PERHITUNGAN AC

OLEH ; MOCHAMAD GILANG SIHASALE


CONTOH PENGUJIAN COP
(ACTUAL DI LAPANGAN)
Temp./RH Ruangan = 25°C/55%
Entalpi = 52,9 Kj/Kg

Lebar = 650mm
Ti
ng
gi
=
90
m
m

5m /s
=2,
a
at a-rat
Vr

Temp./RH Supply = 17°C/90%


Entalpi = 44,7 Kj/Kg

Listrik = 1.8 Ampere/1 phasa


Debit Supply = Vrata-rata x Lebar x Tinggi
Debit Supply = 2,5m/s x 0,65m x 0,09m
Debit Supply = 0,146m = 310 cfm

Cap = Debit supply x x (entalpi ruangan – entalpi supply)


Cap = 0,146 x 1,2 x (52,9 – 44,7)
Cap = 1,44 KJ/s = 1,44 Kw
Cap = 4.910 Btu/h = ½ PK Kompresor

Daya Listrik = Arus x Tegangan x Faktor Daya


Daya Liatrik = 1,8 Ampere x 220V x 0,8
Daya Listrik = 316,8 watt = 0,3168 kW

COP = = = 4,5

EER = = = 15,35 Btu/h/watt


CONTOH PERHITUNGAN COP
(TEORITIS)
43°C
7°C

73°C
11°C 45°C
kondensasi (qc)
3 2

ekspansi (ex) Kerja kompresi (w)

4 Evaporasi (qe) 1
COP = =

COP = = 4,84

EER = = = 16,52 Btu/h/watt