Sie sind auf Seite 1von 104

Planmeca Romexis ®

EN

installation manual
10014600_28
Table of contents

1 INTRODUCTION ................................................................................................................. 5
2 SYSTEM REQUIREMENTS ................................................................................................. 6
3 USER ACCOUNT RECOMMENDATIONS ............................................................................ 9
4 NETWORK RECOMMENDATIONS ...................................................................................... 9
5 SECURING IMAGE DATA ................................................................................................... 9
6 KNOWN ISSUES .............................................................................................................. 10
7 LIST OF COMPONENTS TO BE INSTALLED .................................................................... 11
8 INSTALLING PLANMECA ROMEXIS SOFTWARE ............................................................. 12
8.1 Server installation ...................................................................................................................... 14
8.1.1 Romexis server installation path ................................................................................ 15
8.1.2 Installation Summary Dialog ....................................................................................... 15
8.1.3 Romexis server IP address ........................................................................................ 15
8.1.4 MS SQL Server 2012 Express Installation ................................................................. 16
8.1.5 SQL Server Management Studio ............................................................................... 16
8.1.6 Backing Up MS SQL Server 2012 Express ................................................................ 17
8.1.7 Starting Romexis server service ................................................................................. 17
8.1.8 Romexis server under Windows Vista ........................................................................ 18
8.1.9 Romexis server under Windows 7 .............................................................................. 18
8.2 Client installation ....................................................................................................................... 18
8.2.1 DIDAPI driver installation ........................................................................................... 19
8.2.2 Romexis server IP address ........................................................................................ 20
8.2.3 Romexis installation folder ......................................................................................... 20
8.2.4 Installation summary dialog ........................................................................................ 20
8.2.5 Device tool ................................................................................................................. 21
8.2.6 Drivers ........................................................................................................................ 21
9 FINALIZING INSTALLATION ............................................................................................. 24
10 LICENSE INSTALLATION ................................................................................................. 25
11 UPDATING PLANMECA ROMEXIS VERSION ................................................................... 26
12 POST CONFIGURATION .................................................................................................. 28
12.1 Disabling Java update ............................................................................................................... 28
12.2 Changing Client memory settings manually .............................................................................. 28
13 SETTING UP CLINIC MANAGEMENT ............................................................................... 29
13.1 Before you start ......................................................................................................................... 29
13.2 Configuring Romexis server settings ......................................................................................... 29
13.3 Configuring Clinic Management unit connections ..................................................................... 34
13.3.1 Planmeca Sovereign .................................................................................................. 34
13.3.2 Planmeca Sovereign Classic ...................................................................................... 37
13.3.3 Planmeca Compact i Touch v2 .................................................................................. 39
13.3.4 Planmeca Compact i Touch v1 .................................................................................. 42
13.3.5 Planmeca Compact i Classic v2 ................................................................................. 46
13.3.6 Planmeca Compact i Classic v1 ................................................................................. 48
13.3.7 Planmeca ProMax X-ray units .................................................................................... 51
13.3.8 Planmeca PlanMill 40 units ........................................................................................ 53
13.4 Configuring clinic layout ............................................................................................................. 55

Installation manual Planmeca Romexis 1


Table of contents

13.4.1
Creating floorplan(s) ................................................................................................... 55
13.4.2
Adding units to Clinic Management layout ................................................................. 56
13.4.3
Updating dental unit quick reference card / maintenance and infection control instruc-
tions ............................................................................................................................ 56
13.5 Configuring Romexis clients ...................................................................................................... 59
13.5.1 Configuring intraoral camera ...................................................................................... 59
13.5.2 Configuring Planmeca PlanScan scanner .................................................................. 60
14 DIDAPI CONFIGIGURATION TOOL .................................................................................. 61
14.1 Starting Didapi Configuration tool .............................................................................................. 61
14.2 Summary ................................................................................................................................... 62
14.3 Image processing ...................................................................................................................... 64
14.4 Exposure settings (Dixi 1/2/3 only) ............................................................................................ 67
14.5 Network settings ........................................................................................................................ 68
14.6 Misc. settings (ProMax only) ...................................................................................................... 71
14.7 Log ............................................................................................................................................. 71
15 DICOM INTERFACE CONFIGURATION ............................................................................ 74
16 X-RAY DEVICE ETHERNET CONFIGURATION IN TERMINAL SERVER ENVIRONMENT .. 74
17 SETTING UP MS SQL SERVER 2012 EXPRESS BACKUP ................................................ 75
17.1 Introduction ................................................................................................................................ 75
17.2 Configuration ............................................................................................................................. 75
17.3 Setting up scheduled backup ..................................................................................................... 76
18 INSTALLING PLANMECA ROMEXIS IMPLANT LIBRARY .................................................. 79
18.1 Introduction ................................................................................................................................ 79
18.2 Software requirements ............................................................................................................... 79
18.3 List of implants to be installed .................................................................................................... 79
18.4 Installation procedure ................................................................................................................ 79
18.5 Manual installation ..................................................................................................................... 82
19 CONFIGURING PLANMECA ROMEXIS MANUAL FOR PLANMECA ROMEXIS CLIENT ..... 83
20 TROUBLESHOOTING ....................................................................................................... 84
20.1 Romexis server service ............................................................................................................. 84
20.2 DidapiConfig .............................................................................................................................. 84

Appendix A: PMBRIDGE CONFIGURATION


A.1 Windows Registry additions .............................................................................................. 87
A.2 Windows Environment Variable additions .......................................................................... 88
A.3 Users ............................................................................................................................... 88
A.4 Enabling PMBridge connection in Romexis ........................................................................ 89
A.5 Manual setup of the path ................................................................................................... 89

Appendix B: INSTALLING PLANMECA ROMEXIS ON TURKISH WIN-


DOWS

Appendix C: TRANSFERRING / MERGING DATABASES


C.1 Exporting files from one database to another ..................................................................... 94
C.2 Importing database from one location to the other ............................................................. 95

2 Planmeca Romexis Installation manual


Table of contents

Appendix D: ROMEXIS SILENT INSTALLATION

Appendix E: UNINSTALLING PLANMECA ROMEXIS

Appendix F: PLANMECA ROMEXIS LANGUAGE ABBREVIATIONS

Installation manual Planmeca Romexis 3


Table of contents

The manufacturer, assembler and importer are responsible for the safety, reliability and
performance of the unit only if:
- installation, calibration, modification and repairs are carried out by qualified author-
ised personnel
- electrical installations are carried out according to the appropriate requirements such
as IEC 60364
- equipment is used according to the operating instructions.

Planmeca pursues a policy of continual product development. Although every effort is


made to produce up-to-date product documentation this publication should not be re-
garded as an infallible guide to current specifications. We reserve the right to make
changes without prior notice.

COPYRIGHT PLANMECA
Publication number 10014600 Revision 28
Released 12 December 2014

4 Planmeca Romexis Installation manual


1 INTRODUCTION

1 INTRODUCTION
This manual describes the installation and configuration processes for Planmeca Romexis
software revision 3.8.1.R. and MS SQL Server 2012 Express, as well as the required Java
components.

Software technical architecture


Figure 1: 3-Tier-client / server architecture

(SSL)

Installation manual Planmeca Romexis 5


2 SYSTEM REQUIREMENTS

2 SYSTEM REQUIREMENTS
NOTE
Note that these system requirements are recommendations. Not meeting them may lead
to degraded performance.

NOTE
If dozens of dental units are been connected to the same server it is recommended to
double the server resources.

The latest up-to-date system recommendation you can check from www-page:
http://www.planmeca.com/System-requirements

Table 1: 2D imaging system requirements

2D imaging and general


Client workstation Server
Processor Intel Core 2 Duo 2 GHz or better Intel Core 2 Duo 3 GHz or better
RAM 3 GB 3GB
Graphics card Any (integrated or dedicated) Any
Hard disk 80 GB 2 x 500 GB (RAID1 mirroring)
Operating system • Windows Vista Pro (32 or 64 • Windows 2003 Server (32 bit or
bit) 64 bit)
• Windows 7 Pro (32 or 64 bit) • Windows 2008 Server (32 or 64
• Windows 8 Pro & 8.1 Pro (32 bit)
or 64 bit) • Windows 2012 Server (64 bit)
• Windows Vista Pro (32 or 64 bit)
• Mac OS X (Intel)* • Windows 7 Pro (32 or 64 bit)
• Windows 8 Pro & 8.1 Pro (32 or
*Planmeca Romexis 64 bit)
Cephalometric Analysis module is • Mac OS X (Intel)
not supported on Mac OS.

6 Planmeca Romexis Installation manual


2 SYSTEM REQUIREMENTS

Table 2: 3D imaging system requirements

3D imaging
Client workstation Server
Processor Intel Core i5 Desktop or better Intel Core 2 Duo 3 GHz or better
(Core i7 Desktop recommended)
RAM 3D viewing 3D acquisition
workstation workstation
ProMax 3D s: ProMax 3D s:
8 GB 8 GB
ProMax 3D ProMax 3D
Classic: Classic:
8 GB 8 GB
ProMax 3D ProMax 3D 8 GB
Plus: Plus:
8 GB 16 GB
ProMax 3D ProMax 3D
Mid: Mid:
8 GB 16 GB
ProMax 3D ProMax 3D
Max: Max:
8 GB 16 GB
Graphics card NVIDIA or ATI (dedicated GPU) Any
Hard disk 120 GB 2 x 1 TB (RAID1 mirroring)
recommended
Operating system • Windows Vista Pro (64 bit) • Windows 2003 Server (64 bit)
• Windows 7 Pro (64 bit) • Windows 2008 Server (64 bit)
• Windows 8 Pro & 8.1 Pro (32 • Windows 2012 Server (64 bit)
or 64 bit) • Windows Vista Pro (64 bit)
• Mac OS X (Intel)* • Windows 7 Pro (64 bit)
• Windows 8 Pro & 8.1 Pro (32 or
*Planmeca Romexis 64 bit)
Cephalometric Analysis module is • Mac OS X (Intel)
not supported on Mac OS.
*Planmeca Romexis 3D Ortho
Studio module is not supported
on Mac OS.

Installation manual Planmeca Romexis 7


2 SYSTEM REQUIREMENTS

Table 3: CAD/CAM system requirements

CAD/CAM
Client workstation Server
Processor Intel Core i7 Desktop or better Intel Core 2 Duo 3 GHz or better
RAM 16 GB 8 GB
Graphics card • NVIDIA GTX 660 graphics or Any
better (must be NVIDIA)
• Full HD display (1920x1080
resolution)
• Nvidia drivers 320.40 or
newer
Scanner connection Thunderbolt/Firewire 800 port if -
PC is used for scanning
Hard disk For standalone versions 500 GB 2 x 1 TB (RAID1 mirroring)
hard disk or bigger is recommended
recommended
Operating system Windows 8.1 Pro (64 bit) • Windows 2003 Server (64 bit)
• Windows 2008 Server (64 bit)
• Windows 2012 Server (64 bit)
• Windows Vista Pro (64 bit)
• Windows 7 Pro (64 bit)
• Windows 8 Pro & 8.1 Pro (32 or
64 bit)
• Mac OS X (Intel)

Table 4: Common minimum requirements

Common minimum requirements


Client workstation Server
Monitor 1280 x 1024 1280 x 1024
Peripherals DVD ROM or R/W drive DVD ROM or R/W drive
Backup medium None required DAT or equivalent
Database None • MS SQL 2012 Server Express
(included)
• MS SQL 2005 Server
• MS SQL 2008 Server
• MS SQL 2012 Server
• Oracle 10g2
• Firebird (Mac OS X)
Java Platform, Standard Edition Java SE Runtime Environment 6 Java SE Runtime Environment 6
(JRE) (JRE)
(Included in installation) (Included in installation)

8 Planmeca Romexis Installation manual


3 USER ACCOUNT RECOMMENDATIONS

NOTE
Romexis Cephalometric Analysis module is supported on Windows operating systems.

NOTE
Romexis 3D Ortho Studio is supported on 64-bit Windows operating systems.

NOTE
Romexis Planscan and PlanCAD Easy is supported on Windows 8 operating systems.

NOTE
Consult your local dealer for detailed information on device support for different platforms.

3 USER ACCOUNT RECOMMENDATIONS


Required user account during the installation is Administrator.

NOTE
On Windows 7 and Windows 8 operating systems the UAC level must be less than 2.

The user account which starts the Romexis Service on a 64-bit operating system must
have a valid password set (not null).

4 NETWORK RECOMMENDATIONS
The server client communication is based on Java RMI over TCP/IP, thus support for TCP/
IP protocol is required. Network bandwidth requirements are dominated by digital imaging
requirements. The retrieval of a digital 2D image for viewing requires a transfer of roughly
1 MB of data over the network, while opening a 3D volume for viewing will require a
transfer of 250 MB of data, which thus creates a major load on the network and of course
this transfer time dominates the user observable system performance. Planmeca
recommends that for 3D capture and viewing a gigabit Ethernet should be utilized where
possible.

NOTE
Since the Java RMi protocol relies on multiple simultaneous TCP/IP connections at random
ports, RomexisService.exe needs to be allowed full access to all ports above and including
port 1024. Please refer to your fire wall user guide on how to best achieve this. If a fire wall
is not used in the Romexis intranet this requirement can be ignored.

5 SECURING IMAGE DATA


Image data can be secured by backing up the C:\Romexis_images\ folder. The patient
database should be secured using backup tools of the respective database engine. Refer
to the Windows Backup facility or the documentation of your backup solution.

Installation manual Planmeca Romexis 9


6 KNOWN ISSUES

6 KNOWN ISSUES
If the user account with which Romexis Service is started does not have a valid password
set (not null) Romexis server 12-bit JPEG coding does not work.

10 Planmeca Romexis Installation manual


7 LIST OF COMPONENTS TO BE INSTALLED

7 LIST OF COMPONENTS TO BE INSTALLED


The installation software includes installation for the following components.

NOTE
Components that differ in a 64-bit installation are marked with an extension "(64-bit)" in the
installer component selection dialog.

Common Components
• JRE 1.6.0 Update 45 Java Runtime Engine
Required on every Romexis workstation (delivered within Romexis client and server
installations).

Client
• Planmeca Romexis program for Client
PMBridge program for integration with practice management systems and DX loader
included.
• DIDAPI, Planmeca X-ray device driver.
Required on image capturing workstations.
• Device Tool.
Required for 3D an 2D calibrations.
• Dental unit serial communication
Required if Planmeca Compact i (v1) or Planmeca Compact i Classic (v1) is
connected with Romexis Clinic Management.
• Planmeca Proscanner option.
Required on Proscanner workstations.
• VDDS
Required for integration with most of the German practice management systems, this
requires also PMBridge installation.

The following options must be selected separately


• Planmeca Romexis Cephalometric Analysis module option
• Planmeca Romexis 3D OrthoStudio module option
• Planmeca PlanScan and/or PlanCAD Easy
Required on Planscan or PlanCAD Easy workstations.

Server
• Planmeca Romexis program for Server
• Romexis Database
• MS.NET 2.0, 3.5 SP1 and MS.NET 4.0
Manual installation required prior to MS SQL Server 2012 Express installation.
• Planmeca Romexis Webstart Server files

Installation manual Planmeca Romexis 11


8 INSTALLING PLANMECA ROMEXIS SOFTWARE

8 INSTALLING PLANMECA ROMEXIS SOFTWARE


1. Insert the installation CD-ROM into the drive. The installation will automatically start
and the Romexis Installation window appears. Click Next to start the installation.

NOTE
Network installation is not supported in Windows Vista operating system.

2. The License Agreement screen appears. Read the license and select I accept the
terms of the license agreement.
3. Click Next to continue.

12 Planmeca Romexis Installation manual


8 INSTALLING PLANMECA ROMEXIS SOFTWARE

4. Select the language for software and click Next. The language can be later changed
in Romexis Configuration tool.

5. In the following window you may select either Express or Custom installation.
• In case only a single PC is used with Planmeca ProSensor or intraoral camera
select Express installation with predefined settings.
• If you want to choose which components to install select Custom installation and
continue to sections 8.1 "Server installation" on page 14 and 8.2 "Client
installation" on page 18.

6. In the following window select the device you are installing:


• Intraoral camera installation includes Planmeca Romexis client, server and
database
• ProSensor Ethernet installation includes Planmeca Romexis client, server,
database and DIDAPI driver
• ProSensor USB installation includes Planmeca Romexis client, server, database
and Didapi driver and ProSensor USB driver (ProSensor USB driver installation
requires user input during the installation).

Installation manual Planmeca Romexis 13


8 INSTALLING PLANMECA ROMEXIS SOFTWARE

• PlanLink option installs PlanLink components without Planmeca Romexis

7. Click Next.
8. After the installation is completed, follow the instructions in chapter 10 "LICENSE
INSTALLATION" on page 25 and 9 "FINALIZING INSTALLATION" on page 24 to
enable the use of Planmeca Romexis.

8.1 Server installation


1. Check Server Components option on the left side of the window. All needed
components are automatically selected on the right side of the screen. MS SQL
Server 2012 Express is selected as the default database. Required MS.NET versions
are installed if not found on the target computer.
If you want to install Planmeca Romexis files for Webstart Installation on the server
computer check the Romexis Webstart Server Files.
2. Click Next to proceed.

14 Planmeca Romexis Installation manual


8 INSTALLING PLANMECA ROMEXIS SOFTWARE

8.1.1 Romexis server installation path


Define the destination folder for Romexis server installation and click Next. The default
folder is:
C:\Program Files\Planmeca\Romexis
It is not recommended to change the default destination folder..

8.1.2 Installation Summary Dialog


1. Browse through the summary and verify that you have selected all wanted
components.
2. Click Back if you want to change some selections or if correct components are
chosen, click Next.

8.1.3 Romexis server IP address


1. Define the TCP/IP address of the database server computer and click OK.

Installation manual Planmeca Romexis 15


8 INSTALLING PLANMECA ROMEXIS SOFTWARE

The default IP should correspond with the IP address given to Romexis client as
Romexis server IP address. The default IP 127.0.0.1 equalling to local host is
provided by default.

2. After giving the TCP/IP address the Romexis automatically continues installing the
next component on the list.

8.1.4 MS SQL Server 2012 Express Installation


This procedure will install an instance of MS SQL Server 2012 Express on the server
computer. MS SQL Server 2012 Express depends on Microsoft .NET Framework versions
3.5 and 4.0, which have to be installed manually prior to starting the MS SQL Server
installation.
On Windows 8 operating system MS.NET MS.NET 3.5 SP1 can be enabled in Control
Panel --> Programs and Features --> Turn On/off Windows Features. This process
requires internet access. If no Internet connection is available, the .NET 3.5 SP1
framework can be installed using the Windows installation DVD or ISO-image.
The installer packages of NET frameworks for other operating systems than Windows 8
for manual installation can be found from the installation DVD’s folder \MSSQL :
• .NET 3.5 SP 1 installer for Windows Server 2008 and Windows Vista.
• .NET 4.0 installer for Windows Vista SP1, Windows Server 2008, Windows Server
2008 R2, Windows 7 SP1, Windows Server 2008 R2 SP1.
MS.NET installations can be verified from Windows registry keys (type "regedit" in
Windows Terminal):
Computer\HKEY_LOCAL_MACHINE\SOFTWARE\Microsoft\
NET Framework Setup\NDP\v2.0.50727 (MS.NET 2.0)
Computer\HKEY_LOCAL_MACHINE\SOFTWARE\Microsoft\
NET Framework Setup\NDP\v3.5 (MS.NET 3.5)
Computer\HKEY_LOCAL_MACHINE\SOFTWARE\Microsoft\
NET Framework Setup\NDP\v4 (MS.NET 4.0)

The following database instance and user are created:


Database Instance: ROMEXIS
Database User: romexis

8.1.5 SQL Server Management Studio


SQL Server Management Studio, a graphical tool for managing SQL Server, is provided
on the Install CD and can be separately installed if needed. It can be found under:

16 Planmeca Romexis Installation manual


8 INSTALLING PLANMECA ROMEXIS SOFTWARE

InstallCD\Tools\SQL Server Management Studio

8.1.6 Backing Up MS SQL Server 2012 Express


For more information on how to back up MS SQL Server 2012 Express see 17 "SETTING
UP MS SQL SERVER 2012 EXPRESS BACKUP" on page 75.
1. Enter the Romexis Webstart Server IP address. Click OK.

2. In an update installation of the webstart server files, the installer asks if the user wants
to reconfigure the server configuration files' ip-addresses. If you select Yes, you are
prompted for new ip-address for the configuration files.

8.1.7 Starting Romexis server service


1. Start the Romexis server service in the next opening window. Click Start Service.
2. Click OK in the Service (re)started window.

Installation manual Planmeca Romexis 17


8 INSTALLING PLANMECA ROMEXIS SOFTWARE

3. Click Done.

8.1.8 Romexis server under Windows Vista


1. Start the Romexis server as in the previous chapter 8.1.7 "Starting Romexis server
service" on page 17. Click Start Service.
2. If a message box stating: ‘Failed to make sure that the server is running!’ appears,
click OK in the message box to ignore the message.

The service will start automatically after rebooting the computer at the end of the
installation.
3. Click Done.

8.1.9 Romexis server under Windows 7


1. Start the Romexis server as in the previous chapter 8.1.7 "Starting Romexis server
service" on page 17. Click Start Service.
2. If an error message pops up stating ‘Access denied’, click Done and go to the folder
C:Program Files\Planmeca\RomexisServiceCtrl.exe right-click on the file
RomexisServiceCtrl.exe and select Run as Administrator.

8.2 Client installation

NOTE
The following dialogue appears only in case DIDAPI was selected in Component selection
dialogue.

1. Select Client Components and Common Components on the left and deselect Server
Components.
All required basic components for Client are automatically selected on the right side of
the window:
• Client program
• Device tool: required for 3D an 2D calibrations.
Additional options include:
• Cephalometric Analysis module
• 3D Ortho Studio module

18 Planmeca Romexis Installation manual


8 INSTALLING PLANMECA ROMEXIS SOFTWARE

• CAD/CAM module
• ProScanner module
• To install Dental unit serial communication files for Planmcea Compact i (v1) and
Compact i Classic (v1) dental unit communication check also Dental unit serial
communication.
• To install DIDAPI files check also DIDAPI.
2. Click Next.

8.2.1 DIDAPI driver installation


1. Click Next in the Planmeca X-Ray Interface Setup window.
2. Select DIDAPI and device drivers, and:
• If capturing images with 3rd party software via DIDAPI UI User Interface, select
additionally DIDAPI UI Support for Integrators.
• If capturing images via Planmeca TWAIN Source, select additionally TWAIN
Source Capture.
• If capturing images with ProSensor USB select additionally ProSensor USB
Driver. This feature is intended for ProSensor ControlBox version 2.0.1.R or
newer.

3. Click Next.

Installation manual Planmeca Romexis 19


8 INSTALLING PLANMECA ROMEXIS SOFTWARE

8.2.2 Romexis server IP address


1. Define the TCP/IP address of the database server computer and click OK.
The default IP 127.0.0.1 equalling to local host is provided by default.

2. After having typed the TCP/IP address the Romexis automatically continues installing
the next component on the list.

8.2.3 Romexis installation folder


1. Define the destination folder (the default folder is C:\Program
Files\Planmeca\Romexis) and click Next.
It is not recommended to change the default destination folder.

8.2.4 Installation summary dialog


1. Browse through the summary and verify that you have selected all wanted
components.

20 Planmeca Romexis Installation manual


8 INSTALLING PLANMECA ROMEXIS SOFTWARE

2. Click Back if you want to change some selections or if correct components are
chosen, click Next.

8.2.5 Device tool


If you have selected the Device tool option the following window appears. Click Next.

8.2.6 Drivers
The installation of drivers will start automatically.
The following windows appear if Planmeca ProScanner and/or ProSensor option was
selected in client or Didapikit installation.

Installation manual Planmeca Romexis 21


8 INSTALLING PLANMECA ROMEXIS SOFTWARE

1. In the following windows click Install.

2. When drivers have bee successfully installed the following window appears. Click
Close.

22 Planmeca Romexis Installation manual


8 INSTALLING PLANMECA ROMEXIS SOFTWARE

3. In the following window click Finish.

Installation manual Planmeca Romexis 23


9 FINALIZING INSTALLATION

9 FINALIZING INSTALLATION
1. Select View Romexis Installation Log and View Romexis Bulletin Folder and click
Finish to complete the Romexis setup.

2. The following window appears. Select Yes and OK to reboot the computer.

3. After server installation, follow the instructions in chapter 10 "LICENSE


INSTALLATION" on page 25 to enable the use of Planmeca Romexis.
4. If you have PlanLink installed, start PlanLink Service from Windows Start menu ->
Programs -> Planmeca -> PlanLink Service Control.
5. To start Planmeca Romexis, double-click the Planmeca Romexis icon on the desktop
or choose Planmeca Romexis from the Windows Start menu -> Programs ->
Planmeca -> Planmeca Romexis.

24 Planmeca Romexis Installation manual


10 LICENSE INSTALLATION

10 LICENSE INSTALLATION
NOTE
License installation is only possible on Romexis server computer.

1. To start the License Installer from Windows Start Menu click Programs --> Planmeca
--> Install Romexis License.
2. The License Installer will ask for the location of the license file which is provided on a
separate License CD when purchasing Planmeca Romexis. Select the folder in which
the license file (romexis.lic) can be found and choose Next.

3. Click Install.

4. After the installation is completed, remember to restart the Romexis service in order to
activate the license installation.

Installation manual Planmeca Romexis 25


11 UPDATING PLANMECA ROMEXIS VERSION

11 UPDATING PLANMECA ROMEXIS VERSION


1. Insert the CD-ROM into the drive and follow the instructions on the Installation window
that will appear on the screen.

NOTE
A 32-bit installation on a 64-bit operating system cannot be updated directly to a 64-bit
version. First an uninstallation is required followed by a fresh 64-bit installation of Planmeca
Romexis.

2. Select Modify Installation and click Next.

3. Install Wizard will prompt for an update confirmation. Click Yes to continue.

4. Select the same components that you have installed in a fresh Server/Client/
Standalone installation.
Additionally, you can also select new features. If you are updating a server
installation, remember to select Romexis Database from the Server Components.

26 Planmeca Romexis Installation manual


11 UPDATING PLANMECA ROMEXIS VERSION

This applies only to MS SQL Server databases. In case of Oracle or Solid database,
deselect the options MS SQL Server and Planmeca Romexis Database from Server
Components and run the database update scripts manually.

NOTE
Make sure to select all those Planmeca Romexis components that are installed on the
target computer. If you deselect a component that is already installed it will be removed
from the computer.

The Planmeca Romexis Cephalometric analysis module can be found under Client
components.
5. Follow the instructions in section 10 "LICENSE INSTALLATION" on page 25, or in
section 9 "FINALIZING INSTALLATION" on page 24 depending on your installation
type.

Installation manual Planmeca Romexis 27


12 POST CONFIGURATION

12 POST CONFIGURATION

12.1 Disabling Java update


After the Romexis installation Java automatic update must be disabled in order to
eliminate version conflicts and update problems. Proceed as follows:
Browse to Windows Control Panel --> Java --> Advanced, and select Never Auto-
Download. Click OK.

12.2 Changing Client memory settings manually


The required Java-xmx and minimum memory settings for different setups are listed in the
following table.

Setup Recommended Client Minimum installed


Java-xmx setting Memory

Planmeca ProSensor 500m 3 GB


Standard installation (32-bit OS) 1200m 3 GB
Planmeca ProMax 3D & 3D s 6000m 8 GB
(64-bit OS)
Planmeca ProMax 3D Mid & Max, Acquisition Workstation: 16GB 8000m
HD Modes (64-bit OS) Viewing Workstation:
8GB 6000m

If needed, modify the Romexis client memory setting accordingly in Romexis.bat file
located in the C:\Program Files\Planmeca\Romexis\client folder.

28 Planmeca Romexis Installation manual


13 SETTING UP CLINIC MANAGEMENT

13 SETTING UP CLINIC MANAGEMENT

13.1 Before you start


Before setting up and configuring Clinic Management, plan carefully the following issues:
• Plan for IP addresses and port numbers used in the network.
• Take care that there are no software firewall settings in the Romexis server or
Romexis client computers, and no hardware firewalls in the network, blocking the
ports used by the Clinic Management.
• Plan for naming the devices connected to the Clinic Management, i.e. the names
given for the dental units, Romexis client PCs connected to the dental units, X-ray
devices etc.
• Plan for clinic layout including floor plan picture files, naming rooms/working areas
etc.
• When planning, keep in mind possible new devices added later to the Clinic
Management.
• Get acquainted with the Clinic Management and its functions, see Planmeca Romexis
User’s manual (publication number 10014593).

NOTE
To use Clinic Management module of the Romexis software, the license file (installed in
section 10 "LICENSE INSTALLATION" on page 25) must include the license for using the
Clinic Management module.

NOTE
If several Romexis instances are installed to the same PC, be extra careful with port
numbers given to the different server/services running in the PC - each of them must have
an unique port number.

13.2 Configuring Romexis server settings

1. Start Romexis Configuration tool, in Windows Start menu, click All Programs -->
Planmeca --> Romexis Configuration.
Romexis Configuration login screen appears.

2. To login, enter:
Username: sysadm
Password: promax

Installation manual Planmeca Romexis 29


13 SETTING UP CLINIC MANAGEMENT

Romexis Configuration screen appears.

3. From the directory tree on the left side, under Server Parameters, click Server.
Related parameters appears to the right panel.

4. Check and/or set the values for the following parameters, listed in the table below.

Parameter/setting Description
RMI - Server/Client Communication
RMI Server Host Defines the Romexis server IP address or DNS name.
RMI Server Port Defines the port for Romexis server-client-communication.
Default value is normally ok. Change only in some special cases, e.g. there
are more than one instance of Romexis installed to the same PC.
Class Server

30 Planmeca Romexis Installation manual


13 SETTING UP CLINIC MANAGEMENT

Parameter/setting Description
Class Server Enabled If this option is selected, the Romexis server provides the latest Romexis
connection classes to Romexis connection proxies which communicate with
the dental units.
Class Server provides also other files for the Romexis clients, including
dental unit quick reference card, maintenance and infection control
instructions and dental unit control panel.
Enable this setting (by default this is disabled).
Class Server Port This is the port the server listens to.
Default value is normally ok. Change only in some special cases, e.g. there
are more than one instance of Romexis installed to the same PC.
Unit Communication (PlanLink)
Diagnostics Enabled Enables the communication between Planmeca units.
This must be enabled (by default this is disabled).
Unit Time Sync Enabled If enabled, the time in the dental units connected to the Clinic Management is
synchronised by the Romexis server.
By default enabled, keep enabled.
Diagnostics Port Defines the port number for diagnostics communication.
Default value is normally ok. Change only in some special cases, e.g. there
are more than one instance of Romexis installed to the same PC.

NOTE
Write down the Diagnostics Port parameter value, you will need it later when configuring
units’ Clinic Management connections.
Unit Monitoring / Controlling
Port range begin Sets the smallest port number included to the range of unit monitoring.
Default value is 6000.
Port range end Sets the biggest port number included to the range of unit monitoring.
Default value is 6700.
For example, with default values, unit monitoring port number range is 6000 -
6700.
Usually the default values are sufficient, only if there is a huge number of
units to be connected to the Clinic Management, the range must be
extended.

For the rest of the parameters in the panel, leave the default values.

Installation manual Planmeca Romexis 31


13 SETTING UP CLINIC MANAGEMENT

5. From the directory tree on the left side, under Clinic Management, click PlanLink &
Diagnostics. Related parameters appears to the right panel.

6. Check and/or set the values for the following parameters, listed in the table below.

Parameter/setting Description
Clinic overview and Log Refresh-rate
Show large icons By enabling this setting, the unit icons in the clinic layout are in bigger format.
By default this is diasabled.
E.g. if there are only few units and the floor plan figures are spacious, this can
be enabled.
Note, you can change this setting later when adding units to the clinic layout,
if it seems that bigger icons are more appropriate.
Dental Unit User Settings
Send Service Modes By enabling this setting, it is possible to modify dental unit service mode
settings remotely from Romexis server.
In normal operation this should be left disabled but can be useful at dental
unit installations if numerous new dental units must be configured identically.
NOTE, if enabled temporarily for installing purposes, remember to disable this
setting after completing the installations.
E-mail Notifications
Romexis server can be configured to send alert e-mails when specific diagnostic events take place in dental
units. Romexis sends the e-mails to the SMTP server configured with these settings. The device alerts
triggering the e-mails are configured in the Romexis Admin module.
Note that Romexis server software does not include the SMTP server but the service must externally be
available.
If e-mail notifications is not taken into use, leave these parameters as defaults.
SMTP Server Host Name Defines the SMTP server host.

32 Planmeca Romexis Installation manual


13 SETTING UP CLINIC MANAGEMENT

Parameter/setting Description
SMTP Server Port Defines the SMTP server port.
Notification period (mins) Defines the delay in minutes after which an error is considered to be
important enough to be reported in an e-mail. If an error is negated by itself or
fixed by a user within this time limit, then no error will be reported. The error
will still be shown in the dental unit event log.
Don't e-mail for same error Defines the time limit in minutes during which a persistent error will not be
in (mins) reported again.

For the rest of the parameters in the panel, leave the default values.
7. From the directory tree on the left side, under Image & Data Management, click Data
Folderts. Related parameters appears to the right panel.

8. The Romexis Data Folders settings sheet allows re-configuration of the Romexis
image, cache and ergodata (dental unit diagnostic data) storage paths.
For more information on the needed disk space, see section 2 SYSTEM
REQUIREMENTS.
To change the data folder location, follow the steps below:
a. Click Set Path button.
b. Browse or enter the new storage path.
c. Click Yes to confirm to create new storage folders.
If the given path is valid, the romexis_images, romexis_cache and
romexis_ergodata folders will be automatically created under it.
After Romexis server restart the all new Romexis image, cache and ergodata will be
stored to the new location.
9. Click OK to save the changes and exit Romexis Configuration tool.
10. Restart the Romexis server to activate changes:
a. In Windows Start menu, click All Programs --> Planmeca --> Start Romexis
Service.

b. Click Stop Service.

Installation manual Planmeca Romexis 33


13 SETTING UP CLINIC MANAGEMENT

c. Click Start Service.

d. Click OK.
e. Click Done.

13.3 Configuring Clinic Management unit connections

13.3.1 Planmeca Sovereign

Physical LAN connection


It is assumed that during the Sovereign dental unit installation, the Ethernet cable from the
dental unit is connected and routed to the local area network.

Romexis server

LAN

Ethernet cable

Configuring dental unit


The Planmeca Service Tool (PST) is used for configuring Sovereign dental unit Clinic
Management settings. In this manual, only a short description of using the PST is given,
for detailed information on using the PST, see section PLANMECA SERVICE TOOL in
Planmeca Sovereign Technical manual.

1. Remove the necessary cuspidor covers and connect the computer to the dental unit
ACCU PCB as shown on the figure below.
S258.eps

Ethernet cable

34 Planmeca Romexis Installation manual


13 SETTING UP CLINIC MANAGEMENT

2. Start PST. When the PST is started the user needs to input a pin code. The pin code
is 1701.
3. In the appearing window, click Unit Config. tab.
Username and password dialogue opens.
4. Enter username and passowrd:
User name: pmsovereign
Password: sovereignpm
Sovereign service mode interface opens, see figure below.

5. Click Unit options.

Installation manual Planmeca Romexis 35


13 SETTING UP CLINIC MANAGEMENT

Menu for unit options screen opens, see the figure below (note, that the window
appearance and contents depends on the software version).

6. Modify the values under Network configuration: title (in the right bottom corner) as
described below:
• IP address
Defines dental unit own IP address. Set (if not yet modified during the installation)
according to the IP network plan.

36 Planmeca Romexis Installation manual


13 SETTING UP CLINIC MANAGEMENT

• Netmask
Defines subnet mask. Set if needed.
• Gateway
Defines default gateway. Set if needed.
• PMU Server
Defines the Romexis server IP address. Set according to the IP network plan.
• Hostname
Defines the dental unit name, visible in the Clinic Management. Set according to
the device naming plan.
7. Click Save SW options button.
8. Exit the PST.
9. Reboot the dental unit.

13.3.2 Planmeca Sovereign Classic

Physical LAN connection


It is assumed that during the Sovereign Classic dental unit installation, the Ethernet cable
from the dental unit is connected and routed to the local area network.

Romexis server

LAN

Ethernet cable

Configuring dental unit

NOTE
Follow carefully the order of the steps below - it is important to configure the dental unit’s
network settings (steps 1 - 4) before enabling the Romexis connection (step 5).

1. Touch the Program and About this unit button.

Installation manual Planmeca Romexis 37


13 SETTING UP CLINIC MANAGEMENT

The following information is displayed in the About this unit window (the figure below
is an example only).

2. Touch Network settings arrow (>) to open the network settings menu.

In the menu, you can scroll the list either from the list itself, from the scroll bar to the
right, or by using the Up and Down buttons.
Those settings that can be changed have an Edit button next to them. Press the Edit
button to open a new window where you can edit the setting.
You will be prompted to enter the PIN-code 1701.
3. Edit the following settings in the Network settings menu.
• Name
The name of the dental unit shown in the Romexis. The unit name must be unique
and it has to be changed before connecting the unit to the Romexis.

38 Planmeca Romexis Installation manual


13 SETTING UP CLINIC MANAGEMENT

• IP address
The dental unit’s IP address. The IP address must be unique.
• Network mask
Subnet mask. The default is 255.255.255.0.
• Gateway
Default gateway. The default is 0.0.0.0.
• Romexis server IP address
IP address of the Romexis server, as defined in Romexis Configuration tool
(Server Parameters --> Server --> RMI Server Host setting).
• Romexis server port
Diagnostics server port, as defined in Romexis Configuration tool (Server
Parameters --> Server --> Diagnostics Port setting).
The default is 6812. Change the this setting only if you have changed the default
port 6812 to some other port in Romexis configuration (in step 4 on page 30).
4. Enable Romexis connection.
Toggle the arrow button to enable the connection to the Romexis.
5. Press OK to save the changes and reboot the dental unit.

When the connection is enabled, the Romexis icon can be seen on the control panel:
• When the icon background is blue, the connection is enabled and active.
• When the icon background is grey, the connection is enabled, but the Romexis is off
or not connected.

13.3.3 Planmeca Compact i Touch v2

NOTE
These instruction are valid only for Planmeca Compact i Touch v2 dental unit, if you
connect Planmeca Compact i Touch v1, see instructions given in section 13.3.4 "Planmeca
Compact i Touch v1" on page 42.

Physical LAN connection


An example installation of the system is shown on the figure below.
Compact i v2

Ethernet
interface

Romexis server

LAN

Ethernet cable

1. Open the cuspidor door and remove the electronics control box cover.

Installation manual Planmeca Romexis 39


13 SETTING UP CLINIC MANAGEMENT

2. Connect the Ethernet cable to the connector located on the right upper corner of the
Main PCB.

3. Route the Ethernet cable from the cuspidor to local area network (LAN).

Configuring dental unit

NOTE
Follow carefully the order of the steps below - it is important to configure the dental unit’s
network settings (steps 1 - 4) before enabling the Romexis connection (step 5).

1. Touch the Program and About this unit button.

The following information is displayed in the About this unit window (the figure below
is an example only).

40 Planmeca Romexis Installation manual


13 SETTING UP CLINIC MANAGEMENT

2. Touch Network settings arrow (>) to open the network settings menu.

In the menu, you can scroll the list either from the list itself, from the scroll bar to the
right, or by using the Up and Down buttons.
Those settings that can be changed have an Edit button next to them. Press the Edit
button to open a new window where you can edit the setting.
You will be prompted to enter the PIN-code 1701.
3. Edit the following settings in the Network settings menu.
• Name
The name of the dental unit shown in the Romexis. The unit name must be
unique and it has to be changed before connecting the unit to the Romexis.
• IP address
The dental unit’s IP address. The IP address must be unique.
• Network mask
Subnet mask. The default is 255.255.255.0.
• Gateway
Default gateway. The default is 0.0.0.0.
• Romexis server IP address
IP address of the Romexis server, as defined in the Romexis Configuration tool
(Server Parameters --> Server --> RMI Server Host setting).
• Romexis server port
Diagnostics server port, as defined in Romexis Configuration tool (Server
Parameters --> Server --> Diagnostics Port setting).
The default is 6812. Change the this setting only if you have changed the default
port 6812 to some other port in Romexis configuration (in step 4 on page 30).
4. Enable Romexis connection.
Toggle the arrow button to enable the connection to the Romexis.
5. Press OK to save the changes and reboot the dental unit.

When the connection is enabled, the Romexis icon can be seen on the control panel:
• When the icon background is blue, the connection is enabled and active.

Installation manual Planmeca Romexis 41


13 SETTING UP CLINIC MANAGEMENT

• When the icon background is grey, the connection is enabled, but the Romexis is off
or not connected.

13.3.4 Planmeca Compact i Touch v1

NOTE
These instruction are valid only for Planmeca Compact i Touch v1 dental unit, if you
connect Planmeca Compact i Touch v2, see instructions given in section 13.3.3 "Planmeca
Compact i Touch v2" on page 39.

Configuring LAN and dental unit settings


Planmeca Compact Touch v1 requires Ethernet adapter to be connected to the local area
network. An example installation of the system is shown on the figure below.

Compact i v1

Planet
output

Ethernet Romexis server


adapter

LAN

Ethernet cable

1. Open the cuspidor door and remove the electronics control box cover.
2. Connect the Planet cable to the connector located on the left upper corner of the Main
PCB and connect the other end of the Planet cable to the adapter box (white arrows,
figure 2).
3. Attach the Ethernet adapter box to the cuspidor support plate (black arrow, figure 2).
4. Connect Ethernet cable to the adapter box (grey arrow, figure 2).

42 Planmeca Romexis Installation manual


13 SETTING UP CLINIC MANAGEMENT

Figure 2: Connecting Ethernet adapter box

5. Connect the other end of Ethernet cable (connected in the previous step) to a PC
which is configured to a 10.0.0.x subnet.
The dental unit default IP address is 10.0.0.1. This must be changed to the clients IP
network configuration.
6. At this point, go to the dental unit’s control panel and change the dental unit’s service
mode 201 to value 1, follow the steps below:
a. Touch the Program and then Service mode buttons.
b. Enter PIN code (1701), and touch OK button.
c. Move to the service mode 201 using the up and down arrow buttons.
d. Touch SET button until the yellow indicator light turns on (1 or 5 seconds,
depending on the service mode).
e. Set the value to 1 using the minus (-) and/or the plus (+) buttons.
f. Touch the SET button until the indicator light turns off.
g. To store and activate the new setting and exit the service mode, touch Program
button.
7. Open a web browser in the computer connected to the Ethernet cable (step 5 on page
43) and enter 10.0.0.1 to the address field.
8. To login, enter:
Username: admin
Password: PASS
Ethernet adapter web configuration page appears.
9. Select Network --> Configuration.
10. Enter dental unit’s IP address and netmask to the IP address field.
The IP address and netmask are entered to the IP address field in format:

Installation manual Planmeca Romexis 43


13 SETTING UP CLINIC MANAGEMENT

10.0.0.1 255.255.255.0
11. Click Submit button.
12. Restart the dental unit.
13. Connect the PC to the dental unit equipped with new IP address to verify the
connection.
Make the connection as described earlier, but note that you must configure the PC to
the same subnet than you configured the dental unit.
14. If the connection works, connect the Ethernet cable from the cuspidor (Ethernet
adapter) to local area network (LAN).
Carry out the steps above for all Planmeca Compact i Touch (v1) dental units to be added
to the Clinic Management.

Adding Planmeca Compact i Touch to Romexis software


Before starting, it is recommended to create a list of all Planmeca Compact i Touch (v1)
dental units to be added to the Clinic Management. The list should contain the name and
IP addresses of each dental unit.
1. Start Romexis Configuration, in Windows Start menu, click All Programs -->
Planmeca --> Romexis Configuration. To login, enter:
Username: sysadm
Password: promax
2. From the directory tree on the left side, under Clinic Management, click Dental Unit
Connections.
3. Click Add button.
4. Enter the needed information to the appearing window.
Note, that the name, IP address and Romexis server port must be unique.
• The dental unit IP must be same as entered when the Ethernet adapter was
configured in 13.3.4 "Planmeca Compact i Touch v1" on page 42, step 10.
• The Romexis server port can be any port that is not used.

5. Configure all Compact i Touch (v1) dental units in the same way.
6. From the directory tree on the left side, under Clinic Management, click Dental Unit
Connections.

44 Planmeca Romexis Installation manual


13 SETTING UP CLINIC MANAGEMENT

7. Under Romexis Server Settings, mark Enable Communication Service selection.

NOTE
Do NOT enable the Enable Log (Troubleshooting only) setting.

8. Restart the Romexis server to activate changes:


a. From the directory tree on the left side, under Start-up, click Romexis Server.
b. Click first Stop Service and then Start Service.

9. From the directory tree on the left side, under Server Parameters, click Server, and
under Unit Communication (PlanLink), mark Diagnostics Enabled selection.

10. Restart the Romexis server to activate changes:


a. From the directory tree on the left side, under Start-up, click Romexis Server.
b. Click first Stop Service and then Start Service.

After restart, the Planlink proxy process is started, which enables the communication
between Romexis and Planmeca Compact i Touch (v1) dental units.

Installation manual Planmeca Romexis 45


13 SETTING UP CLINIC MANAGEMENT

13.3.5 Planmeca Compact i Classic v2

Physical LAN connection


An example installation of the system is shown on the figure below.
Compact i v2

Ethernet
interface

Romexis server

LAN

Ethernet cable

1. Open the cuspidor door and remove the electronics control box cover.
2. Connect the Ethernet cable to the connector located on the right upper corner of the
Main PCB.

Configuring dental unit


1. Connect the other end of Ethernet cable (connected in the previous step) to a PC
which is configured to a 10.0.0.x subnet.
The dental unit default IP address is 10.0.0.1. This must be changed to the clients IP
network configuration.
2. Open a web browser in the computer connected to the Ethernet cable (step 1 on page
46) and enter 10.0.0.1 to the address field.
A PIN code dialogue appears.
3. Enter the PIN code 1701 and click Login button.

46 Planmeca Romexis Installation manual


13 SETTING UP CLINIC MANAGEMENT

Unit configuration interface opens to the browser, an example figure below.

4. Modify the values under Change settings: title as described below:


• Unit name
Defines the dental unit name, visible in the Clinic Management. Set according to
the device naming plan. The name must be unique.
• Inet addr.
Defines dental unit own IP address. Set (if not yet modified during the installation)
according to the IP network plan. The IP address must be unique.
• Mask
Defines subnet mask. The default value is 255.255.255.0.
• Gateway
Defines default gateway. The default value is 0.0.0.0.
• Romexis addr.
IP address of the Romexis server, as defined in the Romexis Configuration tool
(Server Parameters --> Server --> RMI Server Host setting).
• Romexis port
Diagnostics server port, as defined in Romexis Configuration tool (Server
Parameters --> Server --> Diagnostics Port setting).
The default is 6812. Change the this setting only if you have changed the default
port 6812 to some other port in Romexis configuration (in step 4 on page 30).
• Mode (SM210)
Set this to value 1 or 2.
5. Click Save button.
6. Exit the browser.

Installation manual Planmeca Romexis 47


13 SETTING UP CLINIC MANAGEMENT

7. Reboot the dental unit.


8. Route the Ethernet cable from the cuspidor to local area network (LAN).

13.3.6 Planmeca Compact i Classic v1

Configuring LAN and dental unit settings


Planmeca Compact i Classic v1 requires Ethernet adapter to be connected to the local
area network. An example installation of the system is shown in the figure below.
Compact i v1

Planet
output

Ethernet Romexis server


adapter

LAN

Ethernet cable

1. Open the cuspidor door and remove the electronics control box cover.
2. Connect the Planet cable to the connector located on the left upper corner of the Main
PCB and connect the other end of the Planet cable to the adapter box (white arrows,
figure 3).
3. Attach the Ethernet adapter box to the cuspidor support plate (black arrow, figure 3).
4. Connect Ethernet cable to the adapter box (grey arrow, figure 3).

48 Planmeca Romexis Installation manual


13 SETTING UP CLINIC MANAGEMENT

Figure 3: Connecting Ethernet adapter box

5. Connect the other end of Ethernet cable (connected in the previous step) to a PC
which is configured to a 10.0.0.x subnet.
The dental unit default IP address is 10.0.0.1. This must be changed to the clients IP
network configuration.
6. At this point, go to the dental unit’s control panel and change the dental unit’s service
mode 201 to value 1, follow the steps below:
a. Enter service mode:
1) Press the program key and hold it down.
2) Press the operating light key until you hear a beep (approx. 2 seconds).
3) Then press the bowl rinse/glass fill key until you hear a beep (approx. 2
seconds).
4) Release both keys (program key & bowl rinse/glass fill key). The display briefly
shows “SEr” when service mode is entered.
b. Navigate to the service mode number 201:
To move to the required service mode, use the chair up and down keys (“C” or
“D”) on the control panel.
c. Enter the SET-mode by pressing and holding the “S”-key until the yellow indicator
light turns on (1 or 5 seconds, depending on the service mode).
d. Set the value to 1.
Decrease the value of the setting with the “A”-key, or increase it with the “B”-key.
e. Exit the SET-mode by briefly pressing the S-key (the indicator light turns off).
f. Exit the service mode, briefly press the program key.
7. Open a web browser in the computer connected to the Ethernet cable (step 5 on page
49) and enter 10.0.0.1 to the address field.
8. To login, enter:
Username: admin

Installation manual Planmeca Romexis 49


13 SETTING UP CLINIC MANAGEMENT

Password: PASS
Ethernet adapter web configuration page appears.
9. Select Network --> Configuration.
10. Enter dental unit’s IP address and netmask to the IP address field.
The IP address and netmask are entered to the IP address field in format:
10.0.0.1 255.255.255.0
11. Click Submit button.
12. Restart the dental unit.
13. Connect the PC to the dental unit equipped with new IP address to verify the
connection.
Make the connection as described earlier, but note that you must configure the PC to
the same subnet than you configured the dental unit.
14. If the connection works, connect the Ethernet cable from the cuspidor (Ethernet
adapter) to local area network (LAN).
Carry out the steps above for all Planmeca Compact i (v1) dental units to be added to the
Clinic Management.

Adding Planmeca Compact i Classic (v1) to Romexis software


Before starting, it is recommended to create a list of all Planmeca Compact i Classic (v1)
dental units to be added to the Clinic Management. The list should contain the name and
IP addresses of each dental unit.
1. Start Romexis Configuration, in Windows Start menu, click All Programs -->
Planmeca --> Romexis Configuration. To login, enter:
Username: sysadm
Password: promax
2. From the directory tree on the left side, under Clinic Management, click Dental Unit
Connections.
3. Click Add button.
4. Enter the needed information to the appearing window.
Note, that the name, IP address and Romexis server port must be unique.
• The dental unit IP must be same as entered when the Ethernet adapter was
configured in 13.3.6 "Planmeca Compact i Classic v1" on page 48, step 10.
• The Romexis server port can be any port that is not used.

5. Configure all Compact i Touch (v1) dental units in the same way.
6. From the directory tree on the left side, under Clinic Management, click Dental Unit
Connections.

50 Planmeca Romexis Installation manual


13 SETTING UP CLINIC MANAGEMENT

7. Under Romexis Server Settings, mark Enable Communication Service selection.

NOTE
Do NOT enable the Enable Log (Troubleshooting only) setting.

8. Restart the Romexis server to activate changes:


a. From the directory tree on the left side, under Start-up, click Romexis Server.
b. Click first Stop Service and then Start Service.

9. From the directory tree on the left side, under Server Parameters, click Server, and
under Unit Communication (PlanLink), mark Diagnostics Enabled selection.

10. Restart the Romexis server to activate changes:


a. From the directory tree on the left side, under Start-up, click Romexis Server.
b. Click first Stop Service and then Start Service.

After restart, the Planlink proxy process is started, which enables the communication
between Romexis and Planmeca Compact i Classic (v1) dental units.

13.3.7 Planmeca ProMax X-ray units

Physical LAN connection


It is assumed that the ProMax X-ray unit and reconstruction PC are installed and
connected to the Romexis PC, according to the instructions given in the ProMax X-ray
unit’s installation manual.

Configuring X-ray unit


1. Go to the ProMax X-ray unit and switch on the unit.

Installation manual Planmeca Romexis 51


13 SETTING UP CLINIC MANAGEMENT

2. In the control panel, touch the service spanner at the top left corner of the main view
to open the settings menu.

3. Select 1600 Clinic Management.

4. Set the following values to the appearing parameters:


• Romexis IP address
IP address of the Romexis server, as defined in the Romexis Configuration tool
(Server Parameters --> Server --> RMI Server Host setting).
• Romexis port number
Diagnostics server port, as defined in Romexis Configuration tool (Server
Parameters --> Server --> Diagnostics Port setting).
The default is 6812. Change the this setting only if you have changed the default
port 6812 to some other port in Romexis configuration (in step 4 on page 30).
• Device number
Enter an unique number for the X-ray unit.
• PlanLink Communication
Set the switch to ON position.
5. Save the changes, touch the green check mark button.
6. Reboot the X-ray unit.

52 Planmeca Romexis Installation manual


13 SETTING UP CLINIC MANAGEMENT

13.3.8 Planmeca PlanMill 40 units

Physical LAN connection


It is assumed that the PlanMill 40 milling unit and job server are installed according to the
Planmeca Chairside CAD/CAM solution, Installation manual (publication number
10036851).
The Romexis server should have network connection with the PlanMill 40 units, for
example as shown in the following figure.
Job server Romexis server

PlanMill 40

LAN

Router

NOTE
The Planmeca Chairside CAD/CAM solution uses a static IP addresses for all system
components. Check all IP addresses within the network to avoid conflicts in the network.

Configuring PlanMill 40 units


The PlanMill 40 milling unit and job server software versions must be 5.5.0.26 or newer. If
not, upgrade the softwares, refer to the Planmeca PlanMill 40, Upgrade instructions
(publication number 10037512).

Check the Planmeca service configuration settings in the PlanMill 40 job server and
modify if necessary, follow the steps below.
1. Set up a remote connection to the PlanMill 40 job server.
For more information on creating remote connection to the PlanMill 40 job server,
refer to the Planmeca PlanMill 40, Upgrade instructions (publication number
10037512).
2. Browse to folder:
C:\Program Files\E4D\Mill-Romexis Interface
3. Open the PlanmecaService.exe.config file.
4. In the file, check and edit if necessary, the Romexis server and job server network
settings in the following lines:
<add key=RomexisServerAddress" value="10.11.12.11"/>
Edit the value to contain the Romexis server IP address, as defined in the Romexis
Configuration tool (Server Parameters --> Server --> RMI Server Host setting).
<add key=RomexisServerPort" value="6812"/>
Edit the value to contain the Romexis server Diagnostics server port number, as
defined in Romexis Configuration tool (Server Parameters --> Server --> Diagnostics
Port setting).
<add value=DevicePublicAddress" value="10.11.12.12"/>

Installation manual Planmeca Romexis 53


13 SETTING UP CLINIC MANAGEMENT

Edit the value to contain the PlanMill 40 job server’s own IP address.
<add value=DevicePublicPort" value="6811"/>
Edit the value to contain the PlanMill 40 job server’s own port number.
5. Save the file.
6. Restart the PlanMill 40 job server, if any changes to the file were made.
7. Close the remote connection.

54 Planmeca Romexis Installation manual


13 SETTING UP CLINIC MANAGEMENT

13.4 Configuring clinic layout

13.4.1 Creating floorplan(s)


Follow the steps below to create floorplan(s). Carry out these steps in the Romexis server.
1. Create a PNG format graphic file from the floor plan of the Clinic Management
area(s).
For multi-floor, multi-clinic or other complex layouts you can create multiple floor
plans. Up to nine custom floor plans can be specified for the clinic view.
Each floor plan graphics must be in PNG format and approximately 1100 x 800 pixels
(maximum) in size. The files must be named floorplan1.png, ending in
floorplan9.png, depending on how many floors/areas are needed.
As an example, the figure below is the default floor plan file, included to the Romexis
installation package.

2. Save the floor plan file(s) under the Romexis installation path, in the folder
/Romexis/sconfig, replacing any previous floorplan*.png files.
3. To give names or rename floor plan(s), start Romexis Configuration, in Windows Start
menu, click All Programs --> Planmeca --> Romexis Configuration.
4. To login, enter:
Username: sysadm
Password: promax
5. From the directory tree on the left side, under Clinic Management, click Floor names.
6. Select the floorplanX from the list and click Update. and enter name for the floor plan
and click OK.
7. After naming the floor plans, click OK to save the changes and exit Romexis
Configuration tool.
8. Restart the Romexis server to activate changes:
a. In Windows Start menu, click All Programs --> Planmeca --> Start Romexis
Service.

Installation manual Planmeca Romexis 55


13 SETTING UP CLINIC MANAGEMENT

b. Click Stop Service.


c. Click Start Service.

d. Click OK.
e. Click Done.

13.4.2 Adding units to Clinic Management layout


Follow the steps below to add units to the Clinic Management layout. Carry out these
steps in the Romexis server.

NOTE
All units to be added to the Clinic Management, must be connected, configured and
switched on.

1. Start Romexis, in Windows Start menu, click All Programs --> Planmeca --> Romexis.
2. Click Clinic button.
3. Click Configure Layout button.
A list of operatories, chairside PCs, dental units, X-ray units, PlanMill 40 units etc. are
shown in the panel at the bottom of the Clinic monitoring tab view.
A PC or a dental unit becomes available in the list once it has connected to the server.
If a PC or a dental unit is not on the list, verify that a connection can be established
and that the dental unit has been connected to the Romexis server.
4. Select an operatory (you can choose between vertical or horizontal operatories).
5. Drag and drop it into the layout.
6. Enter the name of the operatory (the operatories can be named e.g. to match the
names of the actual operatories in the clinic) and click OK.
The operatory appears in the layout.
7. Add a corresponding unit pair into the layout by drag drop it to the layout.
8. In the same way add all other units to the layout.
9. Close the Romexis, click File -> Exit.
When next time starting the Romexis, all added units are visible in the clinic layout, in
Romexis server as well as in any Romexis client installation.

13.4.3 Updating dental unit quick reference card / maintenance and infection
control instructions
This section describes how to update dental unit quick reference card, maintenance and
infection control instructions and the dental unit control panel for the Romexis Clinic
Management module.

1. Insert the USB memory stick including the Planmeca dental unit software update to
the the Romexis server computer USB port.

56 Planmeca Romexis Installation manual


13 SETTING UP CLINIC MANAGEMENT

2. Open the USB drive folder.


3. Run the romexisGUI_update.bat script (located in the root folder of the USB
stick) as an admin user.
In the following, few tips on how to run the script as an admin user, depending on the
operating system, are given:
Windows 7:
a. Click Windows Start menu.
b. In the Search programs and files field type ‘command prompt’.
c. Right-click the Command prompt line and select Run as administrator.
d. The security question “Do you want to allow the following program to make
changes to this computer?” appears. Select Yes.
Windows XP/Vista:
a. From Windows Start menu select Run.
b. Type cmd in the Open field.
c. If you are prompted for an administrator password or confirmation, type the
password or provide confirmation.
4. Go to the USB-drive and find the correct drive letter in Windows Explorer.
5. To run the update script, change to the USB drive root folder.
If e.g. the USB stcik uses disk letter J, enter the following command:
C:\> J:
6. Check with dir -command that romexisGUI_update.bat exists in the USB-drive.
7. Enter the following command in the command prompt.
J:\> romexisGUI_update.bat
Wait until the script has copied all files to the Clinic Management module.
8. Exit the command prompt, enter the following command.
J:\> exit
9. Start Romexis, in Windows Start menu, click All Programs --> Planmeca --> Romexis.

Installation manual Planmeca Romexis 57


13 SETTING UP CLINIC MANAGEMENT

10. Click Clinic and check from the Unit Monitoring and Info tabs that the instructions and
Touch panel have been successfully updated. The unit type is selected from the drop-
down menu under the Info tab.

58 Planmeca Romexis Installation manual


13 SETTING UP CLINIC MANAGEMENT

13.5 Configuring Romexis clients

NOTE
Before configuring Clinic Management related tasks in the Romexis clients, the Romexis
client software must be installed to the client computers, see instructions in section 8.2
"Client installation" on page 18.

13.5.1 Configuring intraoral camera


After the dental unit with intraoral camera has connection to the Romexis server, it can be
configured in Romexis client, that is the Romexis client PC (chairside PC) connected to
the dental unit, see the figure below.
Carry out this configuration for dental units equipped with intraoral camera.

Romexis server

LAN

Intraoral USB cable

Display cable
Romexis client

1. Go to the dental unit and start the dental unit’s Romexis client PC.
2. Start Romexis, in Windows Start menu, click All Programs --> Planmeca --> Romexis.
3. Click Admin button.
4. Click Local Settings tab.
5. Enable Connect to dental unit at Startup setting under the Dental Unit Interface
(PlanLink) title and select the dental unit in question from drop-down menu.

6. To activate changes, restart Romexis client.

Installation manual Planmeca Romexis 59


13 SETTING UP CLINIC MANAGEMENT

13.5.2 Configuring Planmeca PlanScan scanner


After the dental unit with Planmeca PlanScan scanner has connection to the Romexis
server, it can be configured in Romexis client, that is the Romexis client PC (chairside PC)
connected to the dental unit, see the figure below.
Carry out this configuration for dental units equipped with Planmeca PlanScan scanner.

Romexis server

LAN

PlanScan FireWire Cable

Display cable
Romexis client

1. Go to the dental unit and start the dental unit’s Romexis client PC.
2. Start Romexis, in Windows Start menu, click All Programs --> Planmeca --> Romexis.
3. Click Admin button.
4. Click Local Settings tab.
5. Enable Connect to dental unit at Startup setting under the Dental Unit Interface
(PlanLink) title and select the dental unit in question from drop-down menu.

6. Check that Port Number under the PlanScan Control is not in any other use.
7. To activate changes, restart Romexis client.

60 Planmeca Romexis Installation manual


14 DIDAPI CONFIGIGURATION TOOL

14 DIDAPI CONFIGIGURATION TOOL


This section describes how to use the Planmeca DidapiConfig application for configuring
Planmeca ProMax, ProOne, Proline, ProSensor and Dixi X-ray systems.

NOTE
Please see the X-ray unit manuals for availability of specific features.

NOTE
All systems have separate technical manuals, which should be used in conjunction with this
one.

NOTE
Some settings are common to all devices whereas others are device specific. Thus the
contents of the tab images used may be different from the contents in the corresponding
tab of a specific device. In case the settings can be applied only to (a) specific device/s it
is indicated next to the title in question.

14.1 Starting Didapi Configuration tool


1. Click the Didapi icon on your desktop.
2. In the following window select the device you would like to configure.

Installation manual Planmeca Romexis 61


14 DIDAPI CONFIGIGURATION TOOL

14.2 Summary

System information
In the System information field the following information is displayed:
• Operating system
• Computer name
• User name
• Processor

Didapi

NOTE
All the following paths are requested from Didapi.dll. Thus the paths are the ones used by
Didapi.

In the Didapi field the following information is displayed:


• Didapi version
The current Didapi software version.
• Didapi.dll path
The path where the DidapiConfig and the exposure programs using the Didapi.dll
are stored.
In 64-bit Windows operating system the Didapi.dll file is in the format
Didapi_64.dll and in the 32-bit Windows operating system in format
Didapi.dll. For simplicity the format Didapi.dll is used when referring to both
systems.
Sometimes there might be several Didapi.dll files (backups or old/erroneous
installations. The currently used Didpi.dll file is shown in this folder.
• Ethernet configuration file path

62 Planmeca Romexis Installation manual


14 DIDAPI CONFIGIGURATION TOOL

The path where the IP settings are stored. This path can be configured in the Network
settings tab, see section 14.5 "Network settings" on page 68.
• Calibration file(s) path
The path where the sensor calibration files are stored. This path can be configured in
the Log tab, see section14.7 "Log" on page 71.
• Didapi log file path
The path where the Didapi log is stored. This path can be configured in the Log tab,
see section 14.7 "Log" on page 71.
• Didapi.ini path
The path where the Didapi.ini file is stored. This path cannot be configured.
• Images –folder path
The folder where the images to be reprocessed are stored for supported devices. This
path cannot be configured.

Open .ini file


Clicking the button opens the Didapi.ini file where most settings modified by
DidapiConfig software are stored.

Open images -folder


To open the folder where the raw images are stored click this button.

Delete calibration files (ProSensor only)


To delete calibration files click this button. The following warning appears.

To go through with delete click Delete, otherwise click Cancel.

Installation manual Planmeca Romexis 63


14 DIDAPI CONFIGIGURATION TOOL

14.3 Image processing

In the Image processing tab you can set the preprocessing settings for:
• Dimax 2/3/4 and Smartpan panoramic
• Bitewing
• TOMO and TMJ
• ProCeph (ProMax device selected)
and
• Cephalostatic images
The content of the Image processing tab depends on the currently selected device, see
step 2 on page 61.
The Planmeca ProMax, Proline and ProOne share the same settings, as only one device
can be configured at a time. However, only the settings relevant for the current device are
shown. Thus the number of tabs shown depends on the device that is been currently
configured.
The settings in the Planmeca ProMax, Proline and ProOne Image processing tab do not
affect the Planmeca ProSensor and Dixi 1/2/3 settings which are also independent on
each other.

NOTE
Some settings might exclude each other, e.g. you must use either Auto levels settings or
Logarithmic mapping.

To restore default settings click the Set defaults button.

Auto levels enabled


• White
Defines the percentage of cumulative shades of grey that is left out of the contrast
range from the upper end of the contrast range.
• Black
Defines the percentage of cumulative shades of grey that is left out of the contrast
range from the lower end of the contrast range.

64 Planmeca Romexis Installation manual


14 DIDAPI CONFIGIGURATION TOOL

• Midtones (gamma)
Adjusts the gamma curve of the image. Values below 1 will darken the image
whereas the values above 1 will brighten it. When set to 1 the value is not altered.

Logarithmic mapping
Logarithmic mapping can be used to add contrast in the image.
• SCurve
The SCurve processing is a step where the difference of raw data from image to
image is compensated. The SCurve defines a look up table to convert 16-bit data into
12-bit.
The raw data values are different depending on exposure values, patient thickness, x-
ray tube, CCD camera, filtering, aging, etc.
As the position of the curve is changed less radiation moves the curve leftwards and
higher dose moves the curve rightwards. The SCurve searches the histogram and
converts or compresses the data to 12-bit scale - into values between 0 and 4095.
Select the appropriate Scurve from the drop-down menu.

• SCurve quick guide button


To open the quickguide click this button.

• FMH (ProSensor and Dixi 1/2/3 only)

Installation manual Planmeca Romexis 65


14 DIDAPI CONFIGIGURATION TOOL

To select noise filter check the FMH option.

Auto exposure threshold values (ProSensor only)


Threshold values define how easily the sensor detects the start of an exposure. Normally
default values should always be used. If image is triggered without radiation, increasing
the threshold value could solve the problem. If exposure is missed or image integration
starts too late, lower threshold value might help.

Soft tissue filter enabled (ProCeph and Cephalostatic only)


Use this option to show more facial soft tissue.
The scale is from 1,5 to 10. Values above 1 will brighten the image.

DICE
Dental Image Contrast Enhancement (DICE) adjusts and optimizes the contrast of the
image automatically and brings out image details on the entire grey scale.
To set DICE on or off separately for different image modalities check the DICE check
boxes. With panoramic and cephalometric images DICE is selected by default.

Use AGC

NOTE
The AGC setting is shared between PAN, Bitewing, TOMO/TMJ and CEPH tabs.

The Automatic Gain Control (AGC) is supported by later Dimax2 and all Dimax3 sensors.
It is recommended to activate the AGC if the sensor supporting this option is used.
Automatic Gain Control (AGC) optimizes digital sensor sensitivity to produce excellent
image quality regardless of tissue and bone thickness.

66 Planmeca Romexis Installation manual


14 DIDAPI CONFIGIGURATION TOOL

14.4 Exposure settings (Dixi 1/2/3 only)

Exposure mode
In this field you can select the method the sensor uses to detect when an exposure is
taken.
• Auto exposure
The sensor automatically detects the start of radiation by itself.
• Sync. cable exposure (w/PCI or Ethernet interface)
The start of exposure is synchronized with the exposure switch.

Auto exposure threshold values


Threshold values define how easily the sensor detects the start of an exposure. Normally
default values should always be used. If image is triggered without radiation, increasing
the threshold value could solve the problem. If exposure is missed or image integration
starts too late, lower threshold value might help.

Synchronization settings
These settings are valid for Sync cable exposure mode.
• Exposure time
Maximum time for exposure. Sensor stays in image integration mode this long. Set
this value to maximum exposure time used on clinic. Setting too high exposure time
results in noisier images. Setting exposure time lower than used exposure time,
results blurred image.
• Preheat time
The x-ray tube preheat time The default value is usually good with Planmeca Intra.

Installation manual Planmeca Romexis 67


14 DIDAPI CONFIGIGURATION TOOL

14.5 Network settings

Ethernet settings
• ProMax with SmartPan
Select this option if you’re using SmartPan sensor.
• IP address and IP port
The IP address and the IP port for Planmeca Promax, ProOne and Proline need to be
set when starting to use the device.
Default IP addresses and IP ports:
ProMax: 10.0.0.1:5000
RecoPC: 10.0.0.3:5000
SmartPan: 10.0.0.3:5003
Proline: 192.168.0.135:5120
ProOne: 10.0.0.1: 5005
ProSensor: 172.26.150.150 (no port)
Dixi1/2/3: 192.168.0.135:5120
• Box port (Proline and Dixi1/2/3 only)
For Planmeca Proline and Dixi1/2/3 the box port also needs to be set.
The box port is 1/2 depending on the type of connection.

• Reco PC IP address and IP port


The IP Port for RecoPC and ProMax is always 5000 and 5003 for SmartPan.
• Ping IP
Once the IP address has been configured you can test the connection by clicking the
Ping IP button.
The result will be displayed at the bottom of the image.

• Activate IP

68 Planmeca Romexis Installation manual


14 DIDAPI CONFIGIGURATION TOOL

Only one Promax/ProOne/Proline Ethernet device can be activated at a time. The IP


addresses of the currently activated devices are shown at the bottom of the start
page.

There can be maximum two active addresses:


• one for PAN/CEPH (Planmeca ProMax, Proline and ProOne)
and
• one for INTRA (Planmeca ProSensor, Dixi1/2/3).
To activate the current IP address click Activate IP button.
Clicking the Activate IP button activates the current device and stores its IP address
and deactivates the IP address of the ProMax/Proline/ProOne or ProSensor/Dixi123
devices. The user will be prompted.
For example if ProMax has been selected the ProMax IP address will be activated
and stored whereas the Proline and ProOne IP addresses (if active) are disabled. The
Ethernet settings field and the Activate IP button are disabled.
When the IP address of the device is active the address fields are active and the IP
address can be set or changed. The Activate IP button is inactive (grey) and cannot
be used.
When the IP address of the device is not active the address fields cannot be set or
changed. The Activate IP button is active and can be used.

Planet connection settings (ProSensor only)


The Planmeca ProSensor Planet cable is an optional feature of Planmeca Intra X-ray unit
that is used for connecting the device to a computer, as in Planmeca ProSensor there is
no connection for Planmeca Intra. When the planet cable is connected Planmeca Intra
sends exposure parameters to the Romexis. The exposure parameters used with
Planmeca ProSensor are voltage (kV), current (mA), exposure time (s) and DAP
(mGy2cm2).
The Planet cable can also be used to open/lock Planmeca Intra in case the locking mode
has been enabled in the Romexis. In this mode exposures cannot be taken if the Romexis
is not in exposure mode or if for example the exposure request of a student has not been
approved.
• Planmeca Planet cable connected
To connect Planmeca Intra to computer with Planet cable check Planmeca Planet
cable connected and enter the correct port in the port field.

• Help
The Help button can be used to find the current COM ports are available follow the
instruction in the help window.
To open the Planet setup help window click the Help button.

Installation manual Planmeca Romexis 69


14 DIDAPI CONFIGIGURATION TOOL

Follow the instruction and click OK to exit.

The COM ports are shown as follows.

In Mac operating system clicking the Help button opens the path to the corresponding
device of the Mac OS file system.

System information
• Path to Ethernet configuration file

NOTE
This path is automatically set. It is recommended not to change the default destination
folder. It must only be changed for a specific reason.

The IP addresses set in this tab are saved to location defined in the Path to
configuration file field. This path is device specific.
• To activate the IP enter the IP address and the IP port in the respective fields and
click Activate IP.
• To open the configuration file click Open button.
• To select the directory where the configuration files are stored click the Browse...
button.
• To set the directory as default location click the Default location button.
• To change the path select the path for the configuration file and click Apply.

70 Planmeca Romexis Installation manual


14 DIDAPI CONFIGIGURATION TOOL

14.6 Misc. settings (ProMax only)

ProMax color GUI preview


• Midtones (gamma)
Adjusts the gamma curve of the image. Values below 1 will darken the image
whereas the values above 1 will brighten it. When set to 1 the value is not altered.

Space between slices with Dimax2/3 sensors


This feature is intended for adjusting the gray levels (Gray) and the space (Lines) between
slices when using imaging modes producing several slices and printing the images on film.
To restore default settings click Set defaults button.

14.7 Log

Log file

NOTE
The log is NOT device specific. The Log tab is the same than the Log accessed from the
start menu.

Installation manual Planmeca Romexis 71


14 DIDAPI CONFIGIGURATION TOOL

• Choose log level


The log level setting determines how much information will be written to the log file.
The recommended log level settings is Full/debug.
• Log file path

NOTE
It is recommended not to change the default destination folder. It must only be changed for
a specific reason.

• To open a log file click the Open Didapi.log button.

• To save a copy of the log file to a desired location click9 the Save copy as...
button.
• To select a new path for a log file click the Browse... button, select the new path
and click Select path.

• To restore the default log file path click Default location button.
• Workstation ID
Log File Workstation ID sets the name of the current workstation’s DIDAPI log file.
Default Location restores the default log file location.

Calibration

NOTE
It is recommended not to change the default destination folder. It must only be changed for
a specific reason.

72 Planmeca Romexis Installation manual


14 DIDAPI CONFIGIGURATION TOOL

• To define calibration file path click the Browse... button and select the desired
location.
• To restore default calibration file path click the Default location button.
• To browse for calibration files and copy calibration files to a specific location click
Install calibration files button. After selecting the files and clicking Install the selected
files will be copied to the location defined in the Calibration file path field.

NOTE
With some sensors or devices the calibration files are automatically loaded from the sensor
during exposure. With the sensors or devices that the calibration files are not automatically
loaded the files must be installed, e.g. from the CD delivered with the sensor.

Installation manual Planmeca Romexis 73


15 DICOM INTERFACE CONFIGURATION

15 DICOM INTERFACE CONFIGURATION


The DICOM interface can be configured in the Planmeca Romexis Admin module (see
Planmeca Romexis User’s manual, section DICOM Configuration).

16 X-RAY DEVICE ETHERNET CONFIGURATION IN


TERMINAL SERVER ENVIRONMENT
To configure a separate device for each Terminal Server client workstation follow the
instructions below.
X-ray device ethernet configurations are made in the ethernet configuration files, located
in the C:\Program Files\Planmeca\Didapi folder. The file names are:
• ProSensorEthernetConfig.txt
• PromaxEthernetConfig.txt
• ProOneEthernetConfig.txt

NOTE
In older installations didapi files are located in the Dimaxis folder
C:\ProgramFiles\Planmeca\Dimaxis\Program.

Edit the Ethernet configuration file of the respective X-ray device in order to map X-ray
devices to Terminal Server client workstations.
As a terminal server client workstation name one can use either COMPUTERNAME or
CLIENTNAME of the client workstation.
Computername and/or clientname can be seen in Windows command line: Windows Start
Menu --> Run.. --> Type in "cmd" --> In the command line, type in "set".
X-ray devices are mapped with their IP addresses.
E.g. a Terminal Server environment with three ProSensors (ip-addesses: 192.168.0.1,
192.168.0.2, 192.168.0.3) and three Terminal Server clients (clientnames: xpprosensor1,
xpprosensor2, xpprosensor3) would be mapped to each other the following way in the
ProSensorEthernetConfig.txt file.
xpprosensor1=192.168.0.1
xpprosensor2=192.168.0.2
xpprosensor3=192.168.0.3

NOTE
Each terminal server client must have access to the Didapi folder and a working network
connection to the X-ray devices.

74 Planmeca Romexis Installation manual


17 SETTING UP MS SQL SERVER 2012 EXPRESS BACKUP

17 SETTING UP MS SQL SERVER 2012 EXPRESS


BACKUP

17.1 Introduction
This section describes how to set up backups for Planmeca Romexis MS SQL Express by
means of a scheduled execution of a Stored Procedure using a batch file and Windows
Scheduled Tasks service. For backups on other database engines refer to their respective
documentation.

17.2 Configuration
When the Romexis installer deploys MS SQL Server onto the server computer, it also
creates a Stored Procedure in the Romexis instance that provides a facility to make
backups from the Romexis database, and transaction logs. To call the Stored Procedure a
set of two SQL scripts and a batch file is provided on the Romexis installation CD in the
\Tools\backup\ folder.
1. Copy the contents of the folder to an appropriate location such as:
C:\Program Files\Planmeca\Romexis\backup\
2. Modify the following file as instructed in the inline comments:
romexis_db_backup.sql (to configure database backup settings)
The following settings are provided in the file and should be adjusted to fit the local
backup needs. “1” denotes true while “0” denotes false:
• @backupfldr = ’c:\romexis_images’
Folder to write backup to, a subfolder 'romexis_db' is automatically created and
used. This must be changed to point to a safe location that is available for tape
backup.
• @reportfldr = 'c:\romexis_cache’
As above but defines location for writing reports of the backup process.
• @checkattrib = 1
Defines if new backups should have their archive bit set. The Stored Procedure
will automatically delete backups older than defined by dbretainunit UNLESS the
files have their archive bit set to true. If this is left at “1”, the old backups should
have their archive bit set to false when they are backed up to another media to
prevent the file system from being filled with backups.
• @dbretainunit = 'months'
Defines the period for which the backups should be preserved before automatic
deletion. Can be: minutes | hours | days | weeks | months | copies.
• @dbretainval = 2
Specifies how many dbretain units to keep old backups.
• @rptretainunit = 'copies'
Defines the period for which to retain reports for. Can be: minutes | hours | days |
weeks | months | copies.
• @rptretainval = 30
Specifies how many rptretainunits to keep reports.
• @report = 1
Flag to indicate whether to generate reports or not.

Installation manual Planmeca Romexis 75


17 SETTING UP MS SQL SERVER 2012 EXPRESS BACKUP

17.3 Setting up scheduled backup

NOTE
Remember to test the backup functionality after creating the task.

Use the Windows Scheduled Tasks service to setup a daily backup event as follows.
1. Open Control Panel.
2. Open Scheduled Tasks.
3. Double-click Add Scheduled Task to create a new task or on Windows 7 click Create
Basic Task..

4. Proceed with the Scheduled Task Wizard and choose Browse to select the program.
Browse to run_romexis_backups.bat that you have copied to an appropriate
location. (e.g. C:\Program Files\Planmeca\Romexis\backup\).
On Windows 7 additionally add the path to the backup script folder to the field Start in
(optional).

76 Planmeca Romexis Installation manual


17 SETTING UP MS SQL SERVER 2012 EXPRESS BACKUP

5. On Windows 7 after creation of the task, go to Task properties and check the Run with
highest privileges option.

6. Select the appropriate operating system in the Configure for drop-down menu.
7. From the Perform this task options select Daily.

8. Specify a convenient Start time to run the backups, such as after midnight when there
is no other activity.
9. Click Next and specify a user and password to run the backups under.
This is preferably a local backup account that has limited permissions. It should also
be a persistent account since if the account is removed the backups will stop working.
10. Check the configuration and click Finish.
11. Double-click on the Task you just created to double check the configuration.

Installation manual Planmeca Romexis 77


17 SETTING UP MS SQL SERVER 2012 EXPRESS BACKUP

12. Right-click on the Task and choose Run to test the functionality of your setup.
Example screens are presented below

78 Planmeca Romexis Installation manual


18 INSTALLING PLANMECA ROMEXIS IMPLANT LIBRARY

18 INSTALLING PLANMECA ROMEXIS IMPLANT


LIBRARY

18.1 Introduction
This section describes the installation of Planmeca Romexis Implant Library software
version 3.

18.2 Software requirements


• Planmeca Romexis server version 3.1 or newer.
• MS SQL server database
• ~ 4 GB of free space.

NOTE
If you’re using Oracle or Solid server database see chapter 18.5 "Manual installation" on
page 82.

18.3 List of implants to be installed


The Planmeca Romexis Implant Library CD currently contains implant data from the
following manufacturers.

Anthogyr Astra Bego Bicon Biomet


Biotech Biomet 3i Bredent Camlog Clinical House
Biotechnologies Europe

Dentaurum Euroteknika Friadent GC: Leone


Medical Production MiS Neoss Nobel Biocare NucleOSS
Platon Serf Straumann Sweden-Martina TBR
Tekka TFI Thommen Zimmer

NOTE
Planmeca Romexis Implant Library installer Read Me file contains the most updated list of
the implant manufacturers.

18.4 Installation procedure


1. Insert the Planmeca Romexis Implant Library CD into the disk drive.

Installation manual Planmeca Romexis 79


18 INSTALLING PLANMECA ROMEXIS IMPLANT LIBRARY

2. The following window opens. Click Next.

3. In the License Agreement window select I accept the terms of the license agreement
and click Next.

80 Planmeca Romexis Installation manual


18 INSTALLING PLANMECA ROMEXIS IMPLANT LIBRARY

4. Select Romexis Implant Library by checking the box and click Next.

5. In the opening window, select Planmeca Romexis installation folder as the destination
folder by clicking Browse.
The default folder is C:\Program Files\Planmeca\Romexis.

Installation manual Planmeca Romexis 81


18 INSTALLING PLANMECA ROMEXIS IMPLANT LIBRARY

6. Make sure you have selected ROMEXIS Database Server. Click Next.

7. After the installation, verify that the realistic implants can be seen in the Romexis
software. To check the list of implants open the Planmeca Romexis 3D Module and
click on the Implant tab, then select Implant Library.

18.5 Manual installation


1. Browse to the folder \setup on the Planmeca Romexis Implant Library installation
CD.
2. Copy the folder \geometries with all its subfolders to the folder where Planmeca
Romexis server is installed. The default path is C:\Program
Files\Planmcea\Romexis\geometries.
3. Run the batch file all_implants.bat from the folder that corresponds to the
installed Planmeca Romexis database server type.

NOTE
If you are using Planmeca Romexis Database that was originally installed with the old
password (pwromex1s) use the all_implants_old_password.bat.

setup\sql\sql.sqlsrv (MS SQL Server)


setup\sql\sql.ora (Oracle)
setup\sql\sql.solid (Solid)
4. After the installation, verify that the realistic implants can be seen in Planmeca
Romexis software. To check the list of implants open the Planmeca Romexis 3D
Module and click on the Implant tab, then select Implant Library.

82 Planmeca Romexis Installation manual


19 CONFIGURING PLANMECA ROMEXIS MANUAL FOR PLANMECA ROMEXIS CLIENT

19 CONFIGURING PLANMECA ROMEXIS MANUAL


FOR PLANMECA ROMEXIS CLIENT
Planmeca Romexis User’s manual can be configured to be used with the Romexis.
The Romexis installer detects Adobe Acrobat and Adobe Reader installations and
configures the Romexis to open the Romexis User’s manual (PFD format) with the
respected software.
To configure the PFD reader manually after the installation of the Romexis, edit the file /
Planmeca/Romexis/sconfig/manual_config.xml_EDIT as follows:
1. Change the name of the file to manual_config.xml.
2. Make sure the key application default-path contains the path to the
executable file of Adobe Acrobat or Adobe Reader.
3. Make sure that the line:
<locale language="en" doc-file="Romexis_um.pdf"/>
of the language in use contains the name of the user’s manual to be used with the
respected language, and that is found in the /manuals folder of the Romexis folder
structure.

Installation manual Planmeca Romexis 83


20 TROUBLESHOOTING

20 TROUBLESHOOTING

20.1 Romexis server service

Romexis server service does not start


Check that JVM path is correctly set in /server/RomexisService.ini JVM_Path.
Start Romexis Service Control with Administrator privileges by right-clicking on the file and
selecting Run as administrator
If Romexis server service does not start check that the parameter JVM Path of the file
RomexisService.ini in the folder server is the following:
In 32-bit OS:
JVM_Path= C:\Program
Files\Planmeca\Romexis\tools\jre_x86\bin\client\jvm.dll\
In 64-bit OS:
JVM_Path= C:\Program
Files\Planmeca\Romexis\tools\jre_x64\bin\server\jvm.dl

20.2 DidapiConfig

DidapiConfig does not start


The DidapiConfig.exe cannot find the Didapi.dll file
or
The correct JRE (Java Runtime Environment) is missing

Check the following


• The Didapi.dll file is stored under \Program Files\Planmeca\Didapi\.
• The Didapi.dll version is 5.0.0.R or later
• The JRE Java SE version is 6 (or 1.6) or later
• System level Environment variable ”PATH” contains the path to the folder where
Didapi.dll file is stored. Check that this environment variable exists and
Didapi.dll path:
C:\Program Files\Planmeca\Didapi is set there.

84 Planmeca Romexis Installation manual


20 TROUBLESHOOTING

Didapi.ini file is missing or reading/writing is not permitted

Check the following


• The Didapi.ini file can be found in the folder
”ProgramData\Planmeca\Didapi\Config\” (WinXP: Application
Data\Planmeca\Didapi\Config\).
• Reading/writing is permitted.

Didapi.log file is missing or you do not have access rights

Check the following


• Didapi.log can be found in the Didapi.ini that has been correctly set. The
default path is ProgramData\Planmeca\Logs Didapi.ini [LOGFILE]:
LogFilePath=
• Check that the WorkstationID makes sense. Try to remove if set. It is empty by
default. Didapi.ini [LOGFILE]: WorkstationID=

Images –folder access rights


The folder where the Images folder is created is missing or reading/editing is not
permitted.

Check the following


• The folder ProgramData\Planmeca exist and reading/editing reading/editing is
permitted.
• Reading/editing rights admitted to the folder ProgramData\Planmeca\Images.

Installation manual Planmeca Romexis 85


20 TROUBLESHOOTING

User Temp folder access rights


The users Temp folder cannot be found or no rights are admitted. This is an operation
system related problem.

• Check the user rights from your system administrator.


• Check from the operation system settings why the Temp folder cannot be found.

86 Planmeca Romexis Installation manual


Appendix A: PMBRIDGE
CONFIGURATION

To support other software companies and their developers to integrate their software,
Planmeca has created interface standards and libraries.
Pmbridge interface provides a simple way of data transfer between Planmeca Romexis
and practice management software of another company. Pmbridge functions as a "bridge"
and passes necessary patient information to Planmeca Romexis imaging software and
images from Planmeca Romexis to the third party software.
For integrators who do not need image transition from Planmeca Romexis to practice
management software a lighter solution called DxStart is also available .

A.1 Windows Registry additions


The following path is added as following Windows registry entities' values:
C:\Program Files\Planmeca\Romexis\pmbridge
32-bit and 64-bit Windows:
HKEY_LOCAL_MACHINE\SOFTWARE\Microsoft\Windows\CurrentVersion\AppPa
ths\Dimaxis.exe (Value Name: Path)
32-bit and 64-bit Windows:
HKEY_LOCAL_MACHINE\SOFTWARE\Planmeca\Romexis (Value Name: pmbridge)
64-bit Windows:
HKEY_LOCAL_MACHINE\SOFTWARE\Wow6432Node\Microsoft\Windows\CurrentV
ersion\App Paths\Dimaxis.exe (Value Name: Path)
64-bit Windows:

Installation manual Planmeca Romexis 87


A.2 Windows Environment Variable additions Appendix A: PMBRIDGE CONFIGURATION

HKEY_LOCAL_MACHINE\SOFTWARE\Wow6432Node\Planmeca\Romexis (Value
Name: pmbridge)

NOTE
According to Pmbridge SDK instructions, practice management software has to add the
folder 'Program' to the path obtained from registry. That is why the complete path is not
found from the registry.

NOTE
Pmbridge installation updates the Dimaxis.exe registry key to point to Romexis pmbridge
folder. This disables Pmbridge use with Dimaxis. If pmbridge is still desired to be used with
Dimaxis, the respective registry key should be changed to point to Dimaxis pmbridge folder.

A.2 Windows Environment Variable additions


The following path is added to Windows Environment variable Path:
C:\Program Files\Planmeca\Romexis\pmbridge\Program

A.3 Users
Pmbridge user group permissions can be altered to pmbridge user needs in Planmeca
Romexis Admin Module. For more information see Planmeca Romexis User’s manual.¨
The Romexis installer creates a user group Pmbridge Users and a user Pmbridge to
Planmeca Romexis database. When starting Planmeca Romexis via pmbridge, the
respected user is automatically selected (Romexis.bat file's parameters uid (user id)
and pwd (password) found from the pmbridge installation folder).

88 Planmeca Romexis Installation manual


Appendix A: PMBRIDGE CONFIGURATION A.4 Enabling PMBridge connection in Romexis

A.4 Enabling PMBridge connection in Romexis


1. Start Romexis and click Admin button.
2. Click Admin buttonthe tab Local Settings tab.
3. Check that PMBRIDGE Enabled is enabled in section Practice Management Software
Interface (PMBRIDGE). The port number is 1501.

A.5 Manual setup of the path


If launching of the Romexis via PMBridge is not working use manual setup.
The existence of the path to the Planmeca Romexis’s Pmbridge.dll directory needs to
be verified. For historical reasons, the path is saved in Dimaxis registry key. To obtain the
path, open the Windows registry:
1. Open the Windows Start Menu and click Run.

2. In the Run window, enter the command regedit to open the Registry Editor. (In
Vista the command regedit needs to be entered in the Start Search box)

3. Verify the following Key in the registry:


HKEY_LOCAL_MACHINE\SOFTWARE\Microsoft\Windows\CurrentVersion\A
pp Paths\Dimaxis.exe

Installation manual Planmeca Romexis 89


A.5 Manual setup of the path Appendix A: PMBRIDGE CONFIGURATION

64-bit Windows:
HKEY_LOCAL_MACHINE\SOFTWARE\Wow6432Node\Microsoft\Windows\Curr
entVersion\App Paths\Dimaxis.exe (Value Name: Path)

If this key does not exist, it needs to be created.

Creating the key


1. Open the key:
C:\Program Files\Planmeca\Romexis\pmbridge
2. Right-click the App Paths key and select New and Key. Name the created key as
Dimaxis.exe.

3. Right-click the Dimaxis.exe key and select New and String Value. Name the created
string value as Path.

90 Planmeca Romexis Installation manual


Appendix A: PMBRIDGE CONFIGURATION A.5 Manual setup of the path

4. To modify the created path double-click on the Path and enter the Value data e.g.:
C:\Program Files\Planmeca\Romexis\Pmbridge

The Path of the Dimaxis.exe defines the location of the PmBridge files.
5. After having verified or created the Dimaxis.exe key, verify that the pmbridge files
exist in the following folder C: \Program
Files\Planmeca\Romexis\pmbridge\Program.You will find the files on your
Planmeca Romexis Installation CD (..\Tools\pmbridge).

6. Edit the copied Romexis.bat file if necessary.


7. To edit the file right-click on the file name and select Edit with the left mouse button.
A window with the Romexis directory text opens:
cd C:\Program Files\Planmeca\Romexis\client

If the text after @ start does not conform to the directory of the freshly installed
Planmeca Romexis version the directory text needs to be changed.
8. Save the changes and close the window.
9. Change the xmx memory reservation to conform to the Romexis client configuration
recommendations.
10. Start Romexis and click Admin button.
11. Select the Local Settings tab and check that PMBRIDGE Enabled is enabled in the
section of Practice Management Software Interface (PMBRIDGE). The port number is
1501.
12. Continue to set up the PmBridge connection in the Practice Management Software.
Refer to the appropriate manual to proceed.

Set up of VDDS
VDDS Bridge interface is the integration for most German practice management software.
VDDS can be installed from the Planmeca Romexis installation CD's \tools\VDDS
folder.
Pmbridge must be installed when installing VDDS.

Installation manual Planmeca Romexis 91


Appendix B: INSTALLING PLANMECA
ROMEXIS ON TURKISH WINDOWS

NOTE
These instructions are meant for Romexis installation with MS SQL Server 2005 Express.

1. Insert the Planmeca Romexis installation DVD into the drive and start Romexis
installation.
2. In the opening window select Custom installation.
3. Select all necessary components and deselect Romexis Database component. Click
Next.

4. Go through the installation as instructed in the installation manual.


5. After the installation is completed, navigate to installation DVD's folder
\MSSQL\romexis_db\ and start Romexis Database installer by double-clicking the
file Setup.exe.
6. In the opening window select Other Scripts, check Create Database File and click
Next.
7. In the Database Server dialog, make sure to select the following default options:
Database server: (local)\ROMEXIS

92 Planmeca Romexis Installation manual


Appendix B: INSTALLING PLANMECA ROMEXIS ON TURKISH WINDOWS A.5 Manual setup of the path

Connect using: Windows authentication

8. Click Next.
9. After the database installation go to the installation DVD's folder
\MSSQL\romexis_db\db_files.
10. Double-click on the stop_romexis_service.bat file to stop Romexis MS SQL
instance.
11. Navigate to installation DVD's \MSSQL\romexis_db\db_files\ folder.
12. Copy the Romexis database files Romexis_db.MDF and Romexis_db.LDF to the
folder C:\Program Files (x86)\MS SQL Server\MSSQL.1\MSSQL\Data\.
13. Overwrite the existing files.
14. To start Planmeca Romexis MS SQL Server instance go to the installation DVD's
folder \MSSQL\romexis_db\db_files.
15. Double-click on the start_romexis_service.bat file.
16. After the service is running again, navigate to installation DVD's folder
\MSSQL\romexis_db\.
17. Start Romexis Database installer by double-clicking the file Setup.exe.
18. Select Other Scripts, check the option Create Database Users, and click Next.
19. Copy the folder romexis_images with all its sub folders from the installation DVD's
folder \MSSQL\romexis_db\db_files\ to the local system root
C:\romexis_images.
20. Copy the romexis_server.properties file from the folder
\MSSQL\romexis_db\db_files\ to the Romexis installation folder C:\Program
Files\Planmeca\Romexis\sconfig.
21. Install Romexis license.
22. Restart Romexis service.
23. Start Romexis client.

Installation manual Planmeca Romexis 93


Appendix C: TRANSFERRING /
MERGING DATABASES

This tool is used to transfer the database from one location to another for example in case
the client wants to change from one operating system to another or merge two different
databases together.

NOTE
Refer to Romexis installation manual for MacOS when transferring database from / to a
Planmeca Romexis software on MacOS.

NOTE
The source and destination databases need to be updated to the same Planmeca Romexis
software version.

NOTE
It is highly recommended to backup the original database(s) before using the Database
tool.

NOTE
If the Implant Library has been installed to either of the databases (source or target) install
the newest Implant Library to the target database after merging the source database into
an existing database.

C.1 Exporting files from one database to another


NOTE
Before starting shut down Planmeca Romexis server, it is recommended to shut down other
processes and executable files not needed to ensure the database tool has sufficient
amount of free memory.

1. Go to the Planmeca Romexis installation DVD /tools/database_tool/ folder.


2. Start Romexis Service for Database tool by launching the following script:
start_romexis_server_for_database_tool.bat
3. To launch the Database tool, launch the following script:
Export_Romexis_database.bat
The Database tool starts.
4. Choose the folder where to export the database files by clicking the Browse button.

94 Planmeca Romexis Installation manual


Appendix C: TRANSFERRING / MERGING DATABASESC.2 Importing database from one location to the oth-

5. Start export by clicking Export files button.

This may take a few minutes. When export is completed the following message
appears: Tables were serialised to file X.
6. Close the Database Tool.
7. Copy the output folder containing the *.serial files to the media that will be used to
move the database to another system (if the folder is not there already).
8. Copy the Romexis image file folders into the same folder with the *.serial files:
c:\romexis_cache
c:\romexis_ergodata
c:\romexis_images

NOTE
The database transfer tool renames imported duplicate usernames and device names.

NOTE
A statistics window is shown at the end of a merge/import and an export. This page shows
the amount of exported or imported lines in each table. Also renamed duplicate user names
and duplicate device names are listed.

C.2 Importing database from one location to the other


Make a new Planmeca Romexis installation under the same version that was in use when
exporting the data.
Attach the media to the target system.

NOTE
Before starting make sure Romexis server is NOT running.

If merging two databases together start from step 3 on page 96.

Installation manual Planmeca Romexis 95


C.2 Importing database from one location to the otherAppendix C: TRANSFERRING / MERGING DATABAS-

Moving an old database to a new computer with empty database

NOTE
Do not run the script if merging two databases together! The script will empty the target
database.

1. Go to the Planmeca Romexis installation DVD /tools/database_tool/ folder.


2. Remove all lines from each table in the target database and reset the tables’ indexing
to zero by running the following script:
\Clear_Romexis_database.bat

NOTE
This script can be run only once. If it is ran twice the database indexes get corrupted and
have to be re-installed.

3. Start Romexis server for Database tool by launching the following script:
start_romexis_server_for_database_tool.bat
4. Import Romexis database by launching the following script:
Import_Romexis_database.bat
5. Choose the location of serialized (*.serial) files by clicking the Browse button.
6. Start the import by clicking the Import files button.

This may take a few minutes. When serialization is completed the following message
appears:
Files were de-serialized to database
Patient merging is done using external ID of the patient. Also inactivated patient
images will be taken into account.
7. Open Romexis client and verify that the database has been successfully moved to the
new computer.

Merging source database into an existing database


Go through the steps from step 3 to step 7 on page 96.
If the implant library has been installed to either of the databases (source or target) install
the newest Implant Library to the target database after merging the source database into
an existing database.

96 Planmeca Romexis Installation manual


Appendix D: ROMEXIS SILENT
INSTALLATION

Identical Romexis installations can be performed to several workstations using the silent
installation option. Carry out the following steps for Romexis silent installation.

1. Start windows command prompt with administrator privileges.


2. To record your installation, run Romexis setup executable from installation media with
the following command (enter the whole command to the same line):
E:\Romexis\setup.exe /r
/f1"<PATH_TO_RECORD_FILE>\romexis_installation.iss"

Replace <PATH_TO_RECORD> with a file path name you wish to save the result
record file.
If f1 parameter is not set, the record file will be saved by default to folder and with
filename:
C:\Windows\setup.iss
3. Perform the Romexis installation following the installation dialogs normally.
Follow the installation instructions given earlier in this manual.
4. After successful installation, copy the romexis_installation.iss record file to
another workstation or a portable drive.
5. To perform the installation with the exact same configurations on another workstation,
enter the following command via command prompt with administrator privileges (enter
the whole command to the same line):
E:\Romexis\setup.exe /s /SMS
/f1"<PATH_TO_RECORD_FILE>romexis_installation.iss"
Replace the <PATH_TO_RECORD_FILE> with the path you saved the record file.
The installation starts silently. You can monitor when the installation is finished with
Windows Task Manager. If any InstallShield processes are running, the installation is
still running.

NOTE
Make sure that all the workstations you are installing the Romexis meet the requirements
set in the beginning of this manual (e.g. required .NET frameworks etc.).

NOTE
Additional dialogs may appear if the previous Romexis installations in the workstation
differs from the workstation the recording was made. Dialogs may also appear if device
drivers, e.g. for ProSensor or ProScanner are included in to the installation.

Installation manual Planmeca Romexis 97


Appendix E: UNINSTALLING
PLANMECA ROMEXIS

The uninstall of Planmeca Romexis removes Planmeca Romexis server and client
applications and related shortcuts, registry entries and folders. External components that
are installed during the Romexis installation, such as JRE, MS SQL Server etc., are not
removed. Planmeca Romexis Database and image files are also left untouched.

NOTE
It is recommended that the Planmeca Romexis is uninstalled only in case Planmeca
Romexis is no longer used on the respective computer.

The uninstall can be started from Windows Control Panel --> Add/Remove Programs, by
selecting Planmeca Romexis from the Currently Installed Programs list, and clicking
Remove.

Another option is to start Planmeca Romexis Installer from the Installation CD and select
the option Remove from the main selection dialog.

Confirm removal by clicking Yes.

98 Planmeca Romexis Installation manual


Appendix F: PLANMECA ROMEXIS
LANGUAGE ABBREVIATIONS

Simplified Chinese: cn
Czech: cs
Danish: da
German: de
English: en
Greek: el
Spanish: es
Estonian: et
Finnish: fi
French: fr
Hungarian: hu
Japanese: jp
Korean: ko
Lithuanian: lt
Dutch: nl
Norwegian: no
Polish: pl
Portuguese: pt
Romanian: ro
Russian: ru
Slovak: sk
Serbian: sr
Swedish: sv
Traditional Chinese: zh
Turkish: tr
Ukranian: uk

Installation manual Planmeca Romexis 99


Planmeca Oy | Asentajankatu 6 | 00880 Helsinki | Finland
tel. +358 20 7795 500 | fax +358 20 7795 555 | sales@planmeca.com | www.planmeca.com

Das könnte Ihnen auch gefallen