is a unit designed to
treat fresh air only. To handle the
cooling load / heating losses of the
room due to internal and external
heat transmission, an additional APPLICATION
cooling / heating source must be
added. The is intended for a
is designed and manu- wide product range with small vol-
factured for internal installations ume and requirements for regular
within artificial / false ceilings only. fresh air supply in bars, restaurants,
is designed and manu- discos, offices, banks, shops, work-
factured with the “standard” oper- shops, showrooms, smoking areas,
ation side left to the air flow. etc.
Changing the “standard” operation
side is available upon request but
extends the delivery time of the unit
by 1 ÷ 2 weeks.
This mono-block unit provides the
following functions: ventilation, fil-
tering, heat recovery, and heating
and cooling (depending on season
requirements). Thanks to the built-in
refrigerant circuit, oper-
ates as an independent system,
without an outside unit. In order to
deliver a constant fresh air supply,
the unit must function without inter-
ruptions. The secret of our continu-
ous working mode is the absence of
a “defrost” cycle (an important
advantage of in com-
parison to other similar products).
CONSTRUCTION
is a single “1 piece” Sound Insulation Material - The wet components where con-
(standalone) unit consisting of alu- open cell Polyurethane foam, self- densation may occur (such as the
minum profiles, fastenings, con- extinguishing and impregnated, DX coils and plate heat exchanger)
necting angles and decorative type Class 1. Standard used: are equipped with drain pans. The
corks which shape the casing. sheets with a Density of 25kg/m3 condensate is taken away through
and a Thickness of 10mm. special openings, located on the
Side Panels - single skin, manufac- • Option - For advanced / maxi- bottom of the unit.
tured from 1.2mm galvanised mized sound absorbing, insulation
sheet steel mounted to supporting material with improved shape and
columns with bolts. Side panels are thicknesses of 30, 40 50mm are
internally lined with sound insula- available upon request.
tion material only.
FANS
Direct driven, double suction, cen- inverter from the company Ziehl-
trifugal fans with 3 speed motors are Abegg can be used. The fan wheel is
fitted as standard. Each fan wheel is statically and dynamically balanced
statically and dynamically balanced on the axis of the direct-driven
on the axis of the direct-driven elec- motor. Both the fan wheel and the
tric motor. Both the fan wheel and motor are mounted on a common
the motor are mounted on a com- base frame with vibration dampers. Innovation at a glance:
mon base frame with vibration
dampers. Using EC Blue Plug Fans the • Significant weight reduction, which
When higher static pressures or lower ensures the highest IE4 reduces motor bearing loads and increases
sound noise levels are required, EC Premium Efficiency and ErP conform- the system service life
(Electronically Commutated) Blue ity - 2015/EC controller integrated. • Drastic reduction in noise generation
Plug Fans - with a Cpro frequency The high-performance composite leads to tonal noise reduction up to 5 dB
material Cpro ZAmid® (developed • Significant increase of the impeller effi-
using the latest insights), makes the ciency which reduces the absorbed power
impeller significantly lighter than • Reduced power consumption - up to 15%
those made of steel and offers supe- energy savings during operation
• Significant CO2 reduction, improved
rior mechanical properties. ZAmid®
mechanical properties (in comparison with
provides new opportunities for sys-
steel)
tem runtimes, enables lower power
• No welded seams - high peripheral veloc-
consumption and leads to a drastic
ities up to 70 m/s
reduction in noise. Cpro ZAmid® is • Suitable for operational temperatures
manufactured using a one - shot from -20°C to +80°C (in comparison with
injection-moulding process in a highly steel impellers)
complex injection-moulding machine • Corrosion-free
which results in no welded joints. This • No toxic gas emissions
highly technical process ensures the • Colour-stable
highest system reliability.
PLATE HEAT EXCHANGER
EUROVENT Certificate:
03.01.242.
REFRIGERANT
CIRCUIT ñ
SEMI-HERMETIC
The heat pump has 1 circuit and uses The main components of the refrig- All of the units contain
an eco-friendly refrigerant (R407C). erant circuit are: thermal expansion high efficiency direct expansion coils
A “Scroll” compressor is used in valve, check valves, solenoid valves, made from copper tubes with alu-
2 and a “Rotary” com- filter dryer, receiver, suction line minum fins and a condensate drain
pressor is used in 1. accumulator, thermostats (high/low pan. Each coil is dual-mode
It is possible to add capacity control - pressure), differential pressure (reversible) and depending on the
(optional). This option requires the transmitter (high/low pressure) and operation mode (heating or cooling)
unit to be equipped with Plug Fans etc. of the unit, works as an evaporator /
which have a built-in frequency condenser.
inverter.
R407C
EUROVENT Certificate N:
10.02.450.
AUTOMATION SYSTEM
The unit is managed through an electric switchboard located on the
operation side of the unit. It includes a pre-programmed controller
which manages all modes of the unit, as well as the power and
relay-contact equipment. The automation system is standard in
each unit and has an additional LCD display with built-in tempera-
ture sensor, which is normally mounted into the room.
The unit is designed to treat Ventilation - when the space does not
fresh air for the room needs, and to pro- require heating or cooling, the heat pump
vide a comfortable temperature of the sup- is switched off and the unit provides
ply air. Heating, cooling and dehumidifica- untreated fresh air to the space.
tion, or ventilation modes can be operated
automatically or manually. Recirculation (Optional – only for winter
mode) – This mode is possible only if an
Heating - the unit heats the supply air to additional mixing box is mounted to the
the required temperature. When the set body of the unit. It is only used during
point has been reached the unit switches to defrosting of the evaporator and the plate
ventilation mode. heat exchanger in heating mode at low
external temperatures and air supply tem-
Cooling - the unit cools the supply air to perature. The dampers of the fresh air and
the required temperature. When the set extract air close and the recirculation’s
point has been reached the unit switches to damper opens. One and the same air goes
ventilation mode. through the unit - air from the room.
FILTERS
For normal operation of the air han-
dling unit and to prevent contamina- The filters for fresh and extract air
tion of the components, air filters are mounted outside of the unit on
are installed at the entrance of the the duct openings for easy access
unit. and maintenance.
Replacing the filters is quick, requires
Filter medium composition: no special knowledge and there is no
Polyurethane with possibility for risk to the operator (all of which min-
regeneration (washable) imizes high labor costs).
Class of filtration: G2
Cassette thickness: 20 mm
DV_Select
DV_Select is the specialized software used for technical cal-
culations of the “e-conomizer”.
• Friendly interface
• Light, fast and easy to work with, minimum input data
• Winter/Summer mode calculations
• Technical data and drawing printouts can be exported
to a PDF file
• Visualisation of the processes in the Mollier’s diagram
• Printouts consist of detailed info for: pressure drops
for all components, plate exchanger, evaporator and
condenser, compressor, fans, sound pressure level and
dimension and weights
• General data includes the most important parameters
of the unit such as: Total cooling/heating Capacity
(kW), Supply air temperature (°C), Total Power Input
(kW), System COP/EER, Specific Fan Power (SFP) - total
for unit (W/m3/s), Refrigerant type and more …
ADVANTAGES
For investors:
• Initial investment cost reduction
• Installed electricity power reduction
• Lower operating (energy) costs
• Saves space - artificial ceilings
• Absence of “defrost” mode and maintains continuous working of the unit
• Easy maintenance – only one unit
• Internet monitoring
• 100% test in factory conditions
• Low sound parameters
For designers/consultants:
• Selection software is available
• Saving time during the process of design
• Flexibility when there is lack of space
• Fast and easy calculations for yearly operation (energy) costs
• Absence of “defrost” mode
The capital cost of compared with the conventional air cooled heat pump is equivalent
or lower! The benefits of lower energy consumption with the brings immediate cost savings!
1 2
General Technical Data
Speed1 Speed2 Speed3 Speed1 Speed2 Speed3
External pressures for standard with direct driven, double suction, centrifugal fans with 3 speed motors
1 2
SUPPLY SUPPLY
EXHAUST EXHAUST
I speed 134Pa - - 246Pa - -
II speed 234Pa 107Pa - 352Pa 188Pa -
III speed 254Pa 187Pa 33Pa 392Pa 318Pa 108Pa
1 2
Type weight
with
A B Ïixing
box
Type weight
mixing box
mixing box
is the subject of continuing improvement
and future development! Following its policy of continuous
improvement, reserves the right to make any
further changes without the need to inform its customers
and partners about it.