MULTIPLES OF CURRENT SENSOR TAP (X)

.1 .2 .3 .4 .5 .6 .7 .8 1 2 3 4 5 6 7 8
.1 .2 .3 .4 .5 .6 .7 .8 1 2 3 4 5 6 7 8
1000 1000
900 900
800 800
700 700
600 600
500 500

400 400

300 300

200 200

100 100
90 90
80 80
70 70
60 60
TIME IN SECONDS

TIME IN SECONDS
50 50

40 40

30 30
.3X
.6X Ground Fault
20 20
.8X
Pickup Points
AK-15/25
1.0X
1.5X
10 10
9 9
2.0X
8 8
7 7
6 6
5 5

4 4

3 3

.4X Ground Fault .25X Ground Fault


2 .5X 2
Pickup Points .3X Pickup Points
.6X AKR-30 .4X AK-50
.8X .5X AKR-50
1.0X .6X
1 1
.9 .9
.8
1.2X .7X .8
.7 .7
GES-6034A

GES-6034A
.6 .6
.5 .5
.4 .4
Maximum Maximum
.3 .3

.2
Intermediate Intermediate .2
Ground Fault
Delay Bands

.1 Minimum Minimum .1
.09 .09
.08 .08
.07 .07
.06 .06
.05 .05

.04 .04

.03 .03

.02 .02

.01 .01
.1 .2 .3 .4 .5 .6 .7 .8 1 2 3 4 5 6 7 8
.1 .2 .3 .4 .5 .6 .7 .8 1 2 3 4 5 6 7 8

MULTIPLES OF CURRENT SENSOR TAP (X)

GE Consumer & Industrial -


Electrical Distribution Low-Voltage Power Circuit Breaker
GES-6034A
Current Sensor Taps (Amperes) Type AKR Programmer Set Points
AK-15 70, 100, 150, 225 SST Solid-state Overcurrent Trip Device Ground Fault Pickup:
AK-25 70, 100, 150, 225 AK-15/25 .5x, .6x, .8x, 1.0x, 1.5x, & 2.0x
Ground Trip Time-Current Curves
or 200, 300, 400, 600 AKR-30 .4x, .5x, .6x, .8x, 1.0x, & 1.2x
AKR-30 100, 150, 225, 300 AK/AKR-50 .25x, .3x, .4x, .5x, .6x, & .7x
or 300, 400, 600, 800 Curves apply at 50/60 Hertz. Where X = Sensor tap setting
AK/AKR-50 300, 400, 600, 800 From -20C to 70C Programmer Ambient. Ground Fault Delay Bands:
or 600, 800, 1200, 1600 Maximum, Intermediate & Minimum

2.78 3M