SAUDI ARAMCO INSPECTION CHECKLIST
Storage, Handling & Preservation of Portable Fire Protection
SAIC-B-2012 30-Nov-17 MECH-
Equipment
PROJECT TITLE WBS / BI / JO NUMBER CONTRACTOR / SUBCONTRACTOR
EQUIPMENT ID NUMBER(S) EQUIPMENT DESCRIPTION EQPT CODE SYSTEM ID. PLANT NO.
LAYOUT DRAWING NUMBER REV. NO. PURCHASE ORDER NUMBER EC / PMCC / MCC NO.
SCHEDULED INSPECTION DATE & TIME ACTUAL INSPECTION DATE & TIME QUANTITY INSP. MH's SPENT TRAVEL TIME
ITEM
ACCEPTANCE CRITERIA REFERENCE PASS FAIL N/A RE-INSP DATE
No.
A General Requirements
Portable (See Equipment
Fire Extinguishing Note 1) types are one of the following
per SAES-B-019, Table 1 (See Excel Sh # 2 Attached):
A) Portable hand held type
extinguishers (4 types)
• Pressurized Water 9.5 L Class A (SAMS 21-104-550).
• CO2 with nonmetal horn 4.5 Kg Type BC (21-102-223).
• Dry Chemical 12.2 Kg Class BC (hydrocarbon plant) (21-
102-820).
• Multi-purpose Dry Chemical Class ABC (21-102-775). SAES-B-019,
A1
Para. 4.1
B) Wheeled cart type extinguisher (2 types)
• Dry Chem 68 Kg Type BC for hydrocarbon plants (21-106-650).
• CO2 with dual 23 kg (50 lb)
cylinders Type BC (21-106-690) C)
Twin agent Extinguishers (Unit Skid or trailer)
NFPA 10,
Manufacturer Instruction Manual directions (storage, handling &
A2
preservation) for Portable Fire Extinguishers is available.
Para 4.3
ITEM
ACCEPTANCE CRITERIA REFERENCE PASS FAIL N/A RE-INSP DATE
No.
Wheeled type extinguishers are checked during storage:
A) Visual checks to determine physical condition
of extinguishers. Components are free of
corrosion, deterioration & damage.
B) Visual check to determine if any leakage exists (gauges) GI-1781.001,
B3
C) Visual check of tire condition & Supplement 1, 2
pressure as applicable D) Check of
environment (no direct sun, temperatures below 120°F)
Inspection tags are marked with date
of the inspection.
NFPA 10,
Fire extinguishers or extinguishing agents (media) shall be located not
B4
more than 75 ft (22.9 m) of travel distance from the Class D hazard.
Para 6.5.2
NOTES: 1. Storage, Handling & Preservation for new fire extinguishers is agreed upon early in the project. Prior to entering service, all new
fire extinguishers must be delivered to Local Fire Control Unit to be inspected (per GI-1781 supplemental checklists), commissioned, tagged,
and numbered per GI-1781.001, Section 5.12.1 Contractor checks equipment & mat'ls before their delivery to Saudi Aramco.
Storage, handling, preservation, & mixing of any extinguishing agents is approved by SA Fire Control Unit.
REFERENCE DOCUMENTS:
1- Saudi Aramco GI-1781.001 -- Inspection, Test, and Maintenance of Fire Protection Equipment, 3 Jan 2009
2- SAES-B-019 -- Portable, Mobile and Special Fixed Firefighting Equipment, (22 July 2012)
3- NFPA 10 -- Standard for Portable Fire Extinguishers, 2013 Edition
Contractor / Third-Party Saudi Aramco
Construction Representative* PMT Representative
Work is Complete and Ready for Inspection: T&I Witnessed QC Record Reviewed Work Verified
Name, Initials and Date: Name, Initials and Date: