpose a documentation is available on request . Selection of fuses The fuses described in this leaflet are back-up fuses. Values for fuse rated current / minimum breaking current as well as maximum breaking current are given in the technical schedule on page 60. For back-up fuses the minimum breaking current has to be observed which is the smallest current which the fuse can interrupt.

Transformer protection When selecting high voltage fuses for transformer protection the following has to be taken into account: - inrush currents which will occur when the transformer is closed on the circuit and - overload currents. For selection of the correct size of rated current for a certain transformer size please refer to schedule on page 60. For replacement of fuses it always has to be observed that in 3phase installations all 3 fuses should be replaced in case one fuse blows.

HH1-59

HH-Sicherungseinstze
H.V.-Fuse links

Sicherungseinstze nach Franzsischem Standard French standard distribution fuses


Normen: CEI 282.1, NF C 64200, C 64210, C 64203 / According to standards IEC 60 282-1, NF C 64200, C 64210, C 64203

Bemessungs- Bemessungsstrom spannung

Sicherungseinsatz ohne Schlagstift

Sicherungseinsatz mit Schlagstift

Bemessungsausschalt strom Rated breaking current Ia / kA

Kleinster Ausschaltstrom Minimum breaking current Imin / A

Leistungsabgabe

Gewicht /Set

Rated voltage

Rated current

fuse without striker pin fuse with striker pin

Powerloss

Weight / set (1 Set = 3 St./pcs.) kg

Un / kV

In / A

Artikel-Nr./Part No.

Artikel-Nr./Part No.

Pv / W

6,3 10 16 24 32 43 63 30 258 11 30 258 13 63

28 45 72 142 194 284

22 31 38 6 69 96 142

Anwendungsempfehlung zur Absicherung von Netztransformatoren mit HH-Sicherugseinstzen Franz. Standard application recommendation for protection of main transformer with HV fuse links french standard
Bemessungsspannung rated voltage (kV) Nennleistung des Transformators (kVA) transformer rated capacity (kVA)

50 6,3 6,3 6,3

100 16 16 6,3

160 32 16 16

250 32 16 16

400 63 43 43

630 1000 63 43 43 63 43

10 15 20

HH1-60

HH-Sicherungseinstze
H.V.-Fuse links

Zeit/Strom-Kennlinie fr HH-Sicherungseinstze nach Franz. Standard Time current characteristics for fuse links acc. french standard

HH1-61

HH-Sicherungseinstze
H.V.-Fuse links

Strombegrenzungs-Diagramm fr HH-Sicherungseinstze nach franz. Standard Cut off current diagram for HV-fuse links acc. french standard

Schmelz- und Lschintegrale fr HH-Sicherungseinstze nach franz. Standard Melting and total clearing integrals for HV-fuse links acc. french standard
IN A 6,3 10 16 20 25 32 43 63 I2ts A2s 61 154 350 920 1.400 2.200 4.900 10.600 I2ta / 24 kV A2s 390 1.100 2.500 6.500 9.800 16.000 35.000 74.000

HH1-62

HH-Sicherungseinstze
H.V.-Fuse links

HH1-63