Sie sind auf Seite 1von 8

SITOP DC-USV-Modul 40

SITOP DC-UPS-Module 40

Betriebsanleitung

6EP1931-2FC21
6EP1931-2FC42

Order No.: C98130-A7555-A7-05-7419

Operating Instructions
Manuel d'utilisation
Manuale di servizio
Manual de instrucciones

voir Internet http://www.siemens.de/sitop


vedi Internet http://www.siemens.de/sitop
vase Internet http://www.siemens.de/sitop

6EP1931-2FC21

Siemens AG sterreich, 03/2006

6EP1931-2FC42

1 of 8

SITOP DC-USV-Modul 40

Mabild
Dimension drawings

6EP1931-2FC21/42
On / Off
+2V
Zuschaltschwelle
+1V
(cut-in threshold)
+0,5V
+22V fest eingestellt (fixed)
+1V
+1V
+0,5V
Ladeschlussspannung
+0,2V
(end-of-charge voltage)
+0,2V
+ 26,3V fest eingestellt (fixed)
+0,1V
1A / 2A Ladestrom (charging current)
eingestellte Zeit / max. Zeit (set time / max.)
+320s
+160s
+ 80s
Pufferzeit (buffering time)
+ 40s
+ 20s
+ 10s
+5s fest eingestellt (fixed)
Unterbrechung output (disconnection)
Betriebszustand Akku On / Off (operating
state battery)
Kompatibilitt (nur bei 6EP1931-2FC21)
Grundeinstellung, Auslieferzustand
(basic setting, delivery state)

Die Hutschienenbefestigung auf der Rckwand kann von der Position wie SITOP modular (Auslieferzustand) durch Lsen der 3
selbstschneidenden Schrauben auf die Position wie SITOP power versetzt werden.
The mounting position on the rail can be changed from position SITOP modular (delivery state) to new position SITOP power (remove the
3 self-tapping screws)

Hinweis
Diese Betriebsanleitung enthlt aus Grnden der bersichtlichkeit nicht smtliche Detailinformationen des Produkts und kann auch nicht jeden denkbaren Fall
der Aufstellung, des Betriebes oder der Instandhaltung bercksichtigen. Technische nderungen jederzeit vorbehalten. In Zweifelsfllen gilt der deutsche Text.

Note
These operating instructions do not purport to cover all details of the product, nor to provide for every possible contingency that may arise during installation,
operation or maintenance. Subject to change without notice. The German text applies in cases of doubt.

Siemens AG sterreich, 03/2006

2 of 8

SITOP DC-USV-Modul 40

Deutsch
WARNHINWEISE

Nur entsprechend qualifiziertes Fachpersonal darf an diesem Gert oder in dessen Nhe arbeiten.
Der einwandfreie und sichere Betrieb dieses Gertes setzt sachgemen Transport, fachgerechte Lagerung, Aufstellung, Montage und die
ausschlieliche Verwendung von SITOP Batteriemodulen (z.B. Batterie- bzw. Akku-Module 6EP1935-6ME21oder 6EP1935-6MF01) voraus.
Der Wert des Ladestromes und der Ladeschlussspannung ist gem den Empfehlungen unter "Einstellungen" mit den DIP-Schaltern anzupassen.
Eine falsche Einstellung vermindert die Lebensdauer des Akkus und kann zu Zerstrungen fhren.

ACHTUNG
Nur geschultes Personal darf das Gert ffnen. Elektrostatisch gefhrdete Bauelemente (EGB)

Beschreibung und Aufbau


Das DC-USV-Modul 40 ist ein Einbaugert der SITOP -Reihe zur Montage auf Normprofilschiene DIN EN 50022-35x15/7,5. Fr die Installation der Gerte und
Batteriemodule sind die einschlgigen DIN/VDE-Bestimmungen oder lnderspezifischen Vorschriften (z.B. VDE 0510 Teil 2 / EN 50272-2) zu beachten .
In Kombination mit SITOP Batteriemodulen dient es zur Pufferung eines Teiles des Laststromes (max. 40A) von 24V-Laststromversorgungen der Reihe SITOP.
Der Eingang "Input L+" des DC-USV-Moduls ist mit dem Ausgang L+ des versorgenden 24V DC-Netzteils zu verbinden, der Eingang "Input M" mit dem Ausgang M des
versorgenden Netzteils. Das Batteriemodul wird an den Klemmen +Bat und Bat angeschlossen. Die zu puffernden Verbraucher werden ber den Ausgang Output L+
und Output M des DC-USV-Moduls mit der am Eingang angelegten Spannung versorgt, bei Ausfall der 24V DC-Versorgungsspannung bzw. Spannungseinbruch unter
die eingestellte Zuschaltschwelle werden die Verbraucher durch Zuschaltung des im Bereitschaftsparallelbetrieb auf Vollladung gehaltenen Akku-Moduls versorgt.
ber DIP-Schalter knnen die Akku-Zuschaltschwelle, die Ladeschlussspannung, der Ladestrom und die berbrckungszeit eingestellt werden. Ein Schalter dient zur
Einstellung einer definierten berbrckungszeit mit anschlieender Abschaltung des Akkus (siehe Einstellungen), ein Schalter zur berbrckung des ON/OFF-Kreises,
ein Schalter zur Wahl vor Abschaltung der Akkus Ua fr 5s unterbrechen, ein Schalter dient der Wahl wesentliche Eigenschaften analog zur neuen DC-USV-Familie
oder analog zum bisherigen DC-USV-Modul 40, 6EP1931-2FC01 (nur bei 6EP1931-2FC21).
Vier Leuchtdioden, zwei potentialfreie Wechsler, ein Schlieer und eine USB-Schnittstelle (bei 6EP1931-2FC42) bernehmen die Signalisierung von Betriebszustnden
des DC-USV-Moduls 40 (siehe Signalisierung) und die Steuerung Remote-Timerstart.

Technische Daten
Eingangsgren:

Ausgangsgren:

Eingangsnennspannung:
24V DC
Arbeitsspannungsbereich:
22 bis 29V DC
max. Eingangsstrom bei 24V und Batterieladung:
42,6A DC
max. Eingangsstrom bei 24V und geladener Batterie:
40,2A DC
Batteriestrom im Pufferbetrieb:
40,2A DC
Ruhestromaufnahme aus dem Akku:
ca. 0,30 mA
Verlustleistung bei 24V und Batterieladung:
ca. 33 W
Verlustleistung 24V und geladener Batterie:
ca. 32 W
Verlustleistung im Pufferbetrieb:
ca. 34 W

Ausgangsnennspannung:
Ausgangsnennstrom:
Ausgangsstrombereich:

UA1 = 24V DC
IA1 = 40A DC
IA1 = 0 ... 40A DC

Ausgangskennlinie des Ladereglers:


Die Ladung des Akkumoduls erfolgt mit einstellbarem Konstantstrom bis zur
eingestellten Ladeschlussspannung.
Ladeschlussspannung: UA2 = 26,3 bis 29,3V DC
Ladestrom:
IA2 = 1 oder 2A DC

Einstellungen
Einstellung der Zuschaltschwelle:
Sinkt die Eingangsspannung unter den eingestellten Wert der Zuschaltschwelle, so schaltet das USV-Modul in den Pufferbetrieb um. Die Verbraucher werden dann ausschlielich durch das
Akkumodul versorgt. Die Einstellung der Zuschaltschwelle erfolgt mittels 3 Stck DIP-Schalter (Position siehe Seite 2) gem Tabelle 2 (siehe Seite 7). Einstellbereich: 22,0 bis 25,5 V DC in
0,5V-Schritten (Auslieferzustand: 22,5V DC 0,1V). Genauigkeit: 1,8%

Einstellung des Ladestromes:


Die Ladung des Akkumoduls erfolgt mittels Konstantstrom, bis die eingestellte Ladeschlussspannung erreicht ist. Der Ladevorgang wird dann beendet. Bei der Einstellung des Ladestromes sind
die Angaben des verwendeten Akkumoduls zu beachten, um die jeweils optimale Einstellung zu whlen. Die Einstellung des Ladestromes erfolgt mittels eines DIP-Schalters (Position siehe
Seite 2).
Einstellbereich: 1A DC 0,2A DC oder 2A DC 0,2A DC (Auslieferzustand: 2A DC 0,2A DC)

Einstellung der Ladeschlussspannung:


Die Ladeschlussspannung hngt von der jeweiligen Type des Akkus sowie von der Temperatur welcher er ausgesetzt ist ab. Tabelle 1 ( siehe Seite 7) beinhaltet die Ladeschlussspannungen fr
die angegebenen Akkumodule bei unterschiedlichen Temperaturen. Zwischen den Werten kann interpoliert werden. Die Einstellung erfolgt mittels 6 Stck DIP-Schalter (Position siehe Seite 2)
gem Tabelle 3 (siehe Seite 7).
Einstellbereich: 26,3 bis 29,3V DC in 0,1V-Schritten (Auslieferzustand: 26,6V DC 0,1V fr +40C Bleigelakku-Temperatur). Genauigkeit: 0,7%
Hinweis: Fr vorteilhafte tiefere Temperaturen (Optimum sind +20 +25C) muss die Ladeschlussspannung auf Werte gem Tabelle 1 erhht werden !

Einstellung des Betriebszustandes ON/OFF:


Um eine unbeabsichtigte Entladung des Akkus (z.B. durch Ausschalten der Anlage) zu verhindern, kann das DC-USV-Modul mittels DIP-Schalter (oder durch ffnen einer potenzialfreien
Verbindung oder Drahtbrcke zw. Klemme X2.9 und X2.10) in den Betriebszustand OFF (Auslieferzustand) geschaltet werden.
Im Betriebszustand ON (DIP-Schalter geschlossen oder Klemme X2.9 mit X2.10 mit potenzialfreiem Schlieer fr Umax = 15V DC, Imax. = 10mA verbunden oder X2.9 auf Masse gelegt) bietet
das DC-USV-Modul die volle Funktionalitt laut Spezifikation. Im Betriebszustand OFF erfolgt bei Wegfall der Versorgungsspannung keine Umschaltung in den Pufferbetrieb. Alle anderen
Funktionen bleiben erhalten. Wird das USV-Modul whrend des Pufferbetriebes in den Zustand OFF geschaltet, so wird auch der Pufferbetrieb beendet. Im Normalbetrieb wird die Einstellung
ON/OFF alle ca. 20s abgefragt.

Einstellung der Pufferzeit


Die Einstellung der Pufferzeit erfolgt mittels 6 Stck DIP-Schaltern (Position siehe Seite 2) und kann gem Tabelle 4 (siehe Seite 7) in 10s-Schritten von 5s bis 635s vorgenommen werden. Mit
Schalter 1 (eingestellte Zeit / max. Zeit) kann gewhlt werden, ob die Beendigung des Pufferbetriebes nach der eingestellten Zeit oder erst bei Erreichen der Tiefentladeschwelle des Akkus (=
maximale Pufferzeit) erfolgt. (Auslieferzustand Pos. Off = maximale Pufferzeit). Bei 6EP1931-2FC42 kann mit dem Remote-Signal (wird bei der Schnittstelle beschrieben) der Puffertimer
gestartet werden um die USV nach der eingestellten Pufferzeit abzuschalten. In diesem Fall muss der Schalter 1 (eingestellte Zeit / max. Zeit) auf Pos. Off stehen und der Schalter
Unterbrechung auf Pos. On. Wenn die Abschaltung erfolgt ist, besteht keine Mglichkeit mittels nderung der Schaltereinstellung den Pufferbetrieb wieder einzuschalten. Erst nach Wiederkehr
der Eingangsspannung kann ein neuerlicher Pufferbetrieb erfolgen.

Unterbrechung der Ausgangsspannung


Mittels DIP-Schalter kann gewhlt werden, ob die Ausgangsspannung nach Ablauf der eingestellten Pufferzeit fr ca. 5 sec unterbrochen wird oder nicht (Auslieferzustand: Keine
Unterbrechung). Bei Einstellung maximale Pufferzeit erfolgt eine Unterbrechung der Ausgangsspannung (nur bei 6EP1931-2FC42) ber das Remote-Signal der Schnittstelle.

Kompatibilitt (nur bei 6EP1931-2FC21)


Mittels DIP-Schalter kann gewhlt werden: wesentliche Eigenschaften analog zur neuen DC-USV-Familie oder analog zum bisherigen DC-USV-Modul 40 6EP1931-2FC01. (Auslieferzustand
neue DC-USV-Familie)

Schutz- und berwachungsfunktionen


Verpolschutz: Das USV-Modul ist gegen Verpolung der Eingangsspannung und des Akkus elektronisch geschtzt.
berstrom und Kurzschlussschutz: Im Normalbetrieb und im Pufferbetrieb ist das USV-Modul durch die interne Strombegrenzung (typ. 65 bis 110 A fr ca. 20ms bei Kurzschluss,
1,05 bis 1,4 IN fr ca. 80ms bei berstrom) geschtzt. Eine eingebaute (nicht zugngliche) Sicherung (48A) schtzt im Fehlerfall. Im Normalfall erfolgen automatische Wiederanlaufversuche alle
ca. 20s. Im Pufferbetrieb erfolgt speichernde Abschaltung. Wiederanlauf nach Rckkehr zum Normalbetrieb.
Tiefentladeschutz: Blei-Akkumulatoren drfen nur bis zu einer bestimmten Spannung (Tiefentladeschwelle) entladen werden. Wird der Akku weiter entladen, so vermindert dies die
Lebensdauer und kann bis zur Zerstrung fhren. Um den angeschlossenen Akku vor Beschdigung zu schtzen, wird das USV-Modul speichernd abgeschaltet und die Verbraucher vom Akku
getrennt, sobald die Akkuspannung im Pufferbetrieb unter typ. 19V DC (Bereich: 19,5...18,5V DC) sinkt.

Siemens AG sterreich, 03/2006

3 of 8

SITOP DC-USV-Modul 40

Deutsch
Akkutest: Um einen zuverlssigen Pufferbetrieb zu gewhrleisten, muss sichergestellt werden, dass das Akku-Modul voll funktionsfhig ist. Aus diesem Grund wird im Normalbetrieb alle 4h
das angeschlossene Akku-Modul getestet. Der Test findet nur statt, wenn innerhalb dieser 4h kein Pufferbetrieb oder eine Abschaltung des USV-Moduls erfolgt ist. Falls in einer Anwendung in
krzeren Intervallen regelmig ein Pufferbetrieb eingeleitet wird so erfolgt kein Akkutest. Ein defekter Akku wird durch Blinken der Alarmmeldung signalisiert und muss ausgetauscht werden.
Wichtiger Hinweis zum Akkutausch: Werden die Akkus bei blinkendem roten Alarm im laufenden Betrieb (d.h. ohne Abschaltung der 24V DC) ausgetauscht, erlischt der
blinkende rote Alarm (rote LED und Alarm-Relais) erst nach bis zu 4 Stunden ! Bei unzureichend geladenen neuen Akkus kann blinkender oder konstant roter Alarm (bei Akkuspannung <
18,5V) noch lnger (z.B. 8 oder 12 Stunden) anstehen !

Signalisierung
Normalbetrieb, d.h. die Eingangsspannung am DC-USV-Modul ist hher als die eingestellte Zuschaltschwelle. Die Verbraucher werden von der vorgeschalteten Stromversorgung versorgt.
Falls ein Akku-Modul angeschlossen ist, wird dieses geladen. Im Normalbetrieb leuchtet die grne Leuchtdiode (o.k.) und der Relaiskontakt X2.2 X2.3 (o.k.) ist geschlossen.

>85% Vollladung, d.h. Akkuladung grer 85% der je nach Alterung noch vorhandenen Restkapazitt. Es leuchtet die zweite grne Leuchtdiode (Bat>85%) und der Relaiskontakt
X2.7 X2.8 ist geschlossen. (zweite grne Leuchtdiode aus und Relaiskontakt X2.7 X2.8 offen (Ruhestellung bei abgeschaltetem Gert) bedeutet : Bat<85%, d.h. Akkuladung unter 85%)
Pufferbetrieb, d.h. die Eingangsspannung ist niedriger als die eingestellte Zuschaltschwelle. Die Verbraucher werden vom Akku-Modul versorgt. Im Pufferbetrieb leuchtet die gelbe
Leuchtdiode (Bat) und der Relaiskontakt X2.1 X2.2 (Bat) ist geschlossen (Ruhestellung bei abgeschaltetem Gert).
Alarmmeldung Pufferbereitschaft fehlt: Bei Signal Pufferbereitschaft fehlt leuchtet die rote Leuchtdiode (Alarm) und der Relaiskontakt X2.4 X2.5 (Alarm) ist geschlossen
(Ruhestellung bei abgeschaltetem Gert). Ursachen fr eine fehlende Pufferbereitschaft im Normalbetrieb knnen sein:
Betriebszustand OFF, kein Akku-Modul angeschlossen, verpolter oder defekter Akku (Akkuspannung < 18,5V) oder Drahtbruch zwischen Akku und USV-Modul.
Die Abfrage von Betriebszustand ON/OFF, verpolter, defekter oder kein Akku sowie Drahtbruch und somit auch die Ausgabe des Signals erfolgt im Normalbetrieb alle 20s. Nach Fehlerende
erfolgt die Rcksetzung nach der nchsten Abfrage.
Blinkt das Signal im 2s Takt, so ist der Akku zwar defekt, jedoch kann ein Pufferbetrieb noch erfolgen. Die angegebenen Pufferzeiten knnen allerdings nicht mehr eingehalten werden. Das
Akku-Modul ist auszutauschen.
Im Pufferbetrieb bedeutet das Signal Alarm, dass die Akkuspannung auf <20,4V gesunken ist und eine Zwangsabschaltung zum Schutz des Akkus unmittelbar bevor steht. Nach Abschaltung
des Akkus aufgrund berlast, Kurzschluss, Tiefentladeschutz oder abgelaufener Pufferzeit erlischt die rote Leuchtdiode (Alarm), der Relaiskontakt X2.4 X2.5 bleibt geschlossen. Belastbarkeit
der Relaiskontakte: 60V DC / 1A oder 30V AC / 1A

USB: Bei der Type 6EP1931-2FC42 werden die Signale zustzlich ber eine PC-fhige USB-Schnittstelle ausgegeben. Die Signale
werden wie bei der seriellen Schnittstelle mit einem jeweils 5 Zeichen langen String ausgegeben. Es gilt die obenstehende Tabelle. Ein
Softwaretool zum Auslesen und Verarbeiten der Signale steht im Internet unter http://www.ad.siemens.de/sitop kostenlos zur Verfgung.
Hier sind auch weitere Informationen zur Schnittstelle angefhrt.
Technische Ausfhrung: Die USB Schnittstelle entspricht der Spezifikation 2.0. Die Kommunikation erfolgt aber nur mit Full Speed, d.h.
12Mbit/s, die USB-Optionsbaugruppe wird von der DC-USV mit +5V versorgt (self powered), Ausgabe der Signalzustnde alle 75ms
20%; 29ms 20% Datenausgabe; 46ms 20% Pause. Die Verbindung zum PC erfolgt ber ein handelsbliches 4-adriges, geschirmtes
USB-Kabel mit einem Wellenwiderstand von 90Ohm, einem USB Series A Stecker zum PC und einem USB Series B Stecker zur DCUSV und einer maximalen Lnge von 5m. Das Kabel besteht aus zwei 28 bis 20 AWG non-twisted USB-Versorgungsleitungen (VBUS
und GND) und aus zwei 28 AWG twisted pair Datenleitungen (D+ und D-).
Steckerbelegung: Pin 1: VBUS (+4,40V ... +5,25V DC), Sendedaten auf Pin2 (D-) und Pin 3 (D+), Pin 4: GND.
Empfangsdaten: Der Empfang des Zeichens R (Signal Remote Timerstart) startet den Timer im DC-USV-Modul mit der dort eingestellten
berbrckungszeit (Tabelle 2) (Nur bei Einstellung maximale Zeitdauer und Unterbrechung). Nach der eingestellten berbrckungszeit
wird der Pufferbetrieb beendet bzw. die Ausgangsspannung unterbrochen.

Signal

Klartext

Pufferbereitschaft vorhanden
Pufferbereitschaft fehlt

BUFRD
ALARM

Normalbetrieb
kein Normalbetrieb

DC_OK
DC_LO

kein Pufferbetrieb
Pufferbetrieb

*****
*BAT*

85% Vollladung
85% Vollladung

BA>85
BA<85

Umgebung

Vorschriften

Einsatzbedingungen nach EN 60721-3-3, Klimaklasse 3K3 (relative Luftfeuchte


5% bis 85% und absolute Luftfeuchte 1 g/m bis 25 g/m; keine Betauung).
Ortsfester Einsatz, wettergeschtzt, Verschmutzungsgrad 2
Temperatur fr Lagerung und Transport: -40 bis +70C
Temperatur fr Betrieb: 0 bis +60C

Schutzart: IP20 nach EN60529 (VDE 0470 Teil1)


Schutzklasse III nach EN60950
VDE 0100 Teil 410 (IEC 364-4-41)
VDE 0106 Teil 1 (IEC 536)
VDE 0113 Teil 1 (EN 60204-1)
IEC 61131; UL 508 / CSA C22.2 File E197259
Funkentstrt nach EN55022, Grenzwertkurve B
Strfestigkeit nach EN 61000-6-2

Gewicht
6EP1931-2FC21
6EP1931-2FC42

1,1kg
1,1kg

Montagehinweise
Das Gert ist zwecks ordnungsgemer Entwrmung vertikal so zu montieren, dass die Eingangsklemmen, die Ausgangsklemmen und Zuluftschlitze unten sind. Unterhalb und oberhalb des
Gertes soll mindestens ein Freiraum von je 50mm eingehalten werden. Montage / Demontage siehe Bild Seite 8.
Um Streinkopplungen und thermische Beanspruchung zu minimieren, sollen DC-USV-Module und zugehrige Batteriemodule mindestens 50 cm entfernt von Kommutierungsdrosseln installiert
werden! USB-Schnittstellen und Steuerleitungen (ON/OFF-Steuerstromkreis) drfen nicht direkt parallel zu Leistungsleitungen (insbesondere Leitungen zwischen Frequenzumrichter und Motor
sowie Frequenzumrichter und Kommutierungsdrossel) verlegt werden. Um Streinkopplungen zu minimieren soll zu diesen Leitungen ein Abstand von mindestens 10cm eingehalten werden.
Batteriemodule sollen niederohmig verdrahtet (4mm) und an khlem Ort installiert werden (bei Schaltschrnken in der Regel ganz unten).

Vor Beginn der Installations oder Instandhaltungsarbeiten ist der Hauptschalter der Anlage auszuschalten und gegen Wiedereinschalten zu sichern. Es ist die
Betriebsanleitung von SITOP power zu beachten.
Die Sicherung am Akku-Modul ist bei allen Arbeiten zu entfernen.

Wartungshinweise fr Batteriemodule
Um fr Bleigel-Batteriemodule eine mglichst lange Lebensdauer zu erhalten empfiehlt sich technologiebedingt, die Batteriemodule bei der Erst-Inbetriebnahme der Anlage mehrmals auf ca.
19V zu entladen und wieder aufzuladen (ca. 3 x Entladen / Laden, z.B. mit den 24V DC-Verbrauchern der Anlage entladen, hierzu Pufferzeit auf max. Zeit einstellen. Wiederaufladen durch
das DC-USV-Modul). Bei Reinblei-Batteriemodulen ist das nicht erforderlich.

Anschluss und Klemmenbelegung


Klemmen
X1.1
X1.3, X1.5
X1.2/X1.4, X1.6
X1.7/X1.8
X2.1,2,3
X2.4,5,6
X2.7,8
X2.9/X2.10
X3

Funktion
Eingangsspannung DC 24V
Ausgangsspannung DC 24V
Ein/Ausgangsspannung DC 0V
Akku-Modul DC 24V
Signal: Normalbetrieb / Pufferbetrieb
Signal: Pufferbereitschaft fehlt / vorhanden
Signal: Ladezustand >85%
On/Off Brcke (keine Brcke =Off)
USB-Schnittstelle

Anschlusswert
0,33 ... 10mm2
22...7 AWG

0,5... 2,5mm2
20...13 AWG

Anschlusslnge
bis 3m

Bemerkung
Schraubklemmen fr Schraubendreher mit
5mm Klingenbreite

bis 3m
bis 3m
bis 3m
bis 3m
bis 3m

empfohlenes Anzugsmoment 1,2Nm


Schraubklemmen fr Schraubendreher mit
3,5mm Klingenbreite
empfohlenes Anzugsmoment 0,5-0,7Nm
Siehe Beschreibung oben

ACHTUNG
Die externe Beschaltung aller Klemmen (auch Signal- und Meldekontakte) muss den Anforderungen an SELV-Kreise nach
VDE 0805 / EN 60950 gengen.

Siemens AG sterreich, 03/2006

4 of 8

SITOP DC-USV-Modul 40

English
WARNINGS

Only properly qualified personnel may work on or around this equipment.


The successful and safe operation of this equipment is dependent on proper handling, storage and installation. Correct functioning is also
dependent on the use of SITOP battery modules (e.g. battery modules of type 6EP1935-6ME21or 6EP1935-6MF01.
The charging current level and the end-of-charge voltage must be adjusted with DIP-switches to the settings recommended under "Technical Data".
Setting incorrect current and voltage values reduces the life of the battery and may cause irreparable battery damage.

CAUTION
Only trained personnel may open the unit. Electrostatically sensitive devices (ESD)

Description and Design


The DC-UPS module 40 is a chassis unit in the SITOP power product range for mounting on a DIN rail of type DIN EN 50022-35x15/7.5.
The modules and the battery modules must be installed in accordance with the applicable DIN/VDE specifications or pertinent regulations in the country of installation
(e.g. VDE 0510 Part2 / EN 50272-2).
In conjunction with the battery module, it buffers a proportion of the load current (max. 40A) of 24V load current supplies in the SITOP range.
Input "Input L+" on the DC-UPS module must be connected to output L+ of the 24V DC power supply unit and input "Input M" to output M of the power supply unit. The
battery module is connected to terminals +Bat and Bat. The loads to be buffered are supplied via outputs "Output L+" and "Output M" on the DC-UPS module with the
voltage connected to the input. If the 24V DC supply voltage fails or drops below the set cut-in threshold, the battery module, which is maintained at full charge in
continuous supply mode, is connected in to supply the loads.
The battery cut-in threshold, end-of-charge voltage, charging current and the buffering time can be set via DIP-switches. A switch is provided for setting a defined
buffering (stored energy) time with subsequent disconnection of the battery (see Settings), one switch give the alternative attributes like the new DC-UPS-family or
analog to the former DC-UPS 40 6EP1931-2FC01 (only for 6EP1931-2FC21).
The operating states of the DC-UPS module 40 are signaled by four LEDs, two floating changeover and one normally-open contacts and a USB-interface (6EP19312FC42 only) (see Signaling) and the control signal Remote Timerstart.

Technical Data
Input quantities:
Rated input voltage:
Operating voltage range:
Max. input current at 24V and battery charging:
Max. input current at 24V and charged battery:
Battery current in floating operation:
Max. quiescent current consumption of the battery
Power loss at 24V and battery charging:
Power loss at 24V and charged battery:
Power loss in floating operation:

Output quantities:
24V DC
22 to 29V DC
42.6A DC
40.2A DC
40.2A DC
appr. 0.3mA
appr. 33 W
appr. 32 W
appr. 34 W

Rated output DC voltage:


Rated output direct current:
Output current range:

VA1 = 24V DC
IA1 = 40A DC
IA1 = 0 40A DC

Output characteristic of charging regulator:


The battery module is charged at an adjustable constant current until the
set end-of-charge voltage is reached.
End-of-charge voltage: VA2 = 26.3 to 29.3V DC
Charging current:
IA2 = 1 or 2A DC

Settings
Setting the cut-in threshold:
If the input voltage drops below the selected cut-in threshold voltage, the UPS module switches over to floating operation. The loads are then supplied solely by the battery module. The cut-in
threshold is set via three DIP-switches (see page 2 for position) according to table 2 (see page 7).
Setting range: 22.0 to 25.5V DC in 0.5-steps (delivery state: 22.5V DC 0.1V), accuracy 1.8%

Setting the charging current:


The battery module is charged at a constant current until the selected end-of-charge voltage is reached. The charging operation is then ended. When setting the charging current, please read
the instructions for the relevant battery module in order to select the optimum setting. The charging current is set by one DIP-switch (see page 2 for position).
Setting range: 26.3 to 29.2V DC in 0.1V-steps (delivery state: 26,6V DC 0.1V for +40C lead-gel-battery temperature), accuracy 0.7%V DC
Note: for lower temperatures (recommended optimum temperature +20C ... +25C) increase the end-of-charge voltage according to table 1 !

Setting the end-of-charge voltage:


The end-of-charge voltage depends on the battery type and on the battery`s ambient operating temperature. Table 1 (see page 7) shows the end-of-charge voltages for specific battery modules
at different temperatures. It is possible to interpolate between these values. The voltage is set by six DIP-switches (see page 2 for position) according to table 3 (see page 7).
Setting range: 26.3 to 29.2V DC in 0.1V-steps (delivery state: 27.0V DC 0.1V for +25C lead-gel-battery temperature), accuracy 0.7%

Setting the operating state ON/OFF:


To prevent the battery from being discharged unintentionally (e.g. when the system power is disconnected), the DC-UPS module can be switched with a DIP-switch (or a wire jumper (or floating
connection) inserted between terminals X2.9 and X2.10) to operating state "OFF" (delivery state). In the "ON" state (DIP-switch closed or terminals X2.8 and X2.9 connected with a floating
normally-open contact (Vmax = 15V DC, Imax = 10mA) ), the DC-UPS module is fully functional according to specification. In the "OFF" state, the module does not switch over to floating operation
when the mains supply is disconnected but remains functional in every other respect. If the module is switched to "OFF" in floating operation, it stops operating in floating mode.
During normal operation, the polling interval for the ON/OFF setting is appr. 20s.

Setting the buffering time:


The buffering time is set via six DIP-switches (see page 2 for position) as illustrated in Table 4 (see page 7) in 10s-steps from 5s to 635s. By switch 1 (delivery state max. time) you can choose
whether floating operation will be terminated after a prespecified period or when the exhaustive discharge threshold of the battery (= maximum buffering time) is reached (delivery state: max.
buffering time). Using a 6EP1931-2FC42 the remote signal starts the timer to terminate after a prespecified period (switch 1 has to be in position Off and switch interruption in position On). Once
the battery has been disconnected, there is no way in which floating operation can be restarted again by altering the switch setting. Only when the input voltage has recovered floating operation
can be resumed.

Interruption of the output voltage:


By a DIP-switch you can choose if the output voltage is interrupted for 5 s at the end of the buffering time or not (delivery state : no interruption). Using a 6EP1931-2FC42 and set max. time an
interruption is started by the remote signal.

Compatibility (only for 6EP1931-2FC21)


By a DIP-switch you can choose attributes like the new DC-UPS-family or analog to the former DC-UPS 40 6EP1931-2FC01 (delivery state: new familiy)

Protective and Monitoring Functions


Reverse polarity protection: The UPS module is electronically protected against polarity reversal of the input voltage and battery.
Overcurrent and short-circuit protection: The UPS module is protected by an internal current limitation (typ. 65 to 110A for appr. 20ms at a short-circuit,
1.05 to 1.4 IN for appr. 80ms at a overcurrent) in normal and floating operations. An internal 48A-fuse (not accessible) protects the module in case of failure. In normal operation automatic restart
attempts are made appr. every 20s. In floating operations the module shuts down in store mode. Restart after return to normal operation.

Exhaustive discharge protection:

Lead-acid batteries may only be discharged down to a certain voltage (exhaustive discharge threshold). Allowing them to discharge further will
reduce their service life and may result in irreparable battery damage. In order to protect the battery against damage, the UPS module is shut down in store mode and the loads disconnected
from the battery as soon as the battery voltage drops below typ. 19V DC (range 19.5 to 18.5V DC) in floating operation.

Siemens AG sterreich, 03/2006

5 of 8

SITOP DC-USV-Modul 40

English
Battery test: In order to guarantee reliable floating operation, the battery module must be checked to ensure that it is fully functional. For this reason, the connected battery module is tested
every 4 hours under normal operation. The test is carried out only if the battery has not operated in floating mode or been disconnected within this 4 hour period. The battery test is not
performed for applications in which floating operation is activated regularly at shorter intervals. A defective battery is signaled by a flashing alarm and must be replaced then.

Important note changing rechargeable batteries: if you change rechargeable batteries with red alarm blinking under current operation (i.e. without switching off 24V DC), red
blinking alarm
(red LED and alarm relay) turns off only up to 4 hours ! When exchanging to not completely charged batteries the blinking or constantly occurent alarm (when battery voltage < 18,5V) may
persist even longer (e.g. 8 or 12h !).

Signaling
"Normal operation", i.e. the input voltage at the DC-UPS module is higher than the set cut-in threshold. The loads are being fed by the line-side power supply. If a battery module is
connected, it is fully charged. Under normal operation, the green LED (o.k.) is illuminated and relay contact X2.2 X2.3 (o.k.) is closed.
>85% charge, i.e. battery is loaded more than 85% (available rest capacity dependent upon aging). The second green LED (Bat>85%) is illuminated and relay contact X2.7 X2.8 is
closed. (second green LED off and relay contact X2.7 X2.8 open (de-energized position when unit is disconnected) means : Bat<85%, i.e. battery charge below 85%)
"Floating operation", i.e. the input voltage is lower than the set cut-in threshold. The loads are being supplied by the battery module. In floating operation, the yellow LED (Bat) is
illuminated and relay contact X2.1 X2.2 (Bat) closed (de-energized position when unit is disconnected).
Alarm signal "Battery not ready": When the "Battery not ready" signal is active, the red LED (Alarm) is illuminated and relay contact X2.4 X2.5 (Alarm) closed (de-energized position
when unit is disconnected). Causes for the "battery not ready" state in normal operation are as follows: "OFF" operating state, no battery module connected, reversed polarity or defective
battery (battery voltage < 18.5V) or open circuit between battery and UPS module. The interval for polling the operating states ON/OFF, reversed polariy, defective battery or no battery module
connected, open circuit between battery and UPS module, and for activating the relevant signal output is 20 s during normal operation. After the end of the failure the signal remains till to the
next polling.
If the signal flashes in a 2s cycle, this indicates that the battery is defective, but still capable of floating operation. The specified buffering times cannot be kept in such cases. The battery module
must be replaced.
The "Alarm" signal in floating operation means that the battery voltage has dropped to <20.4V and automatic disconnection to protect the battery is imminent. When the battery has been
disconnected due to overload, short circuit, exhaustive discharge protection or buffering timeout, the red LED (Alarm) gets dark, but relay contact X2.4 X2.5 remains closed. Load rating of
relay contacts: 60V DC / 1A or 30V AC / 1A

USB: With module 6EP1931-2FC42, the signals are additionally outputs via a PC-capable USB interface. They are each displayed in the
shape of 5 characters of plain text. The assignment is shown in the table above. A tool for reading out and processing the signals is
available free of charge on the Internet at http://www.ad.siemens.de/sitop. This website also contains further information about the
interface.
Technical specification: The USB interface is according to specification 2.0, the communication runs only at full speed, i.e. 12Mbit/s. The
Interface will be supplied by the DC-UPS with +5V (self-powered), signal state output every 75ms 20%; data output 29ms 20%, pause
46ms 20%. The connection to the PC is made by means of a usual 4-wired shielded USB-cable with a wave-resistance of 90Ohm, a USB
SeriesA connector to the PC and a USB Series B connector to the DC-UPS module and a maximum length of 5m. The cable contains
two 28 to 20 AWG non-twisted USB-supply wires (VBUS and GND) and two 28 AWG twisted pair data wires (D+ and D-).
Pin assignment: Pin1: VBUS (+4.4V to +5.25V DC), transmit data on Pin2 (D-) and Pin3 (D+), Pin4: GND
Receiving data: Receive of the character R (Signal Remote Timerstart) starts the timer of the DC-UPS module with the set buffering time
(table 2) (only with setting max. time and disconnection). After the set buffering time the floating operation ends or the output voltage
will be disconnected.

Signal
Battery ready
Battery not ready

Text

Normal operation
Not normal operation

DC_OK
DC_LO

Not floating operation


Floating operation

*****
*BAT*

>85% charge
<85% charge

BA>85
BA<85

Environment

Standards

Operating conditions acc. to EN 60721-3-3, climate model 3K3 (relative air


humidity 5% to 85%, absolute air humidity 1 g/m3 to 25 g/m3, no condensation)
Stationary operation, weather protected, pollution degree 2
Temperature for storage and shipment:
-40 to +70C
Temperature for operation:
0 to +60C

Degree of protection: IP20 to EN60529 (VDE 0470 Part1)


Protection class III to EN60950
VDE 0100 Part 410 (IEC 364-4-41)
VDE 0106 Part 1 (IEC 536)
VDE 0113 Part 1 (EN 60204-1)
IEC 61131; ; UL 508 / CSA C22.2 File E197259
RI suppression to EN55022, limit-value curve B
Interference immunity to EN 61000-6-2

Weight
6EP1931-2FC21
6EP1931-2FC42

1.1kg
1.1kg

BUFRD
ALARM

Installation Instructions
In order to guarantee effective cooling, the unit must be vertically installed such that the input and output terminals and the incoming air slots are at the bottom. A clearance of at least 50 mm
must be left above and below the unit. Assembly / disassembly see page 8.
To reduce EMI and thermal strain DC-UPS modules and their battery modules should be installed at least 50cm away from commutating chokes ! USB-Interfaces and control leads (ON/OFF
control circuit) must not be laid directly in parallel to power leads or cables (especially leads between frequency converter and motor or frequency converter and commutating choke).
To minimize EMI the distance to those leads should be at least 10cm. Battery modules should be connected low-resistively (4 mm2) and in a cool place (in cubicles usually at the lower end).

Before commencing with the installation or any repair work, switch off the plant main switch and lock it in the "OFF" position. Please read the operating
instructions for SITOP power.
The fuse on the battery module must be removed before any work is carried out.

Maintenance Instructions for Battery modules


To maintain the life cycle of lead gel accumulators as long as possible, it is recommended to discharge them several times down to appr. 19V and then re-charge them (approx. 3 times
discharge / charge, discharge for instance by the DC loads of the plant, buffer time set to maximum; re-charge by DC-UPS module) at the first start-up of the machine.
With pure lead battery modules this is not necessary.

Connection and Terminal Assignments


Terminals

Function

X1.1
X1.3, X1.5
X1.2/X1.4, X1.6
X1.7/X1.8
X2.1,2,3
X2.4,5,6
X2.7,8
X2.9/X2.10
X3

Input voltage DC 24V


Output voltage DC 24V
Input/output voltage DC 0V
Battery module DC 24V
Signal: Normal operation / Floating operation
Signal: Battery not ready / ready
Signal: charge >85%
On/Off jumper (no jumper =Off)
USB-interface

Cable crosssection
0.33 ... 10mm2
22...7 AWG

0.5... 2.5mm2
20...13 AWG

Cable length

Comments

up to 2m

Screw-type terminals for screwdriver with


5mm blade width

up to 2.5m
up to 3m
up to 3m

Recommended tightening torque 1.2Nm


Screw-type terminals for screwdriver with
3.5mm blade width

up to 3m

Recommended tightening torque 0.5-0.7Nm


See description above

CAUTION
The external circuitry of all terminals (including signaling and status contacts) must meet the safety requirements stipulated by
VDE 0805 (EN 60950): SELV.

Siemens AG sterreich, 03/2006

6 of 8

SITOP DC-USV-Modul 40

Tabelle 1: Ladeschlussspannungen bei anderen Akku-Temperaturen


Table 1: End-of-charge voltage for other battery temperatures
Akkumodule Typ Bleigel / Battery type lead gel: 6EP1935-6ME21, 6EP1935-6MF01
-10C
0C
10C
20C
25C
30C
29,0V
28,4V
27,8V
27,3V
27,0V
26,8V

35C
26,7V

40C
26,6V

Tabelle 2: Einstellbare Zuschaltschwellen


Table 2: Adjustable cut-in threshold
gewnschte Zuschaltschwelle [V]
22,5 23,0 23,5 24,0 24,5 25,0

22,0
On1

25,5

Tabelle 3: Einstellbare Ladeschlussspannungen


Table 3: Adjustable end-of-charge voltage
gewnschte Ladeschlussspannung [V]
26,3 26,4 26,5 26,6 26,7 26,8 26,9 27,0 27,1 27,2 27,3 27,4 27,5 27,6 27,7 27,8 27,9 28,0 28,1 28,2 28,3 28,4 28,5 28,6 28,7 28,8 28,9 29,0 29,1 29,2 29,3
On4

Tabelle 4: Einstellbare Pufferzeiten


Table 4: Adjustable buffering time
Schalterstellung / Switch position: On = 1 ; Off = 0
Schalter 1 auf Pos. On: Einstellung um nach der gewnschten Pufferzeit abzuschalten (setting to terminate after the prespecified buffering time)
Schalter 1 auf Pos. Off: Die Abschaltung erfolgt erst bei Erreichen der Tiefentladeschwelle des Akkus. Bei 6EP1931-2FC42 kann im Remote-Betrieb nach der
eingestellten Pufferzeit die Spannung unterbrochen werden ( DIP-Schalter Unterbrechung On)
Setting to terminate when the exhaustive discharge threshold of the battery is reached. Using a 6EP1931-2FC42 an interruption is started by the remote signal. (DIPswitch Disconnection On)

gewnschte Pufferzeit / buffering time [s]


15 25 35 45 55 65 75 85 95 105 115 125 135 145 155 165 175 185 195 205 215 225 235 245 255 265 275 285 295 305 315

On2

gewnschte Pufferzeit / buffering time [s]


325 335 345 355 365 375 385 395 405 415 425 435 445 455 465 475 485 495 505 515 525 535 545 555 565 575 585 595 605 615 625 635
On 2

Siemens AG sterreich, 03/2006

7 of 8

SITOP DC-USV-Modul 40

Herausgegeben vom / Published by


SIMEA Siemens Industrial Manufacturing, Engineering and Applications
Bereich / Group A&D
Siemensstrasse 90-92
A 1210 Wien

Siemens AG sterreich, 03/2006

Siemens AG sterreich All rights reserved.


Liefermglichkeiten und
technische nderungen vorbehalten
Delivery conditions and technical
content subject to changes

8 of 8

SITOP DC-USV-Modul 40

Das könnte Ihnen auch gefallen