ABB. Betriebsanleitung Operating Instructions. VERITRON - Doppelstromrichter Regenerative Controllers Typen AAD 6101 A 8001 A 6151 A 8051 A.
ABB. Betriebsanleitung Operating Instructions. VERITRON - Doppelstromrichter Regenerative Controllers Typen AAD 6101 A 8001 A 6151 A 8051 A.
Druckschrift Nr.
Publication No.
D EA 1552 84 b D, E
®
Diese Betriebsanleitung gilt für VERITRON -Stromrichter These operating instructions apply to Type AAD 6..1 8..1 A
®
Ader Typenreihe AAD 6..1 A - 8..1 A, die zur Drehzahlre- VERITRON Regenerative Controllers for armature supply of
gelung von Gleichstrommotoren eingesetzt werden. DC motors.
Schützen Sie das Gerät vor unzulässiger Beanspru chung. Avoid inadmissible overloading of the controller. Be careful
Fassen Sie das Gerät nur so an, daß Sie keine Bauele - not to bend any components. Do not alter the insulating
mente verbiegen und/oder Isolationsabstände ver ändern. distances. Avoid touching the electronic components,
conductor
Vermeiden Sie das Berühren elektronischer Bauele -
mente, Leiterbahnen und Kontakte. Beachten Sie ent - Follow the indicated sequence of operations during start up.
sprechende Hinweisschilder. For signal voltage measurements a moving -coil instrument
with a min. internal resistance of 10 kW/V is to be used.
Bei der Inbetriebnahme sollte die angegebene Arbeitsrei -
henfolge eingehalten werden. Für die Messungen der When working on live units, adhere to the applicable
Signalspannungen ist ein Drehspuleninstrument zu verwend- safety instructions (er g. VBG 4).
en, dessen Innenwiderstand mindestens 10 k W/V
beträgt.
ABB Drives
ABB
ASEA BROWN BOVERI
Inhaltsverzeichnis
Seite
1. Vorbereitende Arbeiten 3
1.2 Kontrollen und Einstellmaßnahmen bei spannungsfreier Anlage, z.B. Netzsicherungen entfernt 3
1.3. Drehzahl-Istwert-Anpassung 5
1.5. Feldversorgung 6
2.3. Strombegrenzung 8
2.4. Zeitverhalten 8
2.5. Stromregler 8
2.6. Drehzahlregler
12
3. Störungsursachen 17
3.4. Motor beschleunigt schon bei kleiner Sollwertvorgabe auf max. Drehzahl 18
3.5. Drehzahl pendelt nach Last- oder Sollwertänderung oder Motor läuft ruckweise 18
5. Klemmenbelegung 22
6. Bestückung 24
Remark:
English version see page 26
Reglerplatte AF 6002 Hinweis: Bestückungsänderungen können in der Tabelle auf dem Beilageblatt eingetragen werden.
Note: Changes of R-C elements can be entered in the table on the separate sheet.
Anordnung der Potentiometer und Leuchtdioden
1. Vorbereitende Arbeiten
□ Schraubverbindungen.
□ Anker-und Feldanschlüsse.
□ Falls eine Hilfsreihenschlußwicklung (D1 - D2) vorhanden ist, ist diese nicht anzuschließen.
1.2. Kontrollen und Einstellmaßnahmen bei spannungsfeier Anlage, z.B. Netzsicherungen entfernt
□ AAD-Gerät auf evtl. Beschädigungen durch Transport oder Montage überprüfen. Richtigen und festen Anschluß der Haupt- und Steuerleitungen
überprüfen.
□ Zusatzeinrichtungen (s.a. mitgelieferte Unterlagen). Zunächst Gerät ohne Zusatzeinrichtungen in Betrieb nehmen (außer bei Feldschwächgerät
GLB). Zusatzeinrichtungen montieren. Inbetriebnahme der Zusatzeinrichtungen.
□ Netzeinspeisung und Absicherung der Anlage kontrollieren; max. Strom berücksichtigen. Schutzmaßnahme überprüfen (Geräteerdung).
□ Anschlußspannung
Der fett gedruckte Wert ist der übliche Auslieferungszustand bei ABB, Einstellung siehe auch Baugruppe AM 60 . . „Netzteil“.
□ Drahtbrücke, R57/AF 6002 (Bereich I-Regler) entsprechend Angaben in untenstehender Tabelle umlöten (EMK-Anpassung)
□ Befestigungsschrauben lösen und Steuerteil herausklappen. Auf Trafobaugruppe AM 60.. Brücken (oben am Rand) umlöten:
(AM 6003) 415 V ~ 105 nicht eingebaut 1-4 vom Anwender ändern
Steuerteil
(AM 6052) 500 V ~ 103 nicht eingebaut 1-6 Auslieferungszustand bei ABB
Getrennte Versorgung von Leistungsteil und Steuerteil
Hierbei ist es möglich, zunächst den Steuerteil einzuschalten und erst nach Betrieb der Hilfsbetriebe und bestimmter Anlageneinrichtungen
den Leistungsteil einzuschalten. Bei einer Störung braucht nur der Leistungsteil abgeschaltet werden, die Störungsmeldung auf dem Steuerteil
bleibt erhalten.
UV = Versorgungsspannung
Leistungsteil
UV
V/3~ 105 – 117 114 – 126 123 – 136 134 – 148 146 – 162 156 – 173 167 – 185 177 – 195 192 – 212
R57
kW 10 22 // 22 12 27 // 27 15 33 // 33 18 39 // 39 22
UV
V/3~ 201 – 222 219 – 243 239 – 265 249 – 275 274 – 302 301 – 333 328 – 362 356 – 394
R57
kW 47 // 47 27 56 // 68 33 39 47 56 68
□ Frequenz
Die Geräte können mit einer Netzfrequenz von 50 Hz . . . 60 Hz (± 5 %) ohne Umstellmaßnahmen betrieben werden.
□ Sollwert
Sollwertanpassung
Bild 1./3 Widerstand R102 in Abhängigkeit vom Bild 1./4 Widerstand R229 in Abhängigkeit vom Sollwert
Sollwert (< 10V ) (> 10V … 12 V)
Externe Sollwertvorgabe
□ Sollwertleitungen von einer übergeordneten Steuereinrichtung (z.B. NC) an X 1:5, X1:15 abklemmen. Für die Inbetriebnahme kann die interne
Sollwertspannungsquelle benutzt werden; hierzu Anschluß wie in Bild 2.1 angegeben (S. 7) herstellen.
Die Istwertspannung (Tachospannung) ist von der Motordrezahl und dem Tachokennwert (Spannung UT bei 1000 min -1)
abhängig:
□ Anpassung
Der genaue Drehzahl-Abgleich wird bei laufender Maschine am Potentiometer R3/AF 6002 vorgenommen; Prüfung der tatsachlichen Drehzahl mit
einem Drehzahlmesser an der Motorwelle.
Wird der Eingang Klemme X1:13 nicht angesteuert, so werden unabhängig von dem an X1:5 anstehenden Sollwert die Regler gesperrt. Bei einem
Startbefehl (X1:13 mit +24V, z.B. X1:10 verbinden) läuft der Antrieb unverzögert an. Bei Wegnahme des Startbefehls (Halt) wird der Sollwert auf
Null geschaltet und nach Ablauf einer einstellbaren Verzögerungszeit (Bremszeit tV) werden die Regler gesperrt und die Zündimpulse in die
Wechselrichtergrenzlage geschoben.
Wird die Funktion nicht benötigt, sind die Klemmen X1:10 - 13 zu brücken.
1.5. Impulsverschiebung in die Wechselrichtergrenzlage mit Reglersperre (im folgenden als Kurzform: WR-Befehl)
Kontrollieren, welche Schaltungsvariante hierzu vorgesehen ist. ABB-werksmäßig eingestellt für aktive Schaltmaßnahme
(Bild 1./5). Bei passiver Schaltmaßnahme (Bild 1./6, Bild 1./7) Brücke 113/AF 6002 (Bereich Überwachung) entfernen.
mit Brücke 113/AF 6002 ABB-werksmäßig eingebaut: Brücke 113/AF 6002 entfernt vom Anwender:
Bild 1./5 Vorgabe des WR-Befehls durch Kontakt Anmerkung: Bei Ansteuerung mit einem Elektroniksignal, welches nicht aktiv
(drahtbruchsichere Schaltung) Null schalten kann, ist die Brücke, 113/AF6002 vom Anwender zu entfernen
und der Stützpunkt 113/2 mit 0V zu verbinden.
□ Zusätzliche Möglichkeit für Vorgabe der Reglersperre während der Inbetriebnahme vorsehen (z.B. nach Bild 1./5).
□ Potentiometer R5/AF 6002 (Vp) auf Mitte, Potentiometer R3 (n) auf Minimum stellen
1.6. Feldversorgung
Geregelte Feldversorgung
Besonders geeignet für eine geregelte Feldversorgung ist das Feldschwächgerät Typ GLB. Die Ausführung mit einem Nennstrom von 5,5 A
(GLB 0201) ist im AAD 6 . . 1 integrierbar das Gerät mit 15 A - (GLB 0501) ist extern anzuordnen.
Ausführliche Angaben für die Montage und die Inbetriebnahme enthält die mitgelieferte Betriebsanleitung GNV 990 2469.
Das Netzschütz darf nur anziehen, wenn die Überwachungseinrichtungen von z.B. Feldversorgung, Motor-Fremdlüfter den ordnungsgemäßen
Betriebszustand gemeldet haben.
Phasenfolge beachten: An den Anschlüssen AK1, AK2, AK3 muß die Phasenfolge einem Rechtsdrehfeld entsprechen. Bei getrennter
Versorgung von Leistungsteil und Steuerteil ist auf die richtige Phasenzuordnung zu achten! Bei einem Linksdrehfeld (H1 dunkel, H2 an) sind zwei
Drehstromanschlüsse zu tauschen. Leuchtet nach dem Zuschalten die LED H1 nicht, liegt eine Störung vor, die zu beseitigen ist; nähere Angaben
s. 3. Störungsursachen.
□ Antrieb abschalten.
Achtung! Bei eingeschaltetem Gerät keine Änderungen auf der Elektronik durchführen.
□ Strombegrenzungswert auf etwa 5 % Idn einstellen; dazu Brücke P7 - P8/AF 6002 (Bereich n-Regler) einlöten.
Bild 2./1 Anschluß zur Prüfung bei kurzzeitigem Drehen des Motors
Achtung! Bei betriebsmäßigen Sollwertspannungen kleiner 10 V darf die vorzugebende Spannung nsoll, den betriebsmäßig vorgesehenen
max. Sollwert nsoll max nicht überschreiten.
Läuft der Motor kurz an und schaltet das Gerät ab (H2, H3 an), fehlt der Drehzahlistwert oder ist falsch gepolt. Lauft der Motor nicht an und es
fließt Strom:
□ Drehrichtung entsprechend Sollwertpolarität prüfen; bei falscher Drehrichtung Ankerkreis oder Feldkreis und Istwertleitungen umpolen (Antrieb
dazu abschalten!)
□ Bei Antrieben, die in beiden Drehrichtungen arbeiten, Sollwert umpolen: die Motordrehrichtung muß sich ändern.
□ Antrieb abschalten.
Bei einer Sollwertvorgabe und fehlendem oder falsch gepoltem Drehzahlistwert spricht die Tachoüberwachung an:
· LED H3 (rot) an
· 0 V-Ausgabe an X1:25 (+24 V bei vorhandenem Istwert, Belastbarkeit ≥ 600 W bei 20°C)
· Ausgabe des WR-Befehls und Reglersperre, der Antrieb "läuft aus". Gleichzeitig Löschen der Meldung "Betriebsbereit"
(LED H1 bleibt an), Signal an X1:25 wechselt auf 0 V.
□ Soll bei angesprochener Tachoüberwachung die BetriebsbereitmeIdung bestehen bleiben, so ist die Brücke 112/Bereich Über-
wachung auszulöten
□ Soll die Tachoüberwachung grundsätzlich unwirksam sein, so sind auf dem BestückungspIatz Sp die Stifte 38 und 0 V zu verbinden.
□ Prüfung der Tachoüberwachung
□ Antrieb einschalten.
□ Leitung mit Brücke 114/1 verbinden und gegen X1:9 (0 V) tippen (entspricht Istwertunterbrechung): das Gerät muß abschalten und die Störung
mit LED's H2, H3 anzeigen.
□ Antrieb abschalten.
2.3. Strombegrenzung
Die Strombegrenzung ist auf den Nennstrom eingestellt und kann mit dem Widerstand R92/AF 6002 gemeinsam für beide Stromrichtungen bis auf
Null herabgesetzt werden.
Idn = Geräte-Nennstrom
IGrenz
= Strombegrezungswert
Bild 2./2 Strombegrenzungswert in Abhängigkeit von R92 Bild 2./3 Strombegrenzungswert II in Abhängigkeit von R144
Der Strom für die Richtung II kann mit dem Widerstand R144/AF 6002 auf einen kleineren Wert als für Richtung I eingestellt werden (s. Bild 2./3)
□ Antrieb abschalten.
□ Ermittelte Widerstände R92 und ggf. R144/AF 6002 (Bereich n-Regler) einlöten und ggf. Brücke P7 - P8/AF 6002 entfernen.
2.4. Zeitverhalten
Grundsätzliche Abgleichreiheinfolge:
Zuerst Stromregler, danach Drehzahlregler abgleichen. Befindet sich ein weiterer Regler für andere Regelgrößen (z.B. Druck, Kraft, Weg) vor dem
Drehzahlregler, wird er zuletzt abgeglichen.
2.5. Stromregler N4
□ Feldversorgung abklemmen, evtl. vorhandene Feldstromüberwachung überbrücken. Wenn möglich, Motor mechanisch blockieren.
□ Taster (Offner) oder Schalter (Stellung geschlossen) an X1:15 – X1:16 anschließen (Drehzahlregler 1:1 beschaltet).
2.5.1. Stromregler-Bypass N8.1 nur erforderlich bei Antrieben, die mit kleinem Lastmoment betrieben werden (nahezu Leerlauf)
Um ein unzulässiges Überschwingen des Stromes nach einem Last- oder Sollwertsprung zu vermeiden, wird die Beschaltung des Stromreglers bei
Betrieb mit nichtlückendem Strom optimiert. Diese Einstellung hat bei kleiner Last mit lückendem Strom eine sehr träge Stromregelung zur Folge.
Bei lückendem Strom erhält der Stromregler eine P Beschaltung als Bypass die Stromregelung wird dadurch beschleunigt.
Ein sehr gutes Verhalten im Leerlauf oder bei Stillstand wird durch Pulsbetrieb mit kleinem Strom (Nullstrom) erreicht. Der Nullstrom ist mit dem
Widerstand R56 (Bereich I-Regler) einstellbar. ABB-werksmäßig eingestellt ist R56 = 100 kW = Stromistwert von ca. 50 mV Spitze, gemessen an
R93/1 (Bereich I-Regler).
Anmerkung: Je niederohmiger R56, desto kleiner ist der Nullstrom; der Platz R56 darf deshalb nicht unbestückt bleiben!
□ Anlage einschalten und Nullstrom, messen: der Nullstromspitzenwert soll im Bereich von 25 … 100 mV liegen; ggf. R56/AF 6002 bei
ausgeschaltetem Gerät auswechseln.
□ R-Dekade an R12/AF 6002 (Bereich I-Regler). anschließen und Widerstand zwischen 1 … 4,7 kW einstellen.
□ R-Dekade an R13/AF 6002 (Bereich I - Regler) anschließen und mit 820 kW beginnend so lange verringern, bis der Strom wieder die
Lückgrenze erreicht.
□ Widerstand R12 solange erhöhen, bis der Strom gerade beginnt, kleiner zu werden.
□ Antrieb abschalten, Brücke von C5/AF 6002 entfernen und ermittelte Widerstände R12 und R13 auf AF 6002 einlöten.
Hinweis: Wird bei der nachfolgenden Stromregleroptimierung der Widerstand R42/AF 6002 geändert, ist die Bypass-Einstellung nochmals zu
überprüfen.
2.5.2. Stromregleroptimierung
□ An R42/1, 2 eine R-Dekade, an C5/1, 2 eine C-Dekade anschließen und R = 33 kW, C = 1 µF einstellen.
Achtung! Widerstand und Kondensator dürfen auf der Dekade nicht verbunden sein. Die Verbindungsleitungen vom Stromrichter zur
Dekade sind so herzustellen, daß sie sich während der Abgleichmaßnahmen nicht lösen können. Bei eingeschaltetem Gerät
keine Lötarbeiten durchführen.
Bild 2./7
Anschluß der R- und C-Dekade für die Stromregleroptimierung
□ Mehrmals Strom-Sollwertsprünge durch Öffnen des Taster, oder Schalters im X1:15 – X1:16 vorgeben:
Beschaltung ermitteln, bei der der Stromverlauf dem angegebenen in Bild 2./8 entspricht. Vor der Umschaltung auf andere
Beschaltungswerte sollte jeweils Reglersperre vorgegeben werden.
Achtung! Den max. Strom bei stehender Maschine nur kurzzeitig (bis max. 10 s) vorgeben, um eine unzulässige Kollektorerwärmung zu
vermeiden.
Bild 2./8
Stromistwert bei Ankerspeisung, optimaler Verlauf bei sprunghafter
Änderung das Sollwertes von Vorgabe für gerade nicht lückendem
Strom auf Strombegrenzungswert.
Abweichendes Verhalten
Bild 2./13
P-Verstärkung zu klein und I-Verstärkung zu groß:
R42 und C5 vergrößern.
□ Antrieb abschalten.
Hinweise: Ein späteres Erhöhen der Strombegrenzungswerte um mehr als 10 % kann eine neue Optimierung erforderlich machen, Ein
Herabsetzen ist weniger bedeutend, verschlechtert aber das dynamische Verhalten.
Bei einer Änderung von R42/AF 6002 ist die Bypasseinstellung nochmals zu überprüfen (s. 2.5.1).
Die zulässige Stromanstiegsgeschwindigkeit di/dt für den Ankerstrom hängt von der elektrischen und magnetischen Auslegung des Motors ab.
Motoren heutiger Bauart vertragen im allgemeinen ohne Kollektorfeuern die Stromanstiegsgeschwindigkeit von ca. 100 Idn/Sek. Eine zusätzliche
di/dt-Begrenzung könnte erforderlich werden bei
Die Begrenzung beruht auf der Integration des Strom-Sollwerts (C4/AF 6002). Der zulässige di/dt-Wert kann dem Datenblatt des Motor-Herstellers
entnommen werden oder läßt sich anhand des ReversierverhaItens ermitteln (2.6.3.).
Um ein Ansprechen bei Beschleunigungs- und Bremsvorgängen sowie bei Lastschwankungen zu verhindern, erfolgt die Meldung verzögert durch
C65/AF 6002 (Bereich Überwachung):
2.5.5. Stromistwertausgabe
Der Stromistwert kann an X1:1 normiert auf 10V bei Strombegrenzungswert ausgegeben werden:
Idn = Geräte-Nennstrom
IGrenz = Strombegrenzungswert
□ Feldversorgung wieder anschließen, bei vorhandener Feldstromüberwachung Brücke wieder entfernen. Mechanische Blockierung wieder
aufheben, Antrieb für Leerlauf einrichten.
□ Schalterverbindung X1:15 – X1:16 entfernen.
□ Widerstand R89 und Kondensator C31/AF 6002 wieder einlöten.
□ Potentiometer R5/AF 6002 auf Mittelstellung stellen.
□ Sollwertpotentiometer wie in Bild 2./1 (Seite 7) anschließen.
□ Ggf. Verbindung AAD/X1:17 - GLB X1:14 wieder herstellen.
Nenndrehzahl →0
halber
Feldschwächbereich
→0
max. Drehzahl →0
vorgeben und Kollektor beobachten, bei Bürstenfeuer ist die Ursache zu ermitteln, (Ankerspannung und Stromgrenze, sowie Stromistwert
beobachten),
Ein zusätzliches D-Zeitverhalten wird durch Einlöten des Widerstandes R90/AF 6002 und Kondensator C33/AF 6002 erreicht.
Die "l-Verstärkungsunterdrückung" sorgt dafür, daß sich bei Betrieb an der Stromgrenze die neue Drehzahl ohne Überschwingen einstellt.
2.6.5. Drehzahlregleroptimierung
□ Antrieb einschalten.
□ Offset-Abgleich vornehmen: Sollwert "Null“ vorgeben und mit Potentiometer R156/AF 6002 Drehzahl "Null" einstellen; ggf. noch X1:14 und
X1:9 (0 V) verbinden.
□ Kleine Sollwertsprünge (möglichst bei Leerlauf) vorgeben. Der Strom sollte nach Möglichkeit während des Hochlaufs nicht die
Strombegrenzung erreichen.
□ Drehzahlregler-Ausgangsspannung (=Isoll) beobachten. Bei optimaler Beschaltung entspricht der Verlauf dem in Bild 2./15.
Schwingen von Isoll (s. Bild 2./16): R5 in Richtung Minimum drehen (P-Verstärkung kleiner).
Träges Regelverhalten (s. Bild 2./17: R5 in Richtung Maximum drehen (P-Verstärkung größer).
Sollte mit R5/AF 6002 kein optimales Regelverhalten einstellbar sein, muß die Beschaltung R89/AF 6002 und C31 /AF 6002 geändert werden:
R89/2 und C31/2 ablöten und eine RC-Dekade anschließen. Passenden Widerstand R89 und Kondensator C31 ermitteln und bei ausgeschaltetem
Gerät einlöten.
obere Kurve:
Drehzahlregler-Ausgangsspannung,
Meßpunkt X1:16
untere Kurve:
Drehzahlistwert
Meßpunkt Pin 35/SP
Bild 2./15
Optimaler Verlauf bei sprunghafter Änderung des Sollwertes
obere Kurve:
Drehzahlregler-Ausgangsspannung
untere Kurve:
Drehzahlistwert
Bild 2./16
Schwingen, I-Verstärkung verkleinern durch größeren Kondensator C31, P-Verstärkung mit Potentiometer R5 verändern
obere Kurve:
Drehzahlregler-Ausgangsspannung
untere Kurve:
Drehzahlistwert
Bild 2./17
Träges Regelverhalten, I-Verstärkung vergrößern durch kleineren Kondensator C31, P-Verstärkung mit Potentiometer R5 vergrößern
2.6.6. Meldung Drehzahl kleiner Minimal-Drehzahl
LED H8 (grün) an
Der Ansprechwert ist vom Widerstand R190/AF 6002 (Bereich Überwachung) abhängig:
2.6.7. Stillstandslogik
Das Stillstandssignal kann mit dem Drehzahlerreicht-Signal verknüpft werden, so daß aus der Stillstandserfassung eine Stillstandslogik wird. D. h.,
unterschreiten der Drehzahlistwert und der Drehzahlsollwert die jeweilige Meldeschwelle, kommt es zur Ausgabe der Meldung nist = nsoll = 0.
Bei einer Sollwertvorgabe größer als die Ansprechschwelle wird die Stillstandsmeidung wieder unterdrückt.
V 411
Der Drehzahlistwert wird mit dem Drehzahlsollwert verglichen. Sobald die Abweichung den mit R191/AF 6002 eingestellten Wert unterschreitet,
kommt es zur Meldung "Drehzahl-Erreicht":
Einstellung Ansprechwert: mit R191 /AF 6002, die prozentuale Ansprechempfindlichkeit bleibt gleich in einem weiten
Drehzahlbereich
Wird die Meldung Strom an der Strombegrenzung oder Überstrom nicht benötigt, ist alternativ eine Drehzahlüberwachung möglich. Aktivierung der
Überwachung: vom Anwender Brücke 110/AF 6002 entfernen und Widerstand R215/AF 6002 einlöten, Widerstand R93/AF 6002 darf nicht
eingelötet sein.
□ Ansprechschwelle prüfen.
3. Störungsursachen
Netzschütz hat abgeschaltet durch Schalten eines Meldekontaktes in der Überwachungsschleife oder keine Gleichspannung durch Vorgabe des
Sperrbefehls.
Mögliche Ursachen:
□ Feld fehlt
□ Thermoüberwacher F100 /AAD-Gerät hat angesprochen z.B. Behinderung der Luftzufuhr, Lüfter ausgefallen
* Meldungen bleiben nach Abschalten des Netzschützes erhalten, wenn Steuerteil und Leistungsteil getrennt versorgt erden.
3.2. Motordrehzahl geht unter Belastung zurück
Mögliche Ursachen:
□ Überlast
Mögliche Ursachen:
□ Sollwertspannung zu niedrig
3.4. Motor beschleunigt schon bei kleiner Sollwertvorgabe auf max. Drehzahl
Mögliche Ursachen:
□ zu hohe Sollwertspannung
3.5. Drehzahl pendelt nach Last- oder Sollwertänderung oder Motor läuft ruckweise
Mögliche Ursachen:
4.1. AAD 6 . . A
□ Anlage abschalten.
□ Befestigungsschrauben (rechte und linke Vorderkante vom Gerät) löse, und Steuersatz herausklappen.
□ Kreuzschlitzschrauben der Befestigungsplatte “Überspannungsschutz“ lösen. Platte vorsichtig nach vorne ziehen, bis der Leistungsteil von oben
zugänglich ist.
□ Zündleitungen vom auszutauschenden Modul markieren (Zuordnung zu Thyristor 1 und 2)und abziehen.
□ Bei Austausch von Modul V13/V26, Anschlußschrauben der Module V14/V21 und V16/V23 halb herausdrehen. Bei Austausch von Modul
V15/V22, Anschlußschrauben der Module V16/V23 und V12/V25 halb herausdrehen.
Hinweis: Die Befestigungsschrauben lasen sich mit einem Klemmschraubendreher bequem entfernen und einsetzen.
□ Kühlfläche säubern.
□ Anschlußschrauben eindrehen; ggf. bei der mittleren Schraube Flachstecker für Hilfsanschluß unterlegen.
□ Anlage abschalten.
□ Befestigungsschrauben (rechte und linke Vorderkante vom Gerät) lösen und Steuersatz herausklappen.
□ Vom auszutauschenden Thyristor und den in der gleichen Reihe daneben befindlichen Zündleitungen von Impulsübertragern abziehen.
□ Verspannschrauben (AAD 70 . . : SW 8 mm, AAD 71 . . : SW 10 mm) der 3 Thyristoren mit Steckschlüssel herausdrehen; dazu Schrauben von
jeder Spannkappe kreuzweise jeweils bis zu 1/2 Umdrehung lösen.
□ Spannkappen vorsichtig abnehmen; dabei darauf achten, daß die Spannfeder(n) und ggf. Stahlplatte(n) nicht herausfallen. Verbindungsschiene
abnehmen.
□ Auf Kühlerseite des Austausch-Thyristors dünn Kontaktfett Bechern Rhus SU2 auftragen.
□ Thyristor auf Kühler legen. Achtung! Auf Zentrierung und Einbaulage (Polarität) des Thyristors sowie Stellung da, Zündanschlüsse (links)
achten.
□ Thyristor eine halbe Umdrehung nach rechts und links drehen, um die Paste gleichmäßig zu verteilen.
□ Bauteil, gemäß obiger Skizze einlegen und Gs-Schiene auflegen. Gewinde der Schrauben dünn mit Molykote einfetten und wechselseitig mit
je 1/2 Umdrehung anziehen, bis Spannkappen auf Kühlkörper aufliegen.
□ Übertragerplatten befestigen.
□ Anlage abschalten.
□ Befestigungsschrauben (rechte und linke Vorderkante vom Gerät) lösen und Steuersatz herausklappen.
□ Beim auszutauschenden Einschub Sekundärleitungen der Impulsübertrager (gehen zum Steuersatz) abziehen. Beim mittleren Einschub
zusätzlich Leitungen vom Thermoelement abziehen.
□ Einschub herausziehen.
□ Aus Einschub 3 Kupferrohre mit Schrauben und Isolierrohren herausziehen und in auszutauschenden Einschub einsetzen.
□ Einschub so hinlegen, daß Blattfedern der Verspannungen von oben zugänglich sind.
□ Muttern beider Verspannungen abschrauben; dabei wechselseitig bis 1/3 Umdrehungen lösen.
□ Auf Kontaktflächen des (der) Thyristors (Thyristoren) dünn Kontaktfett Bechern Rhus SU2 auftragen.
□ Thyristor(en) entsprechend nachstehender Skizze einlegen. Achtung! Auf Zentrierung und Einbaulage (Polarität) des (der) Thyristors
(Thyristoren) sowie Stellung der Zündanschlüsse achten.
5. Klemmenbelegung
Nr. Funktion
X1:1 Ausgang Stromistwert (+ 10 V = IdN: belastbar mit 3 mA)
2 Verbindung zum Subprint-Platz (Punkt 2)
3 Verbindung zum Subprint-Platz (Punkt 3)
4 Ausgang +15 V, stabilisiert, belastbar mit 100 mA
5 Eingang * Hauptsollwert-Eingang (Umax = 15 V)
6 0 V (Reglererde RE)
7 Ausgang -15 V, stabilisiert, belastbar mit 100 mA
8 Eingang * Istwerteingang für UT - 10 . . . 33 V oder 30 . . . 95 V
9 0 V (Reglererde RE)
10 Ausgang +24 V, unstabilisiert, belastbar mit 350 mA abzüglich Belastung an X1:4
11 Eingang Reglersperre (+24 V = Regler frei; offen = Reglersperre)
12 Gerätemasse GE (als Schirmerde für Schirmleitungen)
13 Eingang +24 V = Start, offen = Halt mit verzögerter Reglersperre
14 Eingang ** n-Regler Gleichtakt-Bezugspunkt für externe Sollwerte
15 Eingang * Zusatzsollwert-Eingang (Umax = 15 V)
16 Ausgang Drehzahlregler-Ausgang (±10 V = +Isoll max)
17 Eingang ** Zusatzeingang für Stromregler
18 Gerätemasse GE (als Schirmerde für Schirmleitungen)
19 Eingang Externe Strombegrenzung 1 und 11 und Verbindung zum Subprint-Platz (Punkt 19)
20 0 V (Reglererde RE)
21 Verbindung zum Subprint-Platz (Punkt 21)
22 Verbindung zum Subprint-Platz (Punkt 22) und X18:1 über einen einlötbaren Widerstand
23 Ausgang Relaistreiberausgang “Betriebsbereit“ = 1 (+24 V)
24 Ausgang Relaistreiberausgang “Stillstand“ = 1 (+24 V)
25 Ausgang Relaistreiberausgang “Tachoausfall“ = 0 (0 V)
26 Ausgang Relaistreiberausgang “Drehz.-Erreicht“ = 1 (+24 V)
27 Ausgang Relaistreiberausgang “Überstrom“ = 0 (0 V)
28 0 V (Reglererde RE)
29 Eingang * Istwerteingang für UT = 90 . . . 280 V
X 17: 1 Ausgang = X1:23 (“Betriebsbereit“)
2 Ausgang = X1:24 (“Stillstand“)
3 Ausgang = X1:25 (“Tachoausfall“)
4 0 V (Reglererde RE)
5 0 V (Reglererde RE)
X 18:1 Ausgang Verbindung zum Subprint-Platz (Punkt 22)
2 Ausgang = X1:26 (“Drehzahl-Erreicht“)
3 Ausgang = X1:27 (“Überstrom“)
4 0 V (Reglererde RE)
5 0 V (Reglererde RE)
X20:1 Ausgang +24 V = Richtung II, ca. +1 V = Richtung I
2 Ausgang +24 V = Richtung I, ca. +1 V = Richtung II
3 Eingang +15 V = Impulse unterdrückt
4 0V
5 0V
-14 V / +14 V = der jeweils fettgedruckte Wert entspricht dem Wert während der angegebenen Funktion (z.B. Strombegrenzungs-Meldung)
6. Bestückung
AAD 6101 A: MCC 18-12io1 6131 A: MCC 18-08io1 6151 A: MCC 18 15io1
AAD 6201 A: MCC 25-12io1 6231 A: MCC 25-08io1 6251 A: MCC 25 15io1
AAD 6301 A: MCC 40-12io1 6331 A: MCC 40-08io1 6351 A: MCC 40-15io1
AAD 6401 A: MCC 40-12io1 6431 A: MCC 40-08io1 6451 A: MCC 40 15io1
AAD 6501 A: MCC 55-12io1 6531 A: MCC 55 08io1 6551 A: MCC 55 15io1
AAD 6601 A: MCC 55-12io1 6631 A: MCC 55-08io1 6651 A: MCC 55-15io1
AAD 6701 A: MCC 65-12io8 6731 A: MCC 65-08io8 6751 A: MCC 65-15io8
AAD 6801 A: MCC 90-12io1 6831 A: MCC 90-08io1 6815 A: MCC 90-15io1
Thyristoren
Die Weiterentwicklung unserer Geräte kann zu anderen Bestückungen führen. Als Ersatzteil sind daher die im Gerät
eingebauten bzw. mitgelieferten Bauelemente zu bestellen.
Thermoschalter F100
Überspannungsschutz
3 x DSI17 - 14 A, 3 x DSI17 – 16 A,
Ident-Nr. Ident-Nr.
GNB 1 117 000 R5 GNB 1 117 000 R6
Lüfter
Page
1. Preliminary checks 28
1.2 Checks and adjustments with power off (e.g. with line fuses removed) 28
3. Trouble-shooting 45
3.4 Motor accelerates to max. speed even after small reference has been present 46
3.5 Hunting occurs after load and reference changes or motor operation is jerky 46
5. Wiring of terminals 50
6. Components 52
Arrangement of potentiometers and LED’S
1. Preliminary checks
□ Check readiness for operation, e.g. oil, brake, ball-screw clamps, gear box, etc.
1.2 Checks and adjustments with power off (e.g. with line fuses removed)
□ Check AAD unit for shipping and mounting damage. Check main and control leads for proper and tiqht connection.
□ Check optional accessories (including documentation supplied). For start-up use unit without accessory equipment at first (does not apply to field
weakening PCB GLB). Then, install the accessory equipment and begin with start-up of this equipment.
□ Check for proper power supply and check that the equipment is properly protected (heed max. current). Inspect protective measures (grounding
of equipment).
□ Supply voltage
The underlined value indicates the voltage for which the equipment is usually supplied by ABB. For adjustments see also component AM 60 . .
“Power pack”.
□ Change jumper R57/AF 6002 (PCB area: current regulator) as instructed in the table below (EMF adaption)
□ Loosen knurled-head screws and swing out electronic section. Change jumpers on transformer module AM 60 . . (at upper edge):
Since power section and electronic section are supplied separately, it is possible to switch on the electronic section only. The power section can be
switched on after the auxiliaries and other items of equipment have reached the operating state. In the event of fault only the power section has to
be switched off; the fault signal of the electronic section is maintained.
□ Loosen knurled-head screws and swing out electronic section. Remove jumpers between
terminals R3, S3, T3 and plugs R2, S2, T2 on transformer module AM 60 . . . Connect
the electronic section leads to terminals R3, S3, T3.
Line voltage corresponds to rated supply voltage, motor voltage considerably smaller than
recommended
□ Calculate size of resistor R57 / AF 6002 (PCB area: current regulator) and solder in:
The resistor installed should approximate the calculated value as closely as possible.
UV
---------------- 105 – 117 114 – 126 123 – 136 134 – 148 146 – 162 156 - 173 167 – 185 177 – 195 192 – 212
V/3 ph
R57
----------- 10 22 // 22 12 27 // 27 15 33 // 33 18 39 // 39 22
kW
UV
---------------- 201 – 222 219 – 243 239 – 265 249 – 275 274 – 302 301 – 333 328 – 362 356 - 394
V/3 ph
R57
----------- 47 // 47 27 56 // 68 33 39 47 56 68
kW
□ Frequency
The units can be operated with a system frequency ranging from 50 Hz to 60 Hz (±5 %) without the need for any adjustment measures.
□ Speed reference
The input for the main reference is terminal X1:5 (max. admissible value 12 V).
Voltage of speed reference signal = 10 V (factory-adjusted)
Adaption of speed reference
Fig. 1, / 3 Resistance R102 as a function of speed Fig. 1. / 4 Resistance R229 as a function of speed
reference ( < 10 V) reference ( > 10 V ... 12 V)
□ Disconnect reference leads from superordinated control system (e.g. numerical control) at X1:5, X1:15. For start-up the internal reference signal
voltage source can be used; in this case connection must be implemented as indicated in figure 2./1 (page 7).
The feedback voltage (tach voltaqe) depends on the motor speed and the tach rating (voltage UT at 1000 min -1).
□ Adaption
Fine balancing of speed is performed on pot R3/AF 6002, with the motor running; measuring of actual speed with an RPM meter at the motor shaft.
1.4 Stop with delayed regulator blocking at X1:13
lf the input at terminal X1:13 is not used, the regulators are blocked irrespective of the reference applied to X1:5. lf a starting command is given
(connect X1:13 to +24 V, e.g. X1:10), the drive starts without any delay. lf the starting command (stop) is removed, the reference is switched to
zero, the regulators are blocked after elapse of an adjustable delay time (braking time tV) and the firing pulse are displaced to the inverter limit
position.
Check which circuit configuration suits your application. The as-delivered condition of the circuit provides for active switching by means of a
contact (Fig. 1. / 5). For passive switching, i.e. presetting of inverter command and regulator blocking by electronic signal (Fig. 1. / 6 and
Fig. 1. / 7), jumper 113 / AF 6002 (PCB area monitoring) must be removed.
Drawn contact position = inverter command and 0V = inverter command and regular blocked
regulator blocked
24 V = pulse release
Contact closed = pulse release
Remark: in the case of actuation by means of an electronic signal,
Fig. 1./5 Inverter command by way of contact which is not able to actively switch to zero, jumper 113 / AF 6002
(fail-safe circuit) must be removed by the user and solder point 113 / 2 must be
connected with 0 V,
□ Set pot R5 / AF 6002 (VP) on 12 o'clock position and pot R3 (n) on min.
□ Switch the system on and adjust field current while motor is in cold condition. Inspect field current monitor (if installed).
The type GLB field weakening PCB lends itself particularly well to controlled field supply. The version with a rated current of 5.5 A d.c. (GLB 0201)
can be integrated into the AAD 6..1, whereas the version with 15 V d.c. (GLB 0501) must be installed separately.
The operating instructions GNV 990 2469 supplied herewith contain detailed information for installation and start-up.
The line contactor should pull up only if the monitors, e.g, the field supply and motor fan monitor, have signalled readiness for operation.
Note proper phase sequence: At terminals AK1, AK2, AK3 the phase sequence must correspond to a clockwise rotating field.
With power section and electronic section being supplied separately, attention must be paid to the proper
phase sequence !
In the case of a counterclockwise rotating field (H1 dark, H2 lit) two three-phase wires must be interchanged
and reconnected. lf, after reconection LED H1 does not come on, there must be a fault. For fault elimination
see 3. TROUBLE- SHOOTING.
Important! Do not perform any changes on the electronic with the unit switched on.
Important! lf voltages smaller than 15 V are used for the speed reference during operation, the preset voltage
for nref must not exceed the nref max value intended for normal operation.
□ Switch unit on, cancel regulator blocking command and observe motor:
lf the motor accelerate, for a short time, and then the AAD unit switches off (LEDs H2 and H3 lit),
there is no tach feedback or the tach feedback has the wrong polarity.
□ Check sense of rotation in accordance with reference polarity; in the case of wrong sense of rotation, change polarity of amature circuit or field circuit
and tach feedback lines (for doing so, switch drive off!).
The tach monitor responds in cases where no speed feedback or feedback with wrong polarity is provided after presetting
of the speed reference
§ 0 V output at X1:25 (+24 V when there is a feedback, load capacity ≥ 600W at 20°C).
§ Output of inverter command, the regulator is blocked, and the drive coasts to rest. Simultaneously the “Ready for operation“ signal is
cancelled (LED H1 remains lit), signal at X1:25 changes to 0 V.
□ If in cases where the tach monitor responds, the “Ready for operation" signal is to be maintained , jumper 112 (PCB area: monitoring) must be
removed.
□ lf the tach monitor is to remain ineffective pins 38 and 0 V (space Sp) are to be connected.
□ Connect a piece of wire with jumper 114/1 and touch to X1:9 (0 V) (equivalent to tach loss). Now the AAD should switch off and LED's H2 and
H3 should be lit.
□ Cancel the signal by switching the unit off and then on.
The current limit is adjusted to rated current and can be reduced for both directions of rotation down to zero by means of resistor R92/AF 6002.
Fig. 2. / 2 Current limit I as a function of R92 Fig. 2. / 3 Current limit II as a function of R144
The current for direction II can be adjusted to a smaller value than for direction I by means lf resistor R144/AF 6002 (see Fig. 2./3)
□ Solder in resistors R92 and, if required, R144/AF 6002 with the calculated resistance values (PCB area: speed regulator) and, if necessary
remove jumper P7 - P8/AF 6002.
2.4 Optimization of regulators
First current regulator then speed regulator. If there comes another regulator for controlling other variables (such as pressure, force, travel) before
the speed regulator, it should be optimized last.
□ Disconnect field supply, bridge field current monitor (if installed). lf possible, block motor mechanically.
□ Interrupt R-C network of speed regulator at R89/2 and C31/2 (PCB area: speed regulator).
□ Connect oscillograph to R93/1 (PCB area: speed regulator) and 0 V.
□ Connect pushbutton (NC contact) or switch (closed type) to X1:15 – X1:16 (speed regulator arranged for 1:1 amplification).
□ Connect pot for reference settinq.
□ Remove connection AAD/X1:17 - GLB/X1:14 - lf any.
Only required for drives operating with small load torque (nearl no-load operation).
In order to avoid overshooting of the current after sudden load or reference changes, the R-C network of the current regulator is optimized during
operation with continuous current flow. This adjustment leads to a very slow response of the current regulator in the event of small loads and
intermittent flow of current. Therefore, a P circuit is used as a bypass during operation with intermittent current flow in order to improve the dynamic
response of the current regulator.
Excellent response at no-load or zero-speed is achieved by pulse operation with a small current (zero-current). The zero-current can be adjusted
with resistor R56 (PCB area: current regulator). The factory-adjusted value of R56 is 150 kW which corresponds to a current feedback of approx. 50
mV (peak), measured at R93/1 (PCB area: current regulator).
Note: The lower the resistance of R56, the smaller the zero-current; therefore, the space of R56 must not remain unoccupied.
Fig. 2. / 5 Zero current, measuring point R93/1
□ Bridge capacitor C5/AF 6002 (current regulator feedback), thus decreasing the current.
□ Connect variable resistance source to R13/AF 6002 (PCB area: current regulator) and reduce it, starting with 820 kW, until the current has
reached the limit for continuous flow again.
□ Increase resistance of R12 until the current flow just begins to decrease.
□ Switch the drive off, remove jumper from C5/AF 6002 and solder in the determined resistances R12 and R13 on AF 6002.
Remark: If during the subsequently performed current regulator optimization resistance R42/AF 6002 is changed, the bypass adjustment
must be checked again.
Important! Resistor and capacitor must be disconnected from the sources. The connections must be such that they cannot work loose during
the balancing procedure. Do not perform any soldering work while the unit is switched on
□ Preset several abrupt changes in current reference by operating the pushbutton or switch at X1:15 - X1:16: determine R-C network at which the
current curve looks like the curve shown in Fig. 2. / 8. Before changing over to then R-C element values, the regulator blocking command should
be applied.
Important! Avoid presetting the max. current for more than 10 s while the motor is or zero speed; otherwise commutator overheating may be
the consequence
Fig. 2. / 9 Fig. 2. / 10
Proportional amplification too small: Proportional amplification too large:
increase value of R42 reduce value of R42
Fig. 2. / 11 Fig. 2. / 12
Integral amplification too large: Proportional and integral amplification too small:
increase value of C5 increase value of R42 and reduce value of C5
Fig. 2. / 13
Notes: If later on the current limit is increased by more than 10%, the optimization procedure may have to be repeated. This is not necessary
in the case of a current reduction, which may, however, affect the dynamic control response.
In the case of any change of R42/AF 6002 the bypass adjustment must be checked pure more (see 2.5.1).
2.5.3 Limitation of rate of rise of current (di/dt adjust only when required)
The admissible rate of rise of the armature current di/dt depends on the electrical and magnetic design data of the motor. In general it can be said
that today's motors are capable of handling the rate of rise of the current (approx. 100 Idn/s) of conventional current regulator R-C networks. A
limitation of the rate of rise might become necessary in the case of
Limitation is achieved by integration of the current reference (C4/AF 6002), The admissible di/dt value can be taken from the data sheet of the
motor manufacturer or can be determined from the reversing behaviour of the motor (see 2.6.3).
□ Guide values: 0.22 µF to 1 µF small capacitance results in high di/dt. As delivered by ABB: 0.47 µF
2.5.4 “Current at limit” or “Overcurrent” signalling
□ Jumper 110/AF 6002 (PCB area: speed regulator) soldered in (as-delivered condition):
Fig. 2. / 14
In order to prevent a response during acceleration and deceleration or when the load is fluctuating, the signals are supplied, delayed by C65/AF
6002 (PCB area: monitoring):
The current feedback signal can be put out at X1:1, with the current limit corresponding to a 10 V signal:
□ Determine value of resistor R14/AF 6002 (PCB area: current regulator) and solder in.
□ Reconnect field supply; remove jumper of field current monitor (if installed). Cancel the mechanical blocking. Adjust drive for no-load operation.
□ Remove connection between X1:15 and X1:16.
□ Solder in resistor R89 und capacitor C31/AF 6002.
□ Set R5/AF 6002 on 12 o'clock position
□ Connect reference pot as illustrated in Fig. 2. / 1 (Page 8).
□ lf necessary, reestablish connection AAD/X1:17 - GLB/X1:14 .
The armature serves as an approximate measure for the speed; however, for more accurate adjustment measure the motor speed with an RPM
meter and make the necessary corrections (if any) on R3/AF 6002.
2.6.3. Controlled field weakening, adjustment of crossover point between armature and field control range
□ Follow procedure indicated in operating instructions for the field weakening PCB.
□ Check behaviour of motor during reversing
□ Provide several abrupt reference settings:
- from rated speed to zero
- from half field weakening range to zero
- from max. speed to zero
- Observe the commutator while applying these abrupt reference changes. If sparking occurs at the brushes, change the
rate of rise of the current di/dt (see 2.5.3).
An additional derivative control action can be achieved by soldering in resistor R90/AF 6002 and capacitor C33/AF 6002. By means of “Integral
amplification suppression" it is ensured that the new speed is reached without overshooting during operation at the current limit.
2.6.5 Speed regulator optimization
Connect pot with changeover switch, and oscillograph as illustrated in Fig. 2. / 15.
□ Apply small reference changes (at no-load if possible). The current should not reach the current limit during acceleration.
□ Observe output voltage of speed regulator (= Iref). lf the R-C network is optimal, the curve obtained should correspond to that shown in
Fig. 2. / 16.
□ In the case of deviations, optimize control response by adjusting pot R5/AF 6002:
lf Iref is oscillating (see Fig. 2. / 17): turn pot R5 counterclockwise (proportional amplification smaller).
If the dynamic response is slow (Fig. 2. / 18): turn pot R5 clockwise (proportional amplification larger).
If the control response cannot be optimized by adjusting pot R5/AF 6002, the R-C network R89/AF 6002 and C31/AF 6002 have to be modified:
remove R89/2 and C31/2 and connect variable R-C sources. Determine the required resistance of R89 and the required capacitance of C31.
Solder in the required resistor and capacitor while the unit is switched off.
upper curve:
speed regulator output voltage,
measuring point X1:16
lower curve:
speed feedback,
measuring point pin 35/SP
Fig. 2. / 16
Optimal curve with abrupt change in reference
upper curve:
speed regulator output voltage
lower curve:
speed feedback
Fig. 2 . / 17
Overshoot: decrease internal amplification by increasing the value of capacitor C31; change proportional amplification with pot R3
upper curve:
speed regulator output voltage
lower curve:
speed feedback
Fig. 2. / 18
Slow control response: increase integral amplification by decreasing the value of capacitor C31; increase proportional amplification with pot R3.
2.6.6 "Speed lower than min. speed” signal
The min. value at which the signal is supplied depends on resistor R190/AF 6002 (PCB area: monitoring):
Fig. 2. / 19
□ Determine value of resistor R190/AF 6002 and solder in; check threshold value.
The zero-speed signal can be combined with the “speed reached” signal, so that zero-speed detection becomes a zero-speed logic. This means
that the signal nfb = nref = 0 is initiated, if both the speed feedback and speed reference have fallen below the respective signal threshold,
If a reference larger than the threshold value is preset, the zero-speed signal is suppressed again.
V 411
The speed feedback is compared with the speed reference. As soon as the deviation becomes smaller than value adjusted by means of
R191/AF 6002, the “Speed reached” signal is provided:
Relay driver outputs X1:26 and X18:2 “1” = +20 V to +30 V
As delivered by ABB :
lf the signal "Current at limit" or "Overcurrent" is not required, speed monitoring is possible as alternative.
Activation of the monitor: jumper 110/AF 6002 to be removed and resistor R215/AF 6002 to be soldered in by user,
resistor R93/AF 6002 must not be soldered in.
Fig. 2. / 20
Line contactor has switched off due to the operation of a pilot contact in the monitoring circuit; or no DC voltage
because blocking command has been preset.
Possible causes:
Signal on AF 6002
“ - ground fault
“ “ § phase loss
“ “ § fuse of smubber circuit blown. F71, F72, F73 (starting with AAD 65..)
“ “ - short circuit
“ “ - ground fault
“ “ - thyristor defective
H6 or H7 H1, H2, H3, H8, § short circuit +24 V to 0 V, fuse F1/AM 60.. blown
(Iow intensity)
* lf electronic action and power section are supplied separately, the signals are maintained after the line contactor switches off.
3.2 Motor speed decreases under load
Possible causes:
□ Current limit set too low.
□ Field current too low.
□ Series field (D1 - D2) connected.
□ Overload.
□ Brushes of motor not in neutral
Possible causes:
□ See under 3.2.
□ Speed feedback not properly balanced on R3/AF 6002.
□ Voltage of speed reference too low.
3.4 Motor accelerates to max. speed even after small reference has been preset
Possible causes:
□ Voltage of speed reference too high,
□ Open circuit on reference pot; no 0 V connection.
3.5 Hunting occurs after load and reference changes or motor operation is jerky
Fig. 4. 1 / 1
□ Turn in terminal screws; use center screw for attaching tab for auxiliary load (if any).
□ Turn in mounting screws and tighten them well; tightening torque 4,5 Nm ±10%
□ Tighten terminal screws and retighten the screws of all modules.
□ Plug in firing leads; in so doing be careful to connect the correct leads to thyristor 1 and 2.
□ Install snubber circuit assembly.
□ Install fan assembly (if any); fold up electronic section and tighten mounting screws.
4.2 AAD 70.., 71..
Figure 4. 2 / 1
□ Pull Pulse firing leads of the thyristor to be replaced and of those in the same row form the pulse transmitters.
□ Remove pulse transmitter plates by removing 2 recessed head screws per plate.
□ Screw out clamping bolts (AAD 70.., SW 8 mm, AAD 71.., SW 10 mm) of the three thyristors by using a socket spanner; for doing so untighten
alternately opposite screws of each clamping cap by up to 1/2 turn each.
□ Carefully remove clamping caps and see to it that clamping sprinq(s) and, if any, steel plate(s) do not fall out.
□ Remove connecting bar.
□ Remove defective thyristor.
□ Clean heatsing surface.
□ Attach firing leads to the new thyristor.
□ Apply a thin layer of contact grease Bechem Rhus SU2 to the heatsing side of the new thyristor.
□ PIace thyristor onto heatsink. Important! Note proper centering and installation position (polarity of thyristor as well as proper position of the
firing terminals (left).
□ Turn thyristor by half a turn clockwise and then counterclockwise for evenly spreading the grease.
□ Install components in accordance with the above drawing and fit d.c. bar. Apply a thin layer of Molykote to the threads of the screws and tighten
alternately opposite screws by 1/2 turn each until clamping caps come to rest on heatsink.
□ Remount Am and Km bars.
□ Mount pulse transmitter plates.
□ Attach firing leads to pulse transmitters.
□ Swing up pulse firing PCB and tighten mounting screws.
4.3 AAD 80..
□ Pull primary leads of the pulse transmitters (to the pulse firing PCB) from plug-in module to be replaced. When replacing the center module, the
leads must also be removed from the thermocouple.
□ Remove fastening screws SW 13 from the front plate bores by using a socket spanner.
□ Pull plug-in module out.
□ Remove 3 copper pipes with screws and isulating pipes from plug-in module and place them into the new plug-in module.
□ Push in new plug-in module and mount it by means of 3 screws.
□ Attach leads to pulse transmitters.
□ On the center plug-in module also attach leads to the thermal switch.
□ Swing up pulse firing PCB and tighten knurled-head screws.
Replacement of a thyristor
Thyristor in the top section Pull off firing leads and remove thyristor.
Thyristor in the bottom section Pull off firing leads from both top thyristors and remove thyristor.
Remove copper plates. Pull off firing leads from the thyristor to be replaced and remove it.
□ Clean all accessible contact plates as well as the contact surfaces of the removed thyristors.
□ Attach firing leads to the new thyristor.
□ Apply a thin layer of contact grease Bechem Rhus SU2 to the contact surfaces of the new thyristor(s).
□ Place thyristor(s) in accordance with the below drawing. Important! Note proper centering and installation position (polarity) of the thyristor(s) as
well as proper position of the firing terminals.
Figure 4. 3 / 2
5. Wiring of terminals
No. Function
X1 : 1 Output Current feedback (+10 V = IdN; load capacity 3 mA)
2 Connection to subboard space (point 2)
3 Connection to subboard space (point 3)
4 Output +15 V, regulated, load capacity 100 mA
5 Input * Main reference value input (Umax = 15 V)
6 0 V (regulator earth RE)
7 Output -15 V, regulated, load "capacity 100 mA
8 Input * Feedback input for UT = 10 ... 33 V or 30 ... 95 V
9 0 V (regulator earth RE)
10 Output +24 V, unregulated, load capacity 350 mA minus load at X1:4
11 Input Regulator blocking (+24 V = regulator released; open = regulator blocked)
12 Unit frame RE (screen earth for screen leads)
13 +24 V = start, open = stop with delayed regulator blocking
14 Input ** Speed regulator in-phase reference point for external reference values
15 Input * Additional reference input (Umax = 15 V)
16 Output Speed regulator output (± 10 V = ±Iref max)
17 Input ** Additional input for current regulator
18 Unit frame RE (screen earth for screen leads)
19 Input External current limitation I or II and connection to subboard space (point 19)
20 0 V (regulator earth RE)
21 Connection to subboard space (point 21)
22 Connection to subboard space (point 22) and to X18:1 via a resistor
23 Output Relay driver output “Ready for operation” = 1 (+24 V)
24 Output Relay driver output “Zero speed” = 1 (+24 V)
25 Output Relay driver output “Tach loss” = 0 (0 V)
26 Output Relay driver output “Speed reached” = 1 (+24 V)
27 Output Relay driver output “Overcurrent” = 0 (+24 V)
28 0 V (regulator earth RE)
29 Input* Feedback input for UT = 90 ... 280 V
X17:1 Output X1:23 (“Ready for operation")
2 Output X1:24 (“Zero speed“)
3 Output X1:25 (“Tach loss“)
4 0 V (regulator earth RE)
5 0 V (regulator earth RE)
X18:1 Output Connection to subboard space (point 22)
2 Output X1:26 (“Speed reached“)
3 Output X1:27 (“Overcurrent“)
4 0 V (regulator earth RE)
5 0 V (regulator earth RE)
X20:1 Output +24 V = direction II, approx. +1 V = direction I
2 Output +24 V = direction I, approx. +1 V = direction II
3 Input +15 V = pulses suppressed
4 0V
5 0V
Pin strip
X15:
1 nref main input 0 … ±15 V
2 = X1:13 = point 13 (subboard space)
3 not wired (soldering tab)
4 Speed regulator mixing point *
5 Centre point of speed regulator network *
6 P-gain of speed regulator *
7 Speed regulator output (= ±Iref) 0 … ±10 V
8 Input at Iref polarity reverser 0 … ±10 V
9 Iref main input 0 … -10 V
10 Current regulator mixing point *
11 Centre point of current regulator network *
12 Current regulator output -14 ... -2 … +2 … +14 V
(= ±Ucontrol bevor EMF control)
13 not wired (soldering tab)
14 = X1:15 = point 15 (subboard space)
15 ±Iref signal for direction indicator 0 … ±10 V
16 Signal output for change over interval 0V/-14 V
(= X11:2)
AAD 6101A MCC 18 - 12io1 6131A MCC 18 - 08i o1 6151A MCC 18 - 15io1
AAD 6201A MCC 25 - 12io1 6231A MCC 25 - 08i o1 6251A MCC 25 - 15io1
AAD 6301A MCC 40 - 12io1 6331A MCC 40 - 08i o1 5351A MCC 40 - 15io1
AAD 6401A MCC 40 - 12io1 6431A MCC 40 - 08i o1 6451A MCC 40 - 15io1
AAD 6501A MCC 55 - 12io1 6531A MCC 55 - 08i o1 6551A MCC 55 - 15io1
AAD 6601A MCC 55 - 12io1 6631A MCC 55 - 08i o1 6651A MCC 55 - 15io1
AAD 6701A MCC 65 - 12io8 6731A MCC 65 - 08i o8 6751A MCC 65 - 15io8
AAD 6801A MCC 90 - 12io1 6831A MCC 90 - 08i o1 6851A MCC 90 - 15io1
Thyristors
Further develop of our units may result in the use off different thyristor
modules and thyristors. Therefore, please order the type of thyristor modules
or thyristors installed in or supplied with your unit, when in need of spares.
Transient suppresion
3 x DSI17 - 14 A, 3 x DSI17 – 16 A,
Ident-No. Ident-No.
GNB 1 117 000 R5 GNB 1 117 000 R6
(1) In the case of a defect, the semiconductor fuses in the AC lines respond.
Fan
Pulse firing board (second board) Typ AE 6003 for AAD 61.1A - 68.1A
Typ AE 6004 for AAD 70.1A - 80.1A
Power pack (at the back of the electronics Typ AM 6203 for AAD 6.01A - 8001A
casing) Typ AM 6032 for AAD 6.31A - 8031A
Typ AM 6052 for AAD 6.51A - 8051A