TESTING /COMMISSIONING REPORT

Saudi Arabia JOB NO: SAB000565

AL MOUAWASAT HOSPITAL - MADINA


CPO-PC-6A DATE: 09-10-2021 COMMISSIONING BY: MOHAMED ASHIQ
BMS - HVAC SYSTEM DDC No: DDCP-SF-05-05A Revision: 00

BMS - HVAC SYSTEM


State Text/Device
Point Name Point Description Point Type Status Present Value Remark
Type/ Polarity
Fan In Auto Position At
NMH-AUF-013-AutoSts Binary Input NotInAuto;Auto Not Tested
MCC
NMH-AUF-013-Cmd Fan Command Binary Ouput Stop;Start Not Tested

NMH-AUF-013-Filter Dirty Filter Binary Input Normal;Alarm Not Tested

NMH-AUF-013-Flow Duct Air Velocity Sensor Analog Input 0-10V Not Tested
Fan Airflow Status From
NMH-AUF-013-FlowSts Binary Input NoFlow;Flow Not Tested
DPS
NMH-AUF-013-Rh Duct Humidity Analog Input 0-10V Not Tested

NMH-AUF-013-RunSts Fan Run Status From MCC Binary Input Off;On Not Tested

NMH-AUF-013-SpdCtrl VFD Speed Control Analog Output 0-10V Not Tested

NMH-AUF-013-SpdFb VFD Speed Feedback Analog Input 0-10V Not Tested

NMH-AUF-013-Temp Duct Temperature Analog Input NTC 20K Not Tested

NMH-AUF-013-Trip Fan Trip Status From MCC Binary Input Normal;Trip Not Tested
Fan In Auto Position At
NMH-AUF-014-AutoSts Binary Input NotInAuto;Auto Not Tested
MCC
NMH-AUF-014-Cmd Fan Command Binary Ouput Stop;Start Not Tested

NMH-AUF-014-Filter Dirty Filter Binary Input Normal;Alarm Not Tested

NMH-AUF-014-Flow Duct Air Velocity Sensor Analog Input 0-10V Not Tested
Fan Airflow Status From
NMH-AUF-014-FlowSts Binary Input NoFlow;Flow Not Tested
DPS
Not Ready for T&C

DDCP-SF-05-05A Page 1 of 9
Not Ready for T&C
NMH-AUF-014-Rh Duct Humidity Analog Input 0-10V Not Tested

NMH-AUF-014-RunSts Fan Run Status From MCC Binary Input Off;On Not Tested

NMH-AUF-014-SpdCtrl VFD Speed Control Analog Output 0-10V Not Tested

NMH-AUF-014-SpdFb VFD Speed Feedback Analog Input 0-10V Not Tested

NMH-AUF-014-Temp Duct Temperature Analog Input NTC 20K Not Tested

NMH-AUF-014-Trip Fan Trip Status From MCC Binary Input Normal;Trip Not Tested
Fan In Auto Position At
NMH-AUF-015-AutoSts Binary Input NotInAuto;Auto Not Tested
MCC
NMH-AUF-015-Cmd Fan Command Binary Ouput Stop;Start Not Tested

NMH-AUF-015-Filter Dirty Filter Binary Input Normal;Alarm Not Tested

NMH-AUF-015-Flow Duct Air Velocity Sensor Analog Input 0-10V Not Tested
Fan Airflow Status From
NMH-AUF-015-FlowSts Binary Input NoFlow;Flow Not Tested
DPS
NMH-AUF-015-Rh Duct Humidity Analog Input 0-10V Not Tested

NMH-AUF-015-RunSts Fan Run Status From MCC Binary Input Off;On Not Tested

NMH-AUF-015-SpdCtrl VFD Speed Control Analog Output 0-10V Not Tested

NMH-AUF-015-SpdFb VFD Speed Feedback Analog Input 0-10V Not Tested

NMH-AUF-015-Temp Duct Temperature Analog Input NTC 20K Not Tested

NMH-AUF-015-Trip Fan Trip Status From MCC Binary Input Normal;Trip Not Tested

NMH-DEH-124-Cmd Heater On Off Command Binary Ouput Off;On Tested Off;On

NMH-DEH-124-RmTemp Room Temperature Analog Input NTC 20K Tested 23.6 ºC

NMH-DEH-124-Sts Heater On Off Status Binary Input Off;On Tested Off;On

NMH-DEH-126-Cmd Heater On Off Command Binary Ouput Off;On Tested Off;On

NMH-DEH-126-RmTemp Room Temperature Analog Input NTC 20K Tested 21.44 ºC

NMH-DEH-126-Sts Heater On Off Status Binary Input Off;On Tested Off;On

NMH-DEH-127-Cmd Heater On Off Command Binary Ouput Off;On Tested Off;On

NMH-DEH-127-RmTemp Room Temperature Analog Input NTC 20K Tested 19.57 ºC

DDCP-SF-05-05A Page 2 of 9
NMH-DEH-127-Sts Heater On Off Status Binary Input Off;On Tested Off;On

NMH-DEH-128-Cmd Heater On Off Command Binary Ouput Off;On Tested Off;On

NMH-DEH-128-RmTemp Room Temperature Analog Input NTC 20K Tested 22.66 ºC

NMH-DEH-128-Sts Heater On Off Status Binary Input Off;On Tested Off;On

NMH-DEH-129-Cmd Heater On Off Command Binary Ouput Off;On Tested Off;On

NMH-DEH-129-RmTemp Room Temperature Analog Input NTC 20K Tested 23.62 ºC

NMH-DEH-129-Sts Heater On Off Status Binary Input Off;On Tested Off;On

NMH-DEH-130-Cmd Heater On Off Command Binary Ouput Off;On Tested Off;On

NMH-DEH-130-RmTemp Room Temperature Analog Input NTC 20K Tested 21.89 ºC

NMH-DEH-130-Sts Heater On Off Status Binary Input Off;On Tested Off;On

NMH-DEH-131-Cmd Heater On Off Command Binary Ouput Off;On Not Tested Off;On No Access to Reach DEH

NMH-DEH-131-RmTemp Room Temperature Analog Input NTC 20K Tested 26.02 ºC

NMH-DEH-131-Sts Heater On Off Status Binary Input Off;On Not Tested Off;On No Access to Reach DEH

NMH-DEH-132-Cmd Heater On Off Command Binary Ouput Off;On Tested Off;On

NMH-DEH-132-RmTemp Room Temperature Analog Input NTC 20K Tested 22.9 ºC

NMH-DEH-132-Sts Heater On Off Status Binary Input Off;On Tested Off;On

NMH-DEH-133-Cmd Heater On Off Command Binary Ouput Off;On Tested Off;On

NMH-DEH-133-RmTemp Room Temperature Analog Input NTC 20K Tested 24.2 ºC

NMH-DEH-133-Sts Heater On Off Status Binary Input Off;On Tested Off;On

NMH-DEH-134-Cmd Heater On Off Command Binary Ouput Off;On Tested Off;On

NMH-DEH-134-RmTemp Room Temperature Analog Input NTC 20K Tested 22.9 ºC

NMH-DEH-134-Sts Heater On Off Status Binary Input Off;On Tested Off;On

NMH-DEH-135-Cmd Heater On Off Command Binary Ouput Off;On Tested Off;On

NMH-DEH-135-RmTemp Room Temperature Analog Input NTC 20K Tested 23.5 ºC

NMH-DEH-135-Sts Heater On Off Status Binary Input Off;On Tested Off;On

NMH-DEH-136-Cmd Heater On Off Command Binary Ouput Off;On Tested Off;On

DDCP-SF-05-05A Page 3 of 9
NMH-DEH-136-RmTemp Room Temperature Analog Input NTC 20K Tested 22.5 ºC

NMH-DEH-136-Sts Heater On Off Status Binary Input Off;On Tested Off;On

NMH-DEH-138-Cmd Heater On Off Command Binary Ouput Off;On Not Tested Off;On Transformer Fuse Out

NMH-DEH-138-RmTemp Room Temperature Analog Input NTC 20K Tested 19.57 ºC

NMH-DEH-138-Sts Heater On Off Status Binary Input Off;On Not Tested Off;On Transformer Fuse Out

NMH-DEH-139-Cmd Heater On Off Command Binary Ouput Off;On Tested Off;On

NMH-DEH-139-RmTemp Room Temperature Analog Input NTC 20K Tested 19.9 ºC

NMH-DEH-139-Sts Heater On Off Status Binary Input Off;On Tested Off;On

NMH-DEH-140-Cmd Heater On Off Command Binary Ouput Off;On Tested Off;On

NMH-DEH-140-RmTemp Room Temperature Analog Input NTC 20K Tested 24.2 ºC


Needs to check again with proper
NMH-DEH-140-Sts Heater On Off Status Binary Input Off;On Tested Off;On
flow
NMH-DEH-141-Cmd Heater On Off Command Binary Ouput Off;On Tested Off;On

NMH-DEH-141-RmTemp Room Temperature Analog Input NTC 20K Tested 19.8 ºC

NMH-DEH-141-Sts Heater On Off Status Binary Input Off;On Tested Off;On

NMH-DEH-142-Cmd Heater On Off Command Binary Ouput Off;On Tested Off;On

NMH-DEH-142-RmTemp Room Temperature Analog Input NTC 20K Not Tested ºC Sensor missing at location

NMH-DEH-142-Sts Heater On Off Status Binary Input Off;On Tested Off;On

NMH-DEH-143-Cmd Heater On Off Command Binary Ouput Off;On Tested Off;On

NMH-DEH-143-RmTemp Room Temperature Analog Input NTC 20K Tested 23.1 ºC

NMH-DEH-143-Sts Heater On Off Status Binary Input Off;On Tested Off;On

NMH-DEH-144-Cmd Heater On Off Command Binary Ouput Off;On Tested Off;On

NMH-DEH-144-RmTemp Room Temperature Analog Input NTC 20K Tested 21.8 ºC

NMH-DEH-144-Sts Heater On Off Status Binary Input Off;On Tested Off;On

NMH-DEH-145-Cmd Heater On Off Command Binary Ouput Off;On Tested Off;On

NMH-DEH-145-RmTemp Room Temperature Analog Input NTC 20K Tested 24.2 ºC

DDCP-SF-05-05A Page 4 of 9
NMH-DEH-145-Sts Heater On Off Status Binary Input Off;On Tested Off;On

NMH-DEH-146-Cmd Heater On Off Command Binary Ouput Off;On Not Tested Off;On Transformer Fuse Out

NMH-DEH-146-RmTemp Room Temperature Analog Input NTC 20K Tested 19.4 ºC

NMH-DEH-146-Sts Heater On Off Status Binary Input Off;On Not Tested Off;On Transformer Fuse Out

NMH-DEH-147-Cmd Heater On Off Command Binary Ouput Off;On Tested Off;On

NMH-DEH-147-RmTemp Room Temperature Analog Input NTC 20K Tested 21.87 ºC

NMH-DEH-147-Sts Heater On Off Status Binary Input Off;On Tested Off;On

NMH-DEH-148-Cmd Heater On Off Command Binary Ouput Off;On Not Tested Off;On No Power from DP Panel (Trip)

NMH-DEH-148-RmTemp Room Temperature Analog Input NTC 20K Tested 24.17 ºC

NMH-DEH-148-Sts Heater On Off Status Binary Input Off;On Not Tested Off;On No Power from DP Panel (Trip)

NMH-DEH-149-Cmd Heater On Off Command Binary Ouput Off;On Tested Off;On

NMH-DEH-149-RmTemp Room Temperature Analog Input NTC 20K Tested 22.7 ºC

NMH-DEH-149-Sts Heater On Off Status Binary Input Off;On Tested Off;On

NMH-DEH-150-Cmd Heater On Off Command Binary Ouput Off;On Tested Off;On

NMH-DEH-150-RmTemp Room Temperature Analog Input NTC 20K Tested 22.9 ºC

NMH-DEH-150-Sts Heater On Off Status Binary Input Off;On Tested Off;On

NMH-DEH-151-Cmd Heater On Off Command Binary Ouput Off;On Tested Off;On

NMH-DEH-151-RmTemp Room Temperature Analog Input NTC 20K Tested 22.2 ºC

NMH-DEH-151-Sts Heater On Off Status Binary Input Off;On Tested Off;On

NMH-DEH-152-Cmd Heater On Off Command Binary Ouput Off;On Tested Off;On

NMH-DEH-152-RmTemp Room Temperature Analog Input NTC 20K Tested 22.6ºC

NMH-DEH-152-Sts Heater On Off Status Binary Input Off;On Tested Off;On

NMH-DEH-153-Cmd Heater On Off Command Binary Ouput Off;On Tested Off;On

NMH-DEH-153-RmTemp Room Temperature Analog Input NTC 20K Tested 21.9 ºC

NMH-DEH-153-Sts Heater On Off Status Binary Input Off;On Tested Off;On

NMH-DEH-154-Cmd Heater On Off Command Binary Ouput Off;On Tested Off;On

DDCP-SF-05-05A Page 5 of 9
NMH-DEH-154-RmTemp Room Temperature Analog Input NTC 20K Tested 24.1 ºC

NMH-DEH-154-Sts Heater On Off Status Binary Input Off;On Tested Off;On

NMH-DEH-155-Cmd Heater On Off Command Binary Ouput Off;On Not Tested Off;On Discount Switch Not able to find

NMH-DEH-155-RmTemp Room Temperature Analog Input NTC 20K Tested 22.7 ºC

NMH-DEH-155-Sts Heater On Off Status Binary Input Off;On Not Tested Off;On Discount Switch Not able to find

NMH-DEH-156-Cmd Heater On Off Command Binary Ouput Off;On Tested Off;On

NMH-DEH-156-RmTemp Room Temperature Analog Input NTC 20K Tested 23.1 ºC

NMH-DEH-156-Sts Heater On Off Status Binary Input Off;On Tested Off;On

NMH-DEH-157-Cmd Heater On Off Command Binary Ouput Off;On Tested Off;On

NMH-DEH-157-RmTemp Room Temperature Analog Input NTC 20K Tested 24.8 ºC

NMH-DEH-157-Sts Heater On Off Status Binary Input Off;On Tested Off;On

NMH-DEH-158-Cmd Heater On Off Command Binary Ouput Off;On Tested Off;On

NMH-DEH-158-RmTemp Room Temperature Analog Input NTC 20K Tested 22.6 ºC

NMH-DEH-158-Sts Heater On Off Status Binary Input Off;On Tested Off;On

NMH-DEH-159-Cmd Heater On Off Command Binary Ouput Off;On Tested Off;On

NMH-DEH-159-RmTemp Room Temperature Analog Input NTC 20K Tested 23.1 ºC

NMH-DEH-159-Sts Heater On Off Status Binary Input Off;On Tested Off;On

NMH-DEH-160-Cmd Heater On Off Command Binary Ouput Off;On Tested Off;On

NMH-DEH-160-RmTemp Room Temperature Analog Input NTC 20K Tested 24.1 ºC

NMH-DEH-160-Sts Heater On Off Status Binary Input Off;On Tested Off;On


No CMD Provision in the Panel.
NMH-DL-L2-CAT-Cmd Panel On Off Command Binary Ouput Off;On Not Tested Off;On
Please confirm to Remove
NMH-DL-L2-CAT-Flt Panel Fault Status Binary Input Normal;Alarm Tested Normal;Alarm

NMH-DL-L2-CAT-Sts Panel On Off Status Binary Input Off;On Tested Off;On

NMH-DL-L2-SUR-Flt Panel Fault Status Binary Input Normal;Alarm Tested Normal;Alarm

NMH-DL-L2-SUR-Sts Panel On Off Status Binary Input Off;On Tested Off;On

DDCP-SF-05-05A Page 6 of 9
NMH-DP-L2-CAT-Flt Panel Fault Status Binary Input Normal;Alarm Tested Normal;Alarm

NMH-DP-L2-CAT-MECH1-Flt Panel Fault Status Binary Input Normal;Alarm Tested Normal;Alarm

NMH-DP-L2-CAT-MECH1-Sts Panel On Off Status Binary Input Off;On Tested Off;On

NMH-DP-L2-CAT-MECH2-Flt Panel Fault Status Binary Input Normal;Alarm Tested Normal;Alarm

NMH-DP-L2-CAT-MECH2-Sts Panel On Off Status Binary Input Off;On Tested Off;On

NMH-DP-L2-CAT-Sts Panel On Off Status Binary Input Off;On Tested Off;On

NMH-DP-L2-SUR-Flt Panel Fault Status Binary Input Normal;Alarm Tested Normal;Alarm

NMH-DP-L2-SUR-MECH-Flt Panel Fault Status Binary Input Normal;Alarm Tested Normal;Alarm

NMH-DP-L2-SUR-MECH-Sts Panel On Off Status Binary Input Off;On Tested Off;On

NMH-DP-L2-SUR-Sts Panel On Off Status Binary Input Off;On Tested Off;On

NMH-EDLP-L2-CAT-Flt Panel Fault Status Binary Input Normal;Alarm Tested Normal;Alarm

NMH-EDLP-L2-CAT-Sts Panel On Off Status Binary Input Off;On Tested Off;On

NMH-EDLP-L2-SUR-Flt Panel Fault Status Binary Input Normal;Alarm Tested Normal;Alarm

NMH-EDLP-L2-SUR-Sts Panel On Off Status Binary Input Off;On Tested Off;On

NMH-EDP-L2-CAT-UPS-Flt Panel Fault Status Binary Input Normal;Alarm Tested Normal;Alarm

NMH-EDP-L2-CAT-UPS-Sts Panel On Off Status Binary Input Off;On Tested Off;On

NMH-EDP-L2-OR-UPS1-Flt Panel Fault Status Binary Input Normal;Alarm Tested Normal;Alarm

NMH-EDP-L2-OR-UPS1-Sts Panel On Off Status Binary Input Off;On Tested Off;On

NMH-EDP-L2-OR-UPS2-Flt Panel Fault Status Binary Input Normal;Alarm Tested Normal;Alarm

NMH-EDP-L2-OR-UPS2-Sts Panel On Off Status Binary Input Off;On Tested Off;On

NMH-EDP-L2-SUR-UPS-Flt Panel Fault Status Binary Input Normal;Alarm Tested Normal;Alarm

NMH-EDP-L2-SUR-UPS-Sts Panel On Off Status Binary Input Off;On Tested Off;On

NMH-ELV-L10-EmgrShutDw Emergency ShutDown Binary Input Normal;Alarm Not Tested

NMH-ELV-L10-Flt Panel Fault Status Binary Input Normal;Alarm Not Tested

NMH-ELV-L10-Sts Panel On Off Status Binary Input Off;On Not Tested

NMH-ELV-L11-EmgrShutDw Emergency ShutDown Binary Input Normal;Alarm Not Tested

DDCP-SF-05-05A Page 7 of 9 Still No cable in the DDC


NMH-ELV-L11-Flt Panel Fault Status Binary Input Normal;Alarm Not Tested

NMH-ELV-L11-Sts Panel On Off Status Binary Input Off;On Not Tested


Still No cable in the DDC
NMH-ELV-L12-EmgrShutDw Emergency ShutDown Binary Input Normal;Alarm Not Tested

NMH-ELV-L12-Flt Panel Fault Status Binary Input Normal;Alarm Not Tested

NMH-ELV-L12-Sts Panel On Off Status Binary Input Off;On Not Tested

NMH-ELV-L9-EmgrShutDw Emergency ShutDown Binary Input Normal;Alarm Not Tested

NMH-ELV-L9-Flt Panel Fault Status Binary Input Normal;Alarm Not Tested

NMH-ELV-L9-Sts Panel On Off Status Binary Input Off;On Not Tested

NMH-EMDB-GR-LS1-Flt1 Panel Fault Status Binary Input Normal;Alarm Not Tested Normal;Alarm

NMH-EMDB-GR-LS1-Sts1 Panel On Off Status Binary Input Off;On Not Tested Off;On

NMH-ESMDB-L2-SUR-Flt Panel Fault Status Binary Input Normal;Alarm Tested Normal;Alarm

NMH-ESMDB-L2-SUR-Sts Panel On Off Status Binary Input Off;On Tested Off;On


NMH-ESMDB-L2-SUR-UPS- Panel Fault Status Binary Input Normal;Alarm Tested Normal;Alarm
Flt
NMH-ESMDB-L2-SUR-UPS- Panel On Off Status Binary Input Off;On Tested Off;On
Sts
NMH-IPS-L2-CAT-Flt Panel Fault Status Binary Input Normal;Alarm Not Tested As per Site Team it's transfer to
software point, Please confirm to
NMH-IPS-L2-CAT-Sts Panel On Off Status Binary Input Off;On Not Tested Remove
NMH-SMDB-L2-CAT-Flt Panel Fault Status Binary Input Normal;Alarm Tested Normal;Alarm

NMH-SMDB-L2-CAT-Sts Panel On Off Status Binary Input Off;On Tested Off;On

NMH-SMDB-L2-SUR-Flt Panel Fault Status Binary Input Normal;Alarm Tested Normal;Alarm

NMH-SMDB-L2-SUR-Sts Panel On Off Status Binary Input Off;On Tested Off;On

NMH-UVL-023-Change UV Lamp Change Binary Input Normal;Change Not Tested

NMH-UVL-023-Fail UV Lamp Fail Alarm Binary Input Normal;Fail Not Tested

NMH-UVL-024-Change UV Lamp Change Binary Input Normal;Change Not Tested

NMH-UVL-024-Fail UV Lamp Fail Alarm Binary Input Normal;Fail Not Tested

NMH-UVL-025-Change UV Lamp Change Binary Input Normal;Change Not Tested

NMH-UVL-025-Fail UV Lamp Fail Alarm Binary Input Normal;Fail Not Tested


Field Side No termination

DDCP-SF-05-05A Page 8 of 9
Field Side No termination
NMH-UVL-026-Change UV Lamp Change Binary Input Normal;Change Not Tested

NMH-UVL-026-Fail UV Lamp Fail Alarm Binary Input Normal;Fail Not Tested

NMH-UVL-027-Change UV Lamp Change Binary Input Normal;Change Not Tested

NMH-UVL-027-Fail UV Lamp Fail Alarm Binary Input Normal;Fail Not Tested

NMH-UVL-028-Change UV Lamp Change Binary Input Normal;Change Not Tested

NMH-UVL-028-Fail UV Lamp Fail Alarm Binary Input Normal;Fail Not Tested


No. of Not
Total No. of Points: 201 No. of Tested: 128
Tested:
73 64%
General Note:

TESTED BY WITNESSED BY WITNESSED BY

HONEYWELL REPRESENTATIVE MEP CONTRACTOR REPRESENTATIVE CONSULTANT REPRESENTATIVE

Name : Mohamed Ashiq Name : Name :

Signature : Signature : Signature :

DDCP-SF-05-05A Page 9 of 9